Plan Review Details - Permit 22100087
Plan Review Stops For Permit 22100087
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-03-10 Cont ID  
Sent By cpuell Date 2023-03-10 Time 12:20 Rev Time 0.00
Received By cpuell Date 2023-03-10 Time 12:20 Sent To  
Notes
2023-03-10 12:20:31APPLICATION UPDATED

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2023-01-31 Cont ID  
Sent By cpuell Date 2023-01-31 Time 09:01 Rev Time 0.00
Received By cpuell Date 2023-01-31 Time 09:01 Sent To  
Notes
2023-01-31 09:01:49PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-12-16 Cont ID  
Sent By cpuell Date 2022-12-16 Time 10:56 Rev Time 0.00
Received By cpuell Date 2022-12-16 Time 10:56 Sent To  
Notes
2022-12-16 10:56:24PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-08 Cont ID  
Sent By cpuell Date 2022-10-08 Time 09:23 Rev Time 0.00
Received By cpuell Date 2022-10-08 Time 09:23 Sent To  
Notes
2022-10-08 09:29:34APPLICATION AND PLANS LIST THE ADDRESS AS 2700 BROADWAY
 HOWEVER BASED ON THE BUILDING LAYOUT I BELIEVE THE
 CORRECT ADDRESS IS 2708 BROADWAY, ALSO PLEASE LIST THE
 UNIT ADDRESSES EFFECTED BY THIS PERMIT. ALL THE
 PREVIOUS UNIT ADDRESSES WERE RETIRED, NEW UNIT
 ADDRESSES NEED TO BE ASSIGNED. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 THE ADDRESSING ISSUES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date 2023-05-24 Cont ID  
Sent By aoliver Date 2023-05-24 Time 08:34 Rev Time 0.00
Received By aoliver Date 2023-05-24 Time 08:33 Sent To  
Notes
2023-05-24 08:36:18OK PER D BATTLES

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2023-05-10 Cont ID  
Sent By rmcphers Date 2023-05-10 Time 11:28 Rev Time 0.00
Received By rmcphers Date 2023-05-10 Time 11:28 Sent To  
Notes
2023-05-10 11:32:25AN ASBESTOS SURVEY IS NOT REQUIRED - - PLEASE PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON
 LETTERHEAD, STATING THAT THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE
 FOLLOWED, AND THAT NOTIFICATION WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2023-02-01 Cont ID  
Sent By rmcphers Date 2023-02-01 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2023-02-01 Time 10:54 Sent To  
Notes
2023-02-01 10:55:14PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-12-19 Cont ID  
Sent By rmcphers Date 2022-12-19 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2022-12-19 Time 14:55 Sent To  
Notes
2022-12-19 14:55:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By rmcphers Date 2022-11-16 Time 13:04 Rev Time 0.00
Received By rmcphers Date 2022-11-16 Time 13:04 Sent To  
Notes
2022-11-16 13:04:35PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-01 Cont ID  
Sent By rmcphers Date 2023-02-01 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2023-02-01 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-19 Cont ID  
Sent By rmcphers Date 2022-12-19 Time 14:53 Rev Time 0.00
Received By rmcphers Date 2022-12-19 Time 14:53 Sent To  
Notes
2022-12-19 14:53:24ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXISTING TENANT SEPARATION HOURLY
 FIRE RATING - FBC 708.1
  
 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND
 DESIGN - FBC 1603.1.4
  
 3) THE ADDRESS ON THE DRAWINGS NEEDS TO MATCH THE
 ADDRESS OF THE BUILDING.
  
 4) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC
 602.1
  
 5) PLEASE LABEL THE ACCESSIBLE ROOMS - FBC 233.3.4.2
 ALTERATIONS TO INDIVIDUAL RESIDENTIAL DWELLING UNITS.
 IN INDIVIDUAL RESIDENTIAL DWELLING UNITS, WHERE A
 BATHROOM OR A KITCHEN IS SUBSTANTIALLY ALTERED, AND AT
 LEAST ONE OTHER ROOM IS ALTERED, THE REQUIREMENTS OF
 233.3.1 SHALL APPLY TO THE ALTERED RESIDENTIAL DWELLING
 UNITS UNTIL THE TOTAL NUMBER OF RESIDENTIAL DWELLING
 UNITS COMPLIES WITH THE MINIMUM NUMBER REQUIRED BY
 233.3.1.1 AND 233.3.1.2. RESIDENTIAL DWELLING UNITS
 REQUIRED TO COMPLY WITH 233.3.1.1 SHALL BE ON AN
 ACCESSIBLE ROUTE AS REQUIRED BY 206.
  
 6) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER SEAT
 DIMENSION DETAILS FBC A 610.3
  
 7) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER GRAB
 BAR DIMENSION DETAILS FBC A 609
  
 8) ACCESSIBLE BATHROOM = PLEASE SHOW ALL SHOWER DETAILS
 - THRESHOLDS, CONTROLS, GRAB BARS ETC. - DIMENSIONS AND
 LOCATIONS PER FBC 608

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By rmcphers Date 2022-11-16 Time 13:04 Rev Time 0.00
Received By rmcphers Date 2022-11-16 Time 13:04 Sent To  
Notes
2022-11-16 13:28:39ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXISTING TENANT SEPARATION HOURLY
 FIRE RATING - FBC 708.1
  
 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND
 DESIGN - FBC 1603.1.4
  
 3) THE ADDRESS ON THE DRAWINGS NEEDS TO MATCH THE
 ADDRESS OF THE BUILDING.
  
 4) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC
 602.1
  
 5) PLEASE LABEL THE ACCESSIBLE ROOMS - FBC 233.3.4.2
 ALTERATIONS TO INDIVIDUAL RESIDENTIAL DWELLING UNITS.
 IN INDIVIDUAL RESIDENTIAL DWELLING UNITS, WHERE A
 BATHROOM OR A KITCHEN IS SUBSTANTIALLY ALTERED, AND AT
 LEAST ONE OTHER ROOM IS ALTERED, THE REQUIREMENTS OF
 233.3.1 SHALL APPLY TO THE ALTERED RESIDENTIAL DWELLING
 UNITS UNTIL THE TOTAL NUMBER OF RESIDENTIAL DWELLING
 UNITS COMPLIES WITH THE MINIMUM NUMBER REQUIRED BY
 233.3.1.1 AND 233.3.1.2. RESIDENTIAL DWELLING UNITS
 REQUIRED TO COMPLY WITH 233.3.1.1 SHALL BE ON AN
 ACCESSIBLE ROUTE AS REQUIRED BY 206.
  
 6) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER SEAT
 DIMENSION DETAILS FBC A 610.3
  
 7) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER GRAB
 BAR DIMENSION DETAILS FBC A 609
  
 8) ACCESSIBLE BATHROOM = PLEASE SHOW ALL SHOWER DETAILS
 - THRESHOLDS, CONTROLS, GRAB BARS ETC. - DIMENSIONS AND
 LOCATIONS PER FBC 608

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-15 Cont ID  
Sent By mpeterso Date 2023-02-15 Time 10:00 Rev Time 0.00
Received By mpeterso Date 2023-02-15 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 10:58 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 10:58 Sent To  
Notes
2023-01-06 10:58:39PREVIOUS COMMENTS NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-11-18 Cont ID  
Sent By mpeterso Date 2022-11-18 Time 08:56 Rev Time 0.00
Received By mpeterso Date 2022-11-18 Time 08:24 Sent To  
Notes
2022-11-18 10:29:59ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL LOCATIONS OF ALL ELECTRIC SERVICE
 EQUIPMENT AND OUTDOOR AIR CONDITIONING EQUIPMENT ON
 ELECTRICAL FLOOR PLAN. ENSURE INSTALLATION COMPLIES
 WITH NEC 110.26 CLEARANCE REQUIREMENTS AND RECEPTACLE
 LOCATION COMPLIANCE WITH NEC 210.63 AND 210.64
 2) PLEASE PROVIDE A RECEPETACLE AT BATH SINK IN MIDDLE
 AND ADA BATHROM UNITS AS COMPLY WITH NEC 210.60(B)
 3) PLEASE PROVIDE A NOTE STATING INSTALLATION WILL
 COMPLY WITH NEC 210.8 GFI PROTECTION AND 210.12(B) OR
 (C) ARC FAULT PROTECTION
 4) IT APPEARS THE WRONG PANEL SCHEDULE AND LOAD
 CALCULATION SHEETS WERE SUBMITTED. PLEASE PROVIDE THE
 CORRECT SHEETS. FBC 107.2 NEC 215.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-12 Cont ID  
Sent By pleduc Date 2022-10-12 Time   Rev Time 0.00
Received By pleduc Date 2022-10-11 Time 14:04 Sent To  
Notes
2022-10-12 15:19:25FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2022-11-21 Cont ID  
Sent By amhamilt Date 2022-11-21 Time 09:54 Rev Time 0.00
Received By amhamilt Date 2022-11-21 Time 09:54 Sent To  
Notes
2022-11-21 09:54:51SUBJECT BUILDING IS OUTSIDE OF HISTORIC LIMITS ON
 PARCEL.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-24 Cont ID  
Sent By aoliver Date 2023-05-24 Time 08:38 Rev Time 0.00
Received By aoliver Date 2023-05-23 Time 17:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-10 Cont ID  
Sent By rmcphers Date 2023-05-10 Time 11:32 Rev Time 0.00
Received By rmcphers Date 2023-04-27 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-15 Cont ID  
Sent By mpeterso Date 2023-02-15 Time 10:01 Rev Time 0.00
Received By mpeterso Date 2023-01-30 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 10:58 Rev Time 0.00
Received By mpeterso Date 2022-12-15 Time 07:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By lmarchan Date 2022-11-22 Time 13:34 Rev Time 0.00
Received By lmarchan Date 2022-10-07 Time 10:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-05-31 Cont ID  
Sent By lmarchan Date 2023-05-31 Time 12:23 Rev Time 0.00
Received By lmarchan Date 2023-05-24 Time 09:36 Sent To  
Notes
2023-05-31 12:23:105/31/23 NO IMPACT FEES DUE. LEM
2023-05-24 09:37:08EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By rmcphers Date 2022-11-16 Time 13:35 Rev Time 0.00
Received By rmcphers Date 2022-11-16 Time 13:35 Sent To  
Notes
2022-11-16 13:36:01PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-05-12 Cont ID  
Sent By medwards Date 2023-05-09 Time 05:42 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 05:42 Sent To  
Notes
2023-05-09 05:42:38APPROVED ME
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-02-07 Cont ID  
Sent By medwards Date 2023-02-07 Time 10:21 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 10:21 Sent To  
Notes
2023-02-07 10:21:373RD REVIEW FMC
 PERMIT: 22100087
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS AN EXISTING I-2 OCCUPANCY? IF SO THE
 MECHANICAL DESIGN SHALL MEET THE REQUIREMENTS OF ASHRAE
 170-2017. FMC 407
  
 2) IT IS UNCLEAR TO THIS REVIEWER AS TO WHEREIN THE
 BUILDING THIS MECHANICAL WORK WILL BE COMPLETED. LABEL
 THE ROOMS ON THE MECHANICAL SHEET TO MATCH THE ROOM THE
 WORK IS TO BE COMPLETED FROM THE A-202 DRAWING.
  
 3) IS THIS A NEW ADDITION? IS IT A MECHANICAL CHANGE
 OUT? IS IT CREATING NEW ROOMS WITHIN AN EXISTING
 FOOTPRINT? PLEASE HELP ME TO UNDERSTAND THE SCOPE OF
 THIS PROJECT.
  
 4) SHEET M-1.0: THE AHU IS SUPPLING AIR TO THE NEXT
 ROOM FROM WHERE THE AHU IS LOCATED. SHOW THE RETURN AIR
 PATH FROM THIS ROOM BACK TO THE AHU IN THE OTHER ROOM.
 FMC 601.6
  
 5) THE AHU MUST MEET THE NEW FEDERAL GUIDELINES FOR THE
 SEER2 RATINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-30 Cont ID  
Sent By medwards Date 2022-12-30 Time 11:12 Rev Time 0.00
Received By medwards Date 2022-12-30 Time 11:12 Sent To  
Notes
2022-12-30 11:18:17 
  
 1ST REVIEW FMC
 PERMIT: 22100087
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 2ND ATTEMPT TO GET A COMPLETE MECHANICAL DESIGN FOR
 THIS CHANGE OF USE.
  
 1) PLEASE PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS
 CHANGE OF USE FROM AN R-2 TO R-4. THIS SHOULD INCLUDE
 THE REQUIREMENTS IN FMC 403.3.2 FOR R-4 OCCUPANCIES AND
 HEATING LOADS REQUIRED BY FMC 312 AND PROVIDE THE
 ENERGY REQUIREMENTS FROM FEC C403.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-10 Cont ID  
Sent By medwards Date 2022-11-10 Time 10:10 Rev Time 0.00
Received By medwards Date 2022-11-10 Time 10:10 Sent To  
Notes
2022-11-10 10:10:201ST REVIEW FMC
 PERMIT: 22100087
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS
 CHANGE OF USE FROM AN R-2 TO R-4. THIS SHOULD INCLUDE
 THE REQUIREMENTS IN FMC 403.3.2 FOR R-4 OCCUPANCIES AND
 HEATING LOADS REQUIRED BY FMC 312 AND PROVIDE THE
 ENERGY REQUIREMENTS FROM FEC C403.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By rwbrown Date 2022-12-16 Time 09:27 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-02 Cont ID  
Sent By rwbrown Date 2022-11-02 Time 10:22 Rev Time 0.00
Received By rwbrown Date 2022-11-02 Time 10:10 Sent To  
Notes
2022-11-02 10:22:161ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE SUBMIT THE
 PLUMBING PAGES AS REQUIRED. INCLUDE ISOMETRICS FOR THE
 NEW CONNECTION FOR BOTH WATER AND DRAIN, WASTE, VENTS,
 HOT WATER DETAILS, FIXTURE SCHEDULES, ETC.
  
 A FULL PLUMBING REVIEW WAS NOT COMPLETED DUE TO LACK OF
 INFORMATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 05:42 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 05:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-01 Cont ID  
Sent By rmcphers Date 2023-02-01 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2023-02-01 Time 10:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-19 Cont ID  
Sent By rmcphers Date 2022-12-19 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2022-12-19 Time 14:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-16 Cont ID  
Sent By rmcphers Date 2022-11-16 Time 13:38 Rev Time 0.00
Received By rmcphers Date 2022-11-16 Time 13:38 Sent To  
Notes
***NONE***