Plan Review Details - Permit 22100176
Plan Review Stops For Permit 22100176
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-08-03 Cont ID  
Sent By rmcdouga Date 2023-08-03 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2023-07-20 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-27 Cont ID  
Sent By rmcdouga Date 2023-04-27 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2023-04-27 Time 09:41 Sent To  
Notes
2023-04-27 11:34:41PLAN REVIEW COMMENTS
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IT APPEARS THAT YOUR CALCULATIONS ON SHEET SP.400
 ARE NOT CORRECT. THE SPA IS 12.5' X 9.0'. THE SURFACE
 OF THE POOL WATER IS 112.5 SQUARE FEET IN AREA WHICH IS
 LESS THAN 120 SQUARE FEET. THE TOTAL PERIMETER OF THE
 POOL IS 34'. THE CONTINOUS 4 FT WIDE DECK CAN BE FIFTY
 PERCENT OF 34' OR 17'. THE DRAWINGS APPEAR TO SHOW THAT
 HALF OF THE PERIMETER OF THE POOL SPA HAS A CONTINOUS
 DECK AT LEAST 4' WIDE. HOWEVER, THERE APPEARS TO BE
 SOME OBSTRUCTIONS TO THE POOL ON THE 50 PERCENT THAT
 YOU ARE CALLING UNOBSTRUCTED. YOU NEED TO REVISE YOUR
 CALCULATIONS AND MAKE SURE THERE ARE NO OBSTRUCTIONS
 FOR THE HALF OF THE DECK THAT IS NOT PLANTER. FBC
 454.1.8.5 DECKS. DECKS SHALL HAVE A MINIMUM 4-FOOTWIDE
 (1219 MM) UNOBSTRUCTED WIDTH AROUND THE ENTIRE POOL
 PERIMETER EXCEPT THAT POOLS OF LESS THAN 120 SQUARE
 FEET (11 M2) OF POOL WATER SURFACE AREA SHALL HAVE A
 MINIMUM 4-FOOT-WIDE (1219 MM) UNOBSTRUCTED CONTINUOUS
 DECK AROUND A MINIMUM OF 50 PERCENT OF THE POOL
 PERIMETER. DECKS LESS THAN 4 FEET (1219 MM) WIDE SHALL
 HAVE BARRIERS TO PREVENT THEIR USE. DECKS SHALL NOT BE
 MORE THAN 10 INCHES (254 MM) BELOW THE TOP OF THE POOL.
 FOR POOLS OF 120 SQUARE FEET (11 M2) OR GREATER, 10
 PERCENT OF THE DECK ALONG THE POOL PERIMETER MAY BE
 OBSTRUCTED.
  
 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-11-08 Cont ID  
Sent By rperdomo Date 2022-11-08 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2022-11-07 Time 15:32 Sent To  
Notes
2022-11-01 16:30:36 
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-01 Cont ID  
Sent By rperdomo Date 2023-05-01 Time 09:34 Rev Time 0.00
Received By rperdomo Date 2023-05-01 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rperdomo Date 2022-11-01 Time 16:44 Rev Time 0.00
Received By rperdomo Date 2022-11-01 Time 16:44 Sent To  
Notes
2022-11-01 16:43:41FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 - FOLLOW REQUIREMENT OF NEC 2017 ARTICLE 680.40 PART IV
 SPAS AND HOT TUBS.
 - ONE LINE DIAGRAM SHOWINGS BONDING AND EQUIPMENT
 GROUNDING, AND EQUIPOTENTIAL BONDING.
  
 RUBEN PEREZ PERDOMO
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 10:51 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 17:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By ccole Date 2023-04-19 Time 10:12 Rev Time 0.00
Received By ccole Date 2023-04-19 Time 09:59 Sent To  
Notes
2023-04-19 10:12:562ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100176
 4/19/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS
 AND NOTE GAS CAN BE SUBMITTED AS A REVISION TO THE
 MASTER PLAN UNDER PERMIT 18100540. IF THIS OPTION IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE REVISION SUBMITTAL.
  
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEETS P.700: THE RISER BRANCH THAT
 CORRELATES TO KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON
 THE DRAWING. PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 INVOLVED WITH SUPPLYING THE GAS HEATER AND OTHER
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 THE RISER IS INCOMPLETE BECAUSE IT DOES NOT INCLUDE THE
 LOW PRESSURE PIPING SYSTEM FROM THE REGULATORS TO THE
 POOL HEATERS. A COMPLETE RISER PER COMMENT #1 ABOVE IS
 REQUIRED.
  
 5) FAILED. P.509: SHOW THE GAS VENT PIPING RUN AND
 TERMINATION LOCATION FROM THE EQUIPMENT ROOM BY
 GRIDLINES 10 & K- SEC. 410.3 FBC FG.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.105C WHICH WAS NOT UPLOADED FOR REVIEW.
  
 6) FAILED. P.509: PLEASE SUBMIT SHEET P.804 THAT
 CONTAINS THE GAS MONITORING AND DETECTING DETAILS
 CALLED OUT ON THE PLAN- SEC. 107.2.1 WPB.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.804 WHICH WAS NOT UPLOADED FOR REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-15 Cont ID  
Sent By ccole Date 2022-11-15 Time 16:47 Rev Time 0.00
Received By ccole Date 2022-11-15 Time 16:34 Sent To  
Notes
2022-11-15 16:49:491ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100176
 11/15/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION IS
 FOR THE SPA WHICH HAS A GAS-FIRED POOL HEATER, HOWEVER
 SINCE SHEET P.509 & P.700 SHOWS MULTIPLE POOL HEATERS
 FOR THE INDOOR POOL AND SPAS THE APPLICANTS SHOULD
 CONSIDER SUBMITTING A SEPARATE PERMIT APPLICATION FOR
 GAS THAT INCLUDES ALL THE GAS WORK RELATING TO THE
 POOLS AND SPAS. IF A SEPARATE PERMIT IS CHOSEN I WILL
 PLACE AN "N" RESULT (NO REVIEW) FOR GAS AND PERFORM THE
 REVIEW UNDER THE SEPARATE PERMIT.
 PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU HAVE
 QUESTIONS..
  
 1) SHEETS P.700: THE RISER BRANCH THAT CORRELATES TO
 KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON THE DRAWING.
 PLEASE PROVIDE A COMPLETE GAS RISER DRAWING THAT
 INCLUDES ALL NEW AND EXISTING GAS PIPING AND
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 2) SP.420, P.509, P.700: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL HEATER- SEC.617.1 FBC FG.
  
 3) SP.420, P.509, P.700: INDICATE HOW COMBUSTION AIR
 WILL BE PROVIDED TO THE HEATER AND SHOW CALCULATIONS
 FOR INDOOR AIR IF APPLICABLE- SEC. 304.1 FBC FG.
  
 4) SP.420, P.509, P.700: PROVIDE A VENTING PLAN FOR THE
 HEATER- SEC. 503.1 FBC FG.
  
 5) P.509: PLEASE INDICATE WHICH FLOOR LEVELS THE
 EQUIPMENT ROOMS ARE ON- SEC. 107.2.1 WPB.
  
 6) P.509: SHOW THE GAS VENT PIPING RUN AND TERMINATION
 LOCATION FROM THE EQUIPMENT ROOM BY GRIDLINES 10 & K-
 SEC. 410.3 FBC FG.
  
 7) P.509: PLEASE SUBMIT SHEET P.804 THAT CONTAINS THE
 GAS MONITORING AND DETECTING DETAILS CALLED OUT ON THE
 PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-08-03 Cont ID  
Sent By rmcdouga Date 2023-08-03 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2023-07-03 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 05:28 Rev Time 0.00
Received By medwards Date 2023-04-18 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By lmarchan Date 2022-11-22 Time 13:25 Rev Time 0.00
Received By lmarchan Date 2022-10-28 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By hmoser Date 2023-07-20 Time 10:50 Rev Time 0.00
Received By hmoser Date 2023-07-20 Time 10:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 05:28 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 05:28 Sent To  
Notes
2023-05-02 05:28:38 
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 10:51 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 17:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By ccole Date 2023-04-19 Time 10:01 Rev Time 0.00
Received By ccole Date 2023-04-19 Time 09:59 Sent To  
Notes
2023-04-19 10:07:492ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100176
 4/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 #1 & #11 ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET SP.003 & SP.620: REFER TO SEC.
 454.1.1.1 FBC B AND PROVIDE THE FOLLOWING INFORMATION
 ON THE PLAN.
 A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT
 OCCUPANTS OF THE FACILITY.
 B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED.
  
 SHEETS SP.001 & SP.002: PLEASE CORRECT THE CALCULATIONS
 SO THEY CLEARLY INDICATE (TRANSIENT UNITS- 5 BATHERS
 PER TRANSIENT UNIT), AND (NON-TRANSIENT UNITS- 7
 BATHERS PER TRANSIENT UNIT)- SEC. 454.1.1.1 FBC B.
 CORRECT THE MIAMI LOCATION TO WEST PALM BEACH.
  
 11) FAILED. P.509: PLEASE REMOVE THE NOTE REQUIRING
 SEPARATE PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 &
 608.16 FBC P.
  
 SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
 PLEASE PROVIDE THE REQUESTED COMPLIANCE INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-15 Cont ID  
Sent By ccole Date 2022-11-15 Time 16:28 Rev Time 0.00
Received By ccole Date 2022-11-04 Time 16:19 Sent To  
Notes
2022-11-15 16:30:081ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100176
 11/15/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP.002: REFER TO SEC. 454.1.1.1 FBC B AND
 PROVIDE THE FOLLOWING INFORMATION ON THE PLAN.
 A) SPA IS FOR USE BY OCCUPANTS OF A TRANSIENT OR
 NON-TRANSIENT FACILITY.
 B) BATHING LOAD CALCULATION.
  
 2) SP.002: PLEASE LABEL THE BATHROOMS BY THE POOL AND
 SPA AS MEN'S AND WOMEN'S POOL AND SPA BATHROOMS AND
 PROVIDE FIXTURE CALCULATIONS IN ACCORDANCE WITH SECTION
 454.1.8.1 AND TABLE 454.1. 454.1.6.1.1. PROVIDE A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES FOR MALE AND FEMALE USE.
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SEC. 454.1.6.1.3: CONFIRM WITH DETAILS AND/OR NOTES
 THAT EACH BATHROOM CONTAINS A FLOOR DRAIN.
 C) SEC. 454.1.6.1.4: SHOW THE LOCATIONS OF REQUIRED
 HOSE BIBS WITHIN 25 FT. OF EACH BATHROOM AND NOTE THAT
 EACH WILL BE EQUIPPED WITH A VACUUM BREAKER.
 D) SEC. 454.1.6.1.2: THE POOL AND SPA BATHROOMS DO NOT
 APPEAR TO BE VISIBLE FROM ALL PORTIONS OF THE DECK.
 SHOW THE LOCATIONS OF DIRECTIONAL SIGNS FOR THE
 BATHROOM.
  
 3) SP.410 DETAIL 7: SHOW THE WALL INLET LOCATION IS A
 MINIMUM OF 12-INCHES BELOW THE NORMAL OPERATING WATER
 LEVEL- SECS. 454.1.8.1 & 454.1.6.5.9 FBC B.
  
 5) SP.420 & SP.470: PLEASE PROVIDE TDH CALCULATIONS FOR
 PUMP SIZING- SEC. 454.1.8.1 454.1.6.5.4 FBC B.
  
 6) SP.420: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE COLLECTOR TANK, AND INCLUDE AN
 EQUIPMENT SCHEDULE- SEC. 608.3 & 608.16 FBC P & SEC.
 454.1.6.3 FBC B.
  
 7) SP.420: PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE MAIN DRAIN GRATES AND SUMPS SHOWING COMPLIANCE
 WITH SEC. 454.1.6.5.10.2 AND ANSI/APSP 16. PLEASE NOTE
 THE SPECS CAN BE A DEFERRED SUBMITTAL PER SEC.
 107.3.4.1 WPB.
  
 8) SP.4.20: THE PIPING PLANS SHOW SPA WASTEWATER
 DRAINING INTO THE SANITARY SYSTEM WHICH IS PROHIBITED-
 SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE DRAWINGS
 ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING INTO THE
 STORM. PLEASE REVIEW THE FOLLOWING INFORMATION AND
 REVISE THE PLAN ACCORDINGLY.
  
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 9) SP.509 & SP.710: THE EMERGENCY SHOWER AND EYEWASH
 STATIONS SHALL CONFORM TO ISEA Z358.1. SUBMIT
 MANUFACTURER' S SPECIFICATIONS TO VERIFY COMPLIANCE.
 A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT,
 THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P.
  
 10) SP.400: SUBMIT MANUFACTURER" S SPECIFICATIONS FOR
 THE POOL LIFT SHOWING COMPLIANCE WITH SECS. 1009.1-
 1009.2.9 FBC ACC. PLEASE NOTE THE SPECS CAN BE A
 DEFERRED SUBMITTAL PER SEC. 107.3.4.1 WPB.
  
 11) SP.520: PLEASE REMOVE THE NOTE REQUIRING SEPARATE
 PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16
 FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 12) P.410: PLEASE NOTE- SEC. 454.1.8.15.
 IF A SPA IS EQUIPPED WITH AN EMERGENCY CUTOFF OR KILL
 SWITCH, IT SHALL INCLUDE PROVISIONS FOR A MINIMUM 80
 DECIBEL AUDIBLE ALARM NEAR THE SPA TO SOUND
 CONTINUOUSLY UNTIL DEACTIVATED WHEN SUCH DEVICE IS
 TRIGGERED. THE FOLLOWING ADDITIONAL RULE SIGN SHALL BE
 INSTALLED TO BE VISIBLE BY THE SPA WHICH READS "ALARM
 INDICATES SPA PUMPS OFF. DO NOT USE SPA WHEN ALARM
 SOUNDS UNTIL ADVISED OTHERWISE."
  
 13) SP.002 & SP.400: SHOW THE WIDTH OF THE DECKS AROUND
 THE SPA IN ACCORDANCE WITH SEC. 454.1.8.5 FBC B.
  
 14) P.107D: THE POOL ON THE PLAN IS UNDER A SEPARATE
 PERMIT HOWEVER THE "SULLAGE POOL WATER"DRAINAGE SHALL
 COMPLY WITH COMMENT 9 ABOVE.
  
 15) SP.420: PROVIDE A SPA EQUIPMENT SUBMITTAL PACKAGE
 THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN
 THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLREASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 10:45 Rev Time 0.00
Received By ccole Date 2023-07-06 Time 09:32 Sent To  
Notes
2023-07-06 10:49:05ELECTRONIC SIGNATURE REVIEW
 PERMIT- 22100176
 7/6/23
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP.002, E.205C, E.627, & P.700 DO NOT BEAR
 VERIFIABLE DIGITAL SIGNATURES AND SEALS BY THE
 ENGINEERS OF RECORD- FL. STATUTE 471.025 AND SEC.
 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-27 Cont ID  
Sent By rmcdouga Date 2023-04-27 Time 11:47 Rev Time 0.00
Received By rmcdouga Date 2023-04-27 Time 11:47 Sent To  
Notes
2023-04-27 11:58:44NOT ALL OF THE PLANS THAT WERE SUBMITTED ARE DIGITALLY
 SIGNED BY THE ENGINEER OR THE DIGITAL SIGNATURE CAN NOT
 BE VERIFIED. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By rmcdouga Date 2022-11-07 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2022-11-07 Time 16:03 Sent To  
Notes
2022-11-07 16:04:53THE PLANS ARE NOT DIGITALLY SIGNED BY THE ENGINEER OR
 THE DIGITAL SIGNATURE CAN NOT BE VERIFIED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-25 Cont ID  
Sent By ckimmerl Date 2023-04-25 Time 11:58 Rev Time 0.00
Received By ckimmerl Date 2023-04-25 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By ckimmerl Date 2022-11-21 Time 15:20 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 15:20 Sent To  
Notes
***NONE***