| Plan Review Stops For Permit 22091281 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-12-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-12-14 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-12-14 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2022-12-14 14:51:45 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-19 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-19 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2023-04-19 08:57:13 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE ADDITIONAL DETAILS FOR THE "THREADED | | | BEAM" AT THE REAR PATIO - SHOW ATTACHMENTS TO THE | | | STRUCTURE. FBC 107.2.1 | | | | | | 2) IN THE PRODUCT APPROVAL FOR THE ROOF TILE - PLEASE | | | CIRCLE THE ROOF TILE ATTACHMENTS TO BE USED - IF USING | | | ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. | | | FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE | | | CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, | | | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, | | | MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE | | | INSTALLED | | | | | | 3) PLEASE PRIVIDE THE FLAME CERTIFICATION (ICC | | | EVALUATION REPORT) FOR THE FOAM INSULATION AT THE | | | BOTTOM OF THE ROOF DECK - R316.3 SURFACE BURNING | | | CHARACTERISTICS. | | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | | | 4) THE SOIL REPORT DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX | | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED | | | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-19 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-19 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2023-01-19 14:45:00 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB | | | 107.3.4 | | | | | | 2) DRAWING S1 "MONO WALL DETAIL" SHOWS ROOFING AS TPO - | | | SHOULD IT SAY SHINGLES? | | | | | | 3) DRAWING S1 "MONO WALL DETAIL" SHOWS FOOTING | | | REINFORCEMENT W/3 #7 - FOOTING SCHEDULE DOES NOT MATCH | | | - PLEASE CLARIFY | | | | | | 4) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE PER | | | FBC R807.1 | | | | | | 5) PLEASE SHOW THE EXTERIOR WALL INSULATION TYPE AND | | | "R" VALUE ON THE DRAWINGS THAT MATCH THE ENERGY CALCS. | | | - FBC WPB 107.2 | | | | | | 6) PLEASE SHOW THE CEILING INSULATION TYPE ON THE | | | DRAWINGS THAT MATCH THE ENERGY CALCS. - FBC WPB 107.2 | | | | | | 7) PLEASE SHOW THE ATTIC VENTILATION TYPE AND ON CENTER | | | SPACING PER FBC R806.1 | | | | | | 8) PLEASE PROVIDE AN EXTERIOR WINDOW FLASHING DETAIL | | | PER FBC R703.4 | | | | | | 9) THE ARCHITECTURAL, STRUCTURAL DRAWINGS AND THE SOIL | | | REPORT DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE | | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | | TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-20 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-20 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-01-05 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-01-05 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2023-01-05 16:18:17 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE IN ACCORDANCE | | | WITH NEC 220 (FOR OPTIONAL METHOD NEC 220.82). | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-04-20 |
Time |
19:58 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-04-20 |
Time |
19:58 |
Sent To |
|
|
| Notes |
| 2023-04-20 19:58:51 | AS PER PREVIOUS COMMENT: | | | | | | A SEPARATE DRIVEWAY PERMIT IS REQUIRED. | | | | | | THANKS, | | | LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR, | | | ENGINEERING SERVICES DEPARTMENT (561) 494-1085 | | | [email protected] | | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2023-01-23 |
|
|
Cont ID |
|
| Sent By |
RROSSANO |
Date |
2023-01-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-01-23 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-23 10:18:41 | A SEPARATE DRIVEWAY PERMIT IS REQUIRED. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-05-23 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-23 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-23 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2023-05-23 14:15:13 | SEE PREVIOUS COMMENTS |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-02-10 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-02-10 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2023-02-10 12:16:36 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PROPERTY IS IN A HISTORIC DISTRICT, NEW CONSTRUCTION | | | REQUIRES HPB APPROVAL. PROPOSED DESIGN DOES NOT APPEAR | | | TO BE IN KEEPING WITH THE ARCHITECTURAL CHARACTER OF | | | THE DISTRICT, PLEASE REACH OUT TO DISCUSS AND FOR COA | | | APPLICATION. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-23 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-23 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-13 |
Time |
17:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-13 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-01-04 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-19 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-19 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2023-01-19 15:05:14 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-24 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-24 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-11 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-11 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2023-01-11 15:07:47 | MECHANICAL DESIGN APPROVED BUT I CANNOT APPROVE IT | | | UNTIL THE DESIGNER SUBMITS DIGITALLY SIGN DRAWINGS. FS | | | 471/481 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-17 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-17 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-01-06 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-01-06 |
Time |
10:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-19 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-19 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2023-04-19 09:04:00 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-19 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-19 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-19 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-19 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2023-04-19 09:02:14 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE SOIL REPORT DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-19 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-19 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2023-01-19 15:04:13 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ALL OF THE DRAWINGS SIGNED BY THE DESIGNER DO NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | 2023-01-11 15:32:25 | DESIGNER NEEDS TO DIGITALLY SIGN THE MECHANICAL | | | DRAWINGS. ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-05-23 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-23 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-23 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2023-05-23 14:15:46 | SEE HISTORIC COMMENTS FROM 2.13.23 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
AHamilto |
Date |
2023-02-10 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-02-10 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2023-02-10 11:38:35 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | SEE HISTORIC COMMENTS | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|