Plan Review Details - Permit 22091340
Plan Review Stops For Permit 22091340
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2023-01-17 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By jwitmer Date 2022-12-14 Time 11:07 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-14 11:07:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22091340
 ADD: 1120 LINCOLN RD.
 CONT: WINGATE CONSTRUCTION
 TEL: 561-838-4320
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 14TH/2022
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE NOTE THE SET BACK DISTANCES ON
 THE SITE PLAN. THE PROPOSED SITE PLAN DOES NOT SHOW THE
 SETBACK DISTANCE REQUIREMENTS OF THE SIDE SETBACK NOR
 REAR SETBACK.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) 2ND REQUEST. ON THE SITE PLAN PROVIDE THE DISTANCE
 FOR THE SIDE SET BACK, THE ACTUAL WIDTH FOR THE
 PROPOSED MANUFACTURED BUILDING (VARIES FROM 8 FEET TO
 13.88 FEET) AND THE REMAINING DISTANCE TO THE MAIN
 STRUCTURE. THE TOTAL DISTANCE SHOULD ADD UP TO 32 FEET
 AS SHOWN ON THE SITE PLAN. SHOW COMPLIANCE WITH 2020
 FBC-BUILDING TABLE 602 FIRE RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE.
  
 3) COMPLIED, S1.
  
 4) 2ND REQUEST. SUBMIT DOWNLOADED STATE APPROVED PLANS
 AND UPLOAD INTO OUR SYSTEM. THE STATE APPROVED PLAN PSI
 APPROVAL 2015-06-02 IS UNDER THE 2014 FBC-B IS THIS
 SHED A USED SHED AND BEING MOVED FROM A DIFFERENT WIND
 ZONE? 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 5) SUBMIT STATE APPROVED PLAN SEE COMMENT # 4. THE
 STATE APPROVED PLAN PSI APPROVAL 2015-06-02 IS TO SMALL
 AND COPIED TO MANY TIMES. 107.2.1.3. QUALITY OF PLANS.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 6) 2ND REQUEST. PLEASE PROVIDE A COMPLETE SET OF PLANS
 FROM THE FLORIDA STATE MANUFACTURES (MODULAR) BUILDING
 PROGRAM.
 HTTPS://FLORIDABUILDING.ORG
 MANUFACTURED BUILDINGS
 BUILDING TYPE: STORAGE SHED
 MANUFACTURER: SUPERIOR SHEDS, INC.
 AGENCY: INTERTEK-ATI (ARCHITECTURAL TESTING, INC)
 AGENCY PLAN # SSI-2220-14
 THERE WILL BE 13 SHEETS THAT WILL NEED TO BE UPLOADED
 TO OUR SYSTEM
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 13:40 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-01 13:40:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22091340
 ADD: 1120 LINCOLN RD.
 CONT: WINGATE CONSTRUCTION
 TEL: 561-838-4320
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 01/2022
 ACTION: DENIED
  
 1) THE PROPOSED SITE PLAN DOES NOT SHOW THE SETBACK
 DISTANCE REQUIREMENTS OF THE SIDE SETBACK NOR REAR
 SETBACK.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) ON THE SITE PLAN PROVIDE THE DISTANCE FOR THE SIDE
 SET BACK, THE ACTUAL WIDTH FOR THE PROPOSED
 MANUFACTURED BUILDING (VARIES FROM 8 FEET TO 13.88
 FEET) AND THE REMAINING DISTANCE TO THE MAIN STRUCTURE.
 THE TOTAL DISTANCE SHOULD ADD UP TO 32 FEET AS SHOWN ON
 THE SITE PLAN. SHOW COMPLIANCE WITH 2020 FBC-BUILDING
 TABLE 602 FIRE RESISTANCE RATING REQUIREMENTS FOR
 EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE.
  
 3) THE PERMIT APPLICATION UNDER DESCRIPTION OF WORK
 LIST MANUFACTURED SHED, PLEASE ADD ON THE PERMIT
 APPLICATION THE INTENDED USE FOR THIS SHED, PROVIDE
 OCCUPANCY TYPE. GENERAL NOTE 2 STATES THIS BUILDING
 BEING USED WITH ONE & TWO FAMILY RESIDENCES FROM DOOR
 HEIGHTS. PROVIDE WHAT THE OCCUPANCY TYPE FOR THIS SHED
 AND PROVIDE USAGE WHAT WILL BE STORED INSIDE TO DECLARE
 IF A S1 OR S2 IS TO BE DECLARED.
  
 4) THE STATE APPROVED PLAN PSI APPROVAL 2015-06-02 IS
 UNDER THE 2014 FBC-B IS THIS SHED A USED SHED AND BEING
 MOVED FROM A DIFFERENT WIND ZONE? 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 5) THE STATE APPROVED PLAN PSI APPROVAL 2015-06-02 IS
 TO SMALL AND COPIED TO MANY TIMES. 107.2.1.3. QUALITY
 OF PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND
 SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 6) PLEASE PROVIDE A COMPLETE SET OF PLANS FROM THE
 FLORIDA STATE MANUFACTURES (MODULAR) BUILDING PROGRAM.
 HTTPS://FLORIDABUILDING.ORG
 MANUFACTURED BUILDINGS
 BUILDING TYPE: STORAGE SHED
 MANUFACTURER: SUPERIOR SHEDS, INC.
 AGENCY: INTERTEK-ATI (ARCHITECTURAL TESTING, INC)
 AGENCY PLAN # SSI-2220-14
 THERE WILL BE 13 SHEETS THAT WILL NEED TO BE UPLOADED
 TO OUR SYSTEM
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-14 Cont ID  
Sent By cwalker Date 2022-12-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-05 Cont ID  
Sent By cwalker Date 2022-10-05 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-10-05 09:47:15FIRE REVIEW COMMENTS:
  
 (1) WHAT WILL BE STORED INSIDE THE PROPOSED STORAGE
 BUILDING? NFPA 1, 1.14
  
 (2) WHAT IS THE DISTANCE OF THE PROPOSED STORAGE
 BUILDING EXTERIOR TO THE PROPERTY LINE? NFPA 80A, 4.3.7
  
 (3) WHAT IS THE DISTANCE OF THE PROPOSED STORAGE
 BUILDING TO THE MAIN BUILDING (EXTERIOR TO EXTERIOR
 DIMENSION)? NFPA 80A, 4.3.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-20 Cont ID  
Sent By vbroglia Date 2023-01-20 Time 13:00 Rev Time 0.00
Received By vbroglia Date 2023-01-12 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-09 Cont ID  
Sent By asangele Date 2023-01-09 Time 16:46 Rev Time 0.00
Received By asangele Date 2023-01-09 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2022-10-04 Time 11:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2023-01-12 Cont ID  
Sent By ccole Date 2023-01-12 Time 16:34 Rev Time 0.00
Received By ccole Date 2023-01-12 Time 16:34 Sent To  
Notes
2023-01-12 16:47:48FL. STATE APPROVED PAPER SHED PLANS AND DESIGN
 CALCULATIONS DO NOT REQUIRE SIGNATURE REVIEW. PLANS
 RETAINED AT MY DESK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 13:41 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-01 13:41:00STATE APPROVED PLANS SSI-2220-14

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-20 Cont ID  
Sent By VBroglia Date 2023-01-20 Time 12:45 Rev Time 0.00
Received By vbroglia Date 2023-01-20 Time 12:45 Sent To  
Notes
2023-01-20 13:00:101/20/23 FAILED
  
 PLEASE ADDRESS THE PREVIOUS COMMENTS
  
 PLEASE NOTE THE SETBACKS FROM THE PROPERTY LINE ON THE
 SITE PLAN PROVIDED, THE SETBACKS SHOW FOLLOW
  
 BUILDING SEPERATION: 6 FEET
 FRONT SETBACKS: 25
 SIDE 5 FEET
 REAR 5 FEET
  
 IF THE BUILDING SEPERATION CANNOT BE 6 FEET, THE
 SETBACKS FROM THE PROPERTY LINES MUST FOLLOW PRIMARY
 STRUCTURE SETBACKS:
  
 FRONT 25 FEET
 SIDE: 5 FEET MIN, 15 FEET TOTAL
 REAR 15 FEET OR 105 OF LOT DEPTH
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-01-09 Cont ID  
Sent By ASangele Date 2023-01-09 Time 16:46 Rev Time 0.00
Received By asangele Date 2023-01-09 Time 16:46 Sent To  
Notes
2023-01-09 16:46:48FAILED
 1/9/2022
  
 PLEASE LABEL SETBACKS OF SHED ON SURVEY.
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-07 Cont ID  
Sent By afowlkes Date 2022-10-07 Time 13:35 Rev Time 0.00
Received By afowlkes Date 2022-10-07 Time 13:35 Sent To  
Notes
2022-10-07 13:37:4110/07/22 FAILED
  
 NEED TO PROVIDE THE SETBACKS OF THE PROPOSED SHED. PER
 CITY CODE, THE SHED MUST BE 5 FT AWAY FROM THE SIDE AND
 REAR PROPERTY LINES.
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431