| 2022-11-07 10:52:24 | RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22091328 |
| | 1801 S FLAGLER DR # 1704 |
| | |
| | 1- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 2- SPECIFY MULLION SIZE AND FASTENING TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES. SEC. 1609.1 |
| | FBC-BUILDING. CLEARLY MARK ON PRODUCT APPROVAL |
| | SUBMITTED |
| | NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| | |
| | RESPONSE: |
| | MULLION SIZE HIGHLIGHTED ON SHEET 3 OF 18 OF FLORIDA |
| | PRODUCT APPROVAL FL34545 SUBMITTED SHOWS A 50-5/8" A |
| | 1X3 MULLION WITH A SPAN OF 50-5/8". BASED ON THE WINDOW |
| | OPENING SHOWN ON THE WINDOW/DOOR SCHEDULE SUBMITTED |
| | THIS MULLION SPAN IS SHORT. THE DESIGN PRESSURE SHOWN |
| | ON THE MULLION SPAN FOR A 63" MULLION SPAN DOESN'T MEET |
| | THE DESIGN PRESSURE SHOWN ON THE WINDOW/DOOR SCHEDULE |
| | SUBMITTED. REVISE MULLION SIZE AS REQUIRED TO MEET THE |
| | CALCULATED DESIGN PRESSURES. |
| | SEC. 1609.1 FBC-BUILDING. |
| | |
| | ORIGINAL COMMENT: |
| | 3- SPECIFY SLIDING GLASS DOOR NUMBER OF PANELS/SIZE AND |
| | SILL HEIGHT TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES. SEC. 1609.1 FBC-BUILDING. CLEARLY MARK ON |
| | PRODUCT APPROVAL SUBMITTED. |
| | NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| | |
| | RESPONSE: |
| | SILL HEIGHT HIGHLIGHTED ON TABLE 2A OF SHEET 7 OF 22 OF |
| | NOA 20-0429.09 SUBMITTED DOESN'T MEET THE DESIGN |
| | PRESSURE SHOWN ON THE WINDOW/DOOR SCHEDULE SUBMITTED. |
| | REVISE AS REQUIRED TO MEET THE CALCULATED DESIGN |
| | PRESSURES. |
| | SEC. 1609.1 FBC-BUILDING. |
| | |
| | 4-OK. |
| | |
| | NOTE: ITEM #5 BELOW TO BE VERIFIED IN FIELD. |
| | 5- WINDOW OPENING CONTROL DEVICES: WINDOW OPENING |
| | CONTROL DEVICES ARE REQUIRED WHEN THE WINDOW SILL IS AT |
| | A HEIGHT LESS THAN 36 INCHES ABOVE THE FINISHED FLOOR. |
| | WINDOW OPENING CONTROL DEVICES NEED TO COMPLY WITH ASTM |
| | F2090. |
| | CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE |
| | WINDOW SILL IS LESS THAN 36" ABOVE THE FINISH FLOOR. |
| | SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |