Plan Review Details - Permit 22091286
Plan Review Stops For Permit 22091286
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By ppetty Date 2022-11-28 Time 13:45 Rev Time 0.00
Received By ppetty Date 2022-11-28 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By ppetty Date 2022-10-20 Time 08:34 Rev Time 0.00
Received By ppetty Date 2022-10-20 Time 08:17 Sent To  
Notes
2022-10-20 08:35:38SEE F/D NOTE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-14 Cont ID  
Sent By cwalker Date 2022-11-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By cwalker Date 2022-10-04 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-10-04 10:32:20FIRE REVIEW COMMENTS:
  
 PROVIDE CLARIFICATION AS TO MANUAL PULL STATION
 LOCATIONS. MANUAL ALARM BOXES SHALL BE LOCATED WITHIN
 5??? OF EACH EXIT DOORWAY. SOME MARKED EXITS DID NOT
 INDICATE A MANUAL PULL STATION AND THE DISTANCE FROM
 THE EXIT TO THE MANUAL STATION WAS NOT IDENTIFIED. NFPA
 72, 17.14.8.4
  
 PROVIDE A CLARIFICATION OF VISIBLE SIGNALING DEVICE
 LOCATIONS FOR ALL OCCUPIABLE SPACES, SUCH AS THE
 WALK-INS. NFPA 72, 18.5.1.2
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-28 Cont ID  
Sent By ppetty Date 2022-11-28 Time 13:45 Rev Time 0.00
Received By ppetty Date 2022-11-13 Time 18:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-20 Cont ID  
Sent By ppetty Date 2022-10-20 Time 08:34 Rev Time 0.00
Received By ppetty Date 2022-10-03 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 09:32 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 09:32 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By shill Date 2022-11-17 Time 17:59 Rev Time 0.00
Received By shill Date 2022-11-17 Time 17:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 09:33 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 09:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved