| Plan Review Stops For Permit 22091294 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-12-07 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-12-07 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-12-07 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2022-12-07 13:03:39 | SOUTH BUILDING HALF ADDRESS READDRESSED TO 202 GREYMON | | | DR UPDATED PERMIT |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-10-20 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-10-20 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2022-10-20 08:33:16 | THIS BUILDING CURRENTLY HAS THE ADDRESS OF 200 1/2 | | | GREYMON DR, HALF ADDRESSES ARE NO LONGER ALLOWED AND IT | | | NEEDS TO BE READDRESSED. THE ADDRESS PROPOSED FOR THE | | | BUILDING IS 202 GREYMON DR. PLEASE HAVE OWNER CONTACT | | | [email protected] OR CALL 561-805-6659 TO DISCUSS | | | ADDRESSING ISSUES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-18 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-18 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-19 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-19 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-16 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-15 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2022-11-16 07:42:16 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE LOCATION AND THE DETAILS FOR THE | | | DRAFT STOP FOR THE 2ND FLOOR TRUSSES - FBC R 302.12 | | | | | | 2) PLEASE SHOW THE GARAGE CEILING DETAILS TO COMPLY | | | WITH FBC TABLE R302.6 | | | | | | 3) PLEASE SHOW GUARD RAIL DETAILS PER FBC R312.1 | | | | | | 4) PLEASE SHOW STAIR HAND RAIL DETAILS PER FBC R311.7.8 | | | | | | 5) PLEASE SHOW STAIR DETAILS - RISER HEIGHT, TREAD | | | DEPTH, STAIR WIDTH ETC. - FBC R311.7 | | | | | | 6) PLEASE PROVIDE A COPY OF THE PRODUCT APPROVAL FOR | | | THE FRONT DOOR AS LISTED ON THE DRAWINGS - FL27606.1 | | | | | | 7) PLEASE PROVIDE COMPLETE THE PRODUCT APPROVALS FOR | | | THE ROOFING SYSTEMS. | | | | | | 8) PLEASE PROVIDE THE ELEVATOR DETAILS - FBC R321.1 | | | | | | 9) THE SITE PLAN NEEDS TO SHOW STORM WATER DRAINAGE FBC | | | WPB107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | | | | 10) A SEPARATE PERMIT IS REQUIRED FOR - SITE WALL, | | | FENCE, POOL | | | | | | 11) ITEMS SUCH AS BUT NOT LIMITED TO ROOFING PRODUCT | | | APPROVALS, ELEVATOR DETAILS - MAY BE DEFERRED | | | SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE | | | CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT | | | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-05 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-05 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-11-07 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-11-07 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
ahamilto |
Date |
2022-11-30 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-11-30 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-03 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-01-17 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-05 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-12-16 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-12-01 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-19 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-16 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-02 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2023-02-16 16:49:19 | RECEIPT MU-2023-005638-0000 $459.33 PAID AO | | | | | 2023-02-02 15:05:09 | 2/2/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-16 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-16 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2022-11-16 07:43:12 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-19 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-19 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-21 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-21 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2022-12-21 15:34:11 | 2ND REVIEW FMC | | | PERMIT: 22091294 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THE NEW DETACHED | | | GARAGE. FEC R101.5.1.1 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-07 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-07 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2022-11-07 09:01:49 | 1ST REVIEW FMC | | | PERMIT: 22091294 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THE HOUSE. FEC | | | R101.5.1.1.1 | | | | | | 2) THE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE AND | | | GUEST HOUSE INDICATES THE CONDENSING UNIT IS A 2.55 | | | TONS 30,582 BTU???S. SHEET M-1 INDICATES THIS | | | CONDENSING UNIT TO BE 24,000 BTU MAX. MAKE SURE THE | | | DOCUMENTS SUBMITTED MATCH. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-19 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-10-29 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-29 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-29 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2023-03-28 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2023-03-28 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2023-03-28 13:08:11 | INSPECTIONS ONLY | | | | | | REVIEWED APPROVED REG |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-19 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-19 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2022-12-19 11:43:27 | ROOFING SYSTEM TO BE DEFERRED |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-16 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-16 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2022-11-16 07:43:46 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-19 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-19 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-16 |
Time |
05:46 |
Rev Time |
|
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-11-07 09:02:32 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-02-02 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-02-02 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-12-30 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-12-30 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-12-30 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2022-12-30 13:14:57 | REQUIRES SEPARATE LANDSCAPE PERMIT SUBMITTAL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
ahamilto |
Date |
2022-11-30 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-11-30 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2022-11-30 10:49:14 | REQUIRES SUBMITTAL OF A SEPARATE LANDSCAPE PERMIT |
|
|