Plan Review Details - Permit 22100177
Plan Review Stops For Permit 22100177
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-05 Cont ID  
Sent By rmcphers Date 2023-07-05 Time 11:20 Rev Time 0.00
Received By rmcphers Date 2023-07-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 10:06 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 09:41 Sent To  
Notes
2023-04-19 09:50:24POOL SPA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP.001, SP.002, SP.120, SP.230, SP.700,
 SP.730, 2.51, 2.52, 2.53 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - PLEASE SEE THE SIGNATURE
 REVIEW FOR A COMPLETE LIST OF DRAWINGS THAT DO NOT SHOW
 AS DIGIALLY SIGNED - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By rmcphers Date 2022-12-14 Time 16:28 Rev Time 0.00
Received By rmcphers Date 2022-12-14 Time 16:20 Sent To  
Notes
2022-12-14 16:27:54POOL SPA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE MAXIMUM STEP RISER IS 10" - FBC 454.1.2.5.3
  
 2) DRAWING SP.001 SHOWS THE CODE VERSION USED FOR
 DESIGN AS 2017 FBC - DRAWING 2.51 SHOWS THE 2014 FBC -
 PLEASE SHOW THE CORRECT CODE VERSION.
  
 3) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-01 Cont ID  
Sent By rperdomo Date 2023-05-01 Time 09:15 Rev Time 0.00
Received By rperdomo Date 2023-05-01 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rperdomo Date 2022-11-07 Time 07:13 Sent To  
Notes
2022-11-07 10:09:50FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 - FOLLOW REQUIREMENTS OF NEC 2017 ARTICLE 680
 - ONE LINE DIAGRAM SHOWINGS GROUNDING (BONDING),
 EQUIPMENT GROUNDING, AND EQUIPOTENTIAL BONDING.
  
 RUBEN P. PERDOMO
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 10:58 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 17:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By ccole Date 2023-04-19 Time 10:27 Rev Time 0.00
Received By ccole Date 2023-04-19 Time 10:15 Sent To  
Notes
2023-04-19 10:28:362ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100177
 4/19/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS
 AND NOTE GAS CAN BE SUBMITTED AS A REVISION TO THE
 MASTER PLAN UNDER PERMIT 18100540. IF THIS OPTION IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE REVISION SUBMITTAL.
  
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEETS P.700: THE RISER BRANCH THAT
 CORRELATES TO KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON
 THE DRAWING. PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 INVOLVED WITH SUPPLYING THE GAS HEATER AND OTHER
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 THE RISER IS INCOMPLETE BECAUSE IT DOES NOT INCLUDE THE
 LOW PRESSURE PIPING SYSTEM FROM THE REGULATORS TO THE
 POOL HEATERS. A COMPLETE RISER PER COMMENT #1 ABOVE IS
 REQUIRED.
  
 5) FAILED. P.509: SHOW THE GAS VENT PIPING RUN AND
 TERMINATION LOCATION FROM THE EQUIPMENT ROOM BY
 GRIDLINES 10 & K- SEC. 410.3 FBC FG.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.105C WHICH WAS NOT UPLOADED FOR REVIEW.
  
 6) FAILED. P.509: PLEASE SUBMIT SHEET P.804 THAT
 CONTAINS THE GAS MONITORING AND DETECTING DETAILS
 CALLED OUT ON THE PLAN- SEC. 107.2.1 WPB.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.804 WHICH WAS NOT UPLOADED FOR REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By ccole Date 2022-11-16 Time 09:00 Rev Time 0.00
Received By ccole Date 2022-11-16 Time 09:00 Sent To  
Notes
2022-11-16 09:01:501ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100177
 11/16/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION IS
 FOR THE HOTEL SPA WHICH HAS A GAS-FIRED POOL HEATER,
 HOWEVER SINCE SHEET P.509 & P.700 SHOWS MULTIPLE POOL
 HEATERS FOR THE INDOOR POOL AND SPAS THE APPLICANTS
 SHOULD CONSIDER SUBMITTING A SEPARATE PERMIT
 APPLICATION FOR GAS THAT INCLUDES ALL THE GAS WORK
 RELATING TO THE POOLS AND SPAS. IF A SEPARATE PERMIT IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE SEPARATE PERMIT.
 PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU HAVE
 QUESTIONS..
  
 1) SHEETS P.700: THE RISER BRANCH THAT CORRELATES TO
 KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON THE DRAWING.
 PLEASE PROVIDE A COMPLETE GAS RISER DRAWING THAT
 INCLUDES ALL NEW AND EXISTING GAS PIPING INVOLVED WITH
 SUPPLYING THE GAS HEATER AND OTHER APPLIANCES- SECTIONS
 401.3 & 401.4 FBC FG. REFER TO FBC CHAPTER 4 FUEL FBC-
 THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 2) SP.420, P.509, P.700: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL HEATER- SEC.617.1 FBC FG.
  
 3) SP.420, P.509, P.700: INDICATE HOW COMBUSTION AIR
 WILL BE PROVIDED TO THE HEATER AND SHOW CALCULATIONS
 FOR INDOOR AIR IF APPLICABLE- SEC. 304.1 FBC FG.
  
 4) SP.420, P.509, P.700: PROVIDE A VENTING PLAN FOR THE
 HEATER- SEC. 503.1 FBC FG.
  
 5) P.509: PLEASE INDICATE WHICH FLOOR LEVELS THE
 EQUIPMENT ROOMS ARE ON- SEC. 107.2.1 WPB.
  
 6) P.509: SHOW THE GAS VENT PIPING RUN AND TERMINATION
 LOCATION FROM THE EQUIPMENT ROOM BY GRIDLINES 10 & K-
 SEC. 410.3 FBC FG.
  
 7) P.509: PLEASE SUBMIT SHEET P.804 THAT CONTAINS THE
 GAS MONITORING AND DETECTING DETAILS CALLED OUT ON THE
 PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-20 Cont ID  
Sent By hmoser Date 2023-07-20 Time 10:57 Rev Time 0.00
Received By hmoser Date 2023-07-03 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 05:58 Rev Time 0.00
Received By medwards Date 2023-04-18 Time 17:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-14 Cont ID  
Sent By rmcphers Date 2022-12-14 Time 16:31 Rev Time 0.00
Received By rmcphers Date 2022-10-28 Time 12:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By hmoser Date 2023-07-20 Time 10:56 Rev Time 0.00
Received By hmoser Date 2023-07-20 Time 10:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 05:57 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 05:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 10:58 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 17:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By ccole Date 2023-04-19 Time 10:24 Rev Time 0.00
Received By ccole Date 2023-04-19 Time 10:15 Sent To  
Notes
2023-04-19 10:26:372ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100177
 4/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 #1 & #11 ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET SP.003 & SP.620: REFER TO SEC.
 454.1.1.1 FBC B AND PROVIDE THE FOLLOWING INFORMATION
 ON THE PLAN.
 A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT
 OCCUPANTS OF THE FACILITY.
 B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED.
  
 SHEETS SP.001 & SP.002: PLEASE CORRECT THE CALCULATIONS
 SO THEY CLEARLY INDICATE (TRANSIENT UNITS- 5 BATHERS
 PER TRANSIENT UNIT), AND (NON-TRANSIENT UNITS- 7
 BATHERS PER TRANSIENT UNIT)- SEC. 454.1.1.1 FBC B.
 CORRECT THE MIAMI LOCATION TO WEST PALM BEACH.
  
 11) FAILED. P.509: PLEASE REMOVE THE NOTE REQUIRING
 SEPARATE PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 &
 608.16 FBC P.
  
 SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
 PLEASE PROVIDE THE REQUESTED COMPLIANCE INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By ccole Date 2022-11-16 Time 08:52 Rev Time 0.00
Received By ccole Date 2022-11-16 Time 07:47 Sent To  
Notes
2022-11-16 08:53:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100177
 11/16/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THE FOLLOWING
 COMMENTS WITH THE EXCEPTION OF COMMENT #1 ARE INTENDED
 FOR THE SPA ONLY
  
 1) SHEETS SP.001 & A1.108: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE WITH
 TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC.
 454.1.8.1 FBC B. THE FLOOR PLAN APPEARS TO SHOW THE
 BATHROOMS ADJACENT TO THE POOL DECK WILL ALSO BE USED
 BY OCCUPANTS OF THE OUTDOOR BAR. PLEASE SEE THE
 EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF APPLICABLE
 THEN THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE
 DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE
 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE
 THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE
 BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO
 CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE.
 PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS-
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SECS. 454.1.6.1.1 & 454.1.6.1.3: CONFIRM WITH
 DETAILS AND/OR NOTES THAT EACH BATHROOM CONTAINS A
 DIAPER CHANGING STATION AND A FLOOR DRAIN.
 C) SEC. 454.1.6.1.2: THE RESTROOMS ARE DO NOT APPEAR TO
 BE VISIBLE FROM ALL PORTIONS OF THE DECK. SHOW THE
 LOCATIONS OF DIRECTIONAL SIGNS FOR THE BATHROOM
 2) SP.210 DETAIL 7: SHOW THE WALL INLET LOCATION IS A
 MINIMUM OF 12-INCHES BELOW THE NORMAL OPERATING WATER
 LEVEL- SECS. 454.1.8.1 & 454.1.6.5.9 FBC B.
  
 3) SP.220 & SP.730: PLEASE PROVIDE TDH CALCULATIONS FOR
 PUMP SIZING- SEC. 454.1.8.1 454.1.6.5.4 FBC B.
  
 4) SP.220: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE COLLECTOR TANK, AND INCLUDE AN
 EQUIPMENT SCHEDULE- SEC. 608.3 & 608.16 FBC P & SEC.
 454.1.6.3 FBC B.
  
 5) SP.220: THE PIPING PLANS SHOW SPA WASTEWATER
 DRAINING INTO THE SANITARY SYSTEM WHICH IS PROHIBITED-
 SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE DRAWINGS
 ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING INTO THE
 STORM. PLEASE REVIEW THE FOLLOWING INFORMATION AND
 REVISE THE PLAN ACCORDINGLY.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER' S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 6) SP.509 & SP.710: THE EMERGENCY SHOWER AND EYEWASH
 STATIONS SHALL CONFORM TO ISEA Z358.1. SUBMIT
 MANUFACTURER' S SPECIFICATIONS TO VERIFY COMPLIANCE.
 A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT,
 THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P.
  
 7) SP.200: SUBMIT MANUFACTURER' S SPECIFICATIONS FOR
 THE SPA LIFT SHOWING COMPLIANCE WITH SECS. 1009.1-
 1009.2.9 FBC ACC. PLEASE NOTE THE SPECS CAN BE A
 DEFERRED SUBMITTAL PER SEC. 107.3.4.1 WPB.
  
 8) SP.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE
 PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16
 FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 9) P.210: PLEASE NOTE- SEC. 454.1.8.15.
 IF A SPA IS EQUIPPED WITH AN EMERGENCY CUTOFF OR KILL
 SWITCH, IT SHALL INCLUDE PROVISIONS FOR A MINIMUM 80
 DECIBEL AUDIBLE ALARM NEAR THE SPA TO SOUND
 CONTINUOUSLY UNTIL DEACTIVATED WHEN SUCH DEVICE IS
 TRIGGERED. THE FOLLOWING ADDITIONAL RULE SIGN SHALL BE
 INSTALLED TO BE VISIBLE BY THE SPA WHICH READS "ALARM
 INDICATES SPA PUMPS OFF. DO NOT USE SPA WHEN ALARM
 SOUNDS UNTIL ADVISED OTHERWISE".
  
 10) SP.220: PROVIDE A SPA EQUIPMENT SUBMITTAL PACKAGE
 THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN
 THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLREASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-07-05 Cont ID  
Sent By rmcphers Date 2023-07-05 Time 11:20 Rev Time 0.00
Received By rmcphers Date 2023-07-05 Time 11:20 Sent To  
Notes
2023-07-05 11:21:20SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS E.205C, E.622, P.700 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - PLEASE SEE THE
 SIGNATURE REVIEW FOR A COMPLETE LIST OF DRAWINGS THAT
 DO NOT SHOW AS DIGIALLY SIGNED - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 09:55 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 09:55 Sent To  
Notes
2023-04-19 09:55:32SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP.001, SP.002, SP.120, SP.230, SP.700,
 SP.730, 2.51, 2.52, 2.53, E.622, P.700, M.205C, M.206C,
 M.207A, M.265, M.266 DO NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER - PLEASE SEE THE SIGNATURE REVIEW FOR A
 COMPLETE LIST OF DRAWINGS THAT DO NOT SHOW AS DIGIALLY
 SIGNED - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By rmcphers Date 2022-12-14 Time 16:30 Rev Time 0.00
Received By rmcphers Date 2022-12-14 Time 16:30 Sent To  
Notes
2022-12-14 16:31:34SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-25 Cont ID  
Sent By ckimmerl Date 2023-04-25 Time 12:00 Rev Time 0.00
Received By ckimmerl Date 2023-04-25 Time 11:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By ckimmber Date 2022-11-21 Time 15:43 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 15:43 Sent To  
Notes
***NONE***