Plan Review Details - Permit 22091257
Plan Review Stops For Permit 22091257
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-10-13 Cont ID  
Sent By cpuell Date 2022-10-13 Time 16:16 Rev Time 0.00
Received By cpuell Date 2022-10-13 Time 16:15 Sent To  
Notes
2022-10-13 16:20:06UPDATED ADDRESS TO 206 S OLIVE AVE TO REFLECT THE
 CORRECT LOCATION OF THE STORE. UPDATED PERMIT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By rmcphers Date 2023-01-24 Time 08:49 Rev Time 0.00
Received By rmcphers Date 2023-01-24 Time 08:49 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 14:22 Sent To  
Notes
2022-11-14 14:23:01PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By rmcphers Date 2023-01-24 Time 08:47 Rev Time 0.00
Received By rmcphers Date 2023-01-24 Time 08:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 14:23 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-25 Cont ID  
Sent By fgiaquin Date 2022-10-25 Time 20:43 Rev Time 0.00
Received By fgiaquin Date 2022-10-25 Time 18:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By pleduc Date 2023-01-24 Time   Rev Time 0.00
Received By pleduc Date 2023-01-24 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By pleduc Date 2022-10-13 Time   Rev Time 0.00
Received By pleduc Date 2022-10-13 Time 15:27 Sent To  
Notes
2022-10-13 15:36:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF THREE DIFFERENT ADDRESSES
 ON THE APPLICATION AND PLAN SHEETS.
  
 THE APPLICATION INDICATES 224 DATURA ST, SHEET C-1
 INDICATES 206 S OLIVE AVE, SHEET 1.0A AND ALL OTHER
 SHEETS INDICATE 216 S KLIVE AVE.
  
 FOR THE OFFICIAL RECORD, PLEASECLARIFY THE CORRECT
 ADDRESS AND CORRECT ON ALL SHEETS.
  
  
  
 2) PLEASE INDICATE ON THE LIFE SAFETY PLAN WITH
 FOLLOWING NOTE OF ACKNOWLEDGMENT:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS.
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 3) PLEASE INDICATE ON THE MECHAINCAL PLAN WITH A NOTE
 OF ACKNOWLEDGMENT:
  
 ANY WORK ON THE HOOD & FIRE SUPPRESSION SYSTEMS SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-02-03 Cont ID  
Sent By amhamilt Date 2023-02-03 Time 11:59 Rev Time 0.00
Received By amhamilt Date 2023-02-03 Time 11:59 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By amhamilt Date 2022-11-21 Time 10:17 Rev Time 0.00
Received By amhamilt Date 2022-11-21 Time 10:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-28 Cont ID  
Sent By lmarchan Date 2023-02-28 Time 08:06 Rev Time 0.00
Received By lmarchan Date 2023-02-22 Time 06:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-06 Cont ID  
Sent By lmarchan Date 2023-02-06 Time 08:25 Rev Time 0.00
Received By lmarchan Date 2023-01-23 Time 06:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By lmarchan Date 2022-11-22 Time 13:41 Rev Time 0.00
Received By lmarchan Date 2022-10-11 Time 07:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 06:43 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 06:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-26 Cont ID  
Sent By medwards Date 2023-01-26 Time 16:41 Rev Time 0.00
Received By medwards Date 2023-01-26 Time 16:41 Sent To  
Notes
2023-01-26 16:42:172ND REVIEW FMC
 PERMIT: 22091257
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS REVIEWER DID NOT COMMENT THAT THE SMOKER HAD TO
 BE UL LISTED. THE CODE STATES THAT IT SHOULD BE LISTED
 AND LABELED. IT CAN BE FROM ANOTHER TESTING FACILITY.
 AGAIN, I ASK THAT YOU SUBMIT THE SMOKER???S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS AS THE
 SMOKERS EXHAUST AND COMBUSTION AIR WILL HAVE AN EFFECT
 ON THE MECHANICAL SYSTEM DESIGN. THE MANUFACTURER OF
 THIS SMOKER SHOULD STATE THE COMBUSTION AIR AMOUNTS
 WILL BE NEEDED. FMC 917.1
  
 2) THIS SMOKER MUST ALSO MEET ALL OF THE REQUIREMENTS
 OF FMC 906. PROVIDE A COMPLETE DESIGN FOR THIS SMOKER
 THAT INCLUDES CHAPTERS 3,5,7 AND 8.
  
 3) IS THERE TO BE ANY OTHER COOKING IN THIS KITCHEN?
 PROVIDE A LIST OR MENU FOR THE FOODS SERVED IN THIS
 RESTAURANT.
  
 4) AGAIN, PROVIDE THE USE OF SPACE FOR THE ADJACENT
 TENANT SPACE. WHAT WAS THE PREVIOUS USE OF THIS SPACE?
 PROVIDE THE SQUARE FOOTAGE OF THIS SPACE. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 13:34 Rev Time 0.00
Received By medwards Date 2022-11-01 Time 13:33 Sent To  
Notes
2022-11-01 13:34:201ST REVIEW FMC
 PERMIT: 22100465
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVISE THE ADDRESS ON THE DRAWINGS TO THE
 CORRECTED ADDRESS: 206 S. OLIVE.
  
 2) PROVIDE A SITE PLAN FOR THIS BUILDING THAT INCLUDES
 THE PROPERTY LOT LINES.
  
 3) PROVIDE A DETAIL OF THE GREASE DUCT AND HEAT PIPE
 THAT IS EXISTING INCLUDING THE TERMINATION LOCATIONS.
 FBC107.3.5
  
 4) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING
 THAT THE KITCHEN HOOD, GREASE DUCT AND WALK-IN COOLERS
 WILL REQUIRE SEPARATE PERMIT APPLICATIONS AND
 MECHANICAL REVIEWS AS THEY WILL NOT BE REVIEWED UNDER
 THIS PERMIT.
  
 5) PROVIDE DETAILS FOR THE SMOKER. FMC 906
  
 6) THE COOKING EQUIPMENT INCLUDING THE SMOKER SHALL BE
 LISTED AND LABELED FOR INDOOR USE. FMC 917.1
  
 7) PROVIDE DETAILS AS TO WHAT WILL BE UNDER THE HEAT
 HOOD. SHEET 4.0M INDICATES EXISTING WELDED DUCTWORK TO
 ROOF. SHEET 1.1A DEMO DRAWING DOES NOT SHOW THIS DUCT
 WORK AS EXISTING. PLEASE CORRECT THE STATEMENT ON 4.0M
 TO INDICATE THIS TO BE A NEW HEAT DUCT. FBC 107.3.5
  
 8) PLEASE CORRECT THE OUTDOOR AIR CALCULATIONS. DINING
 ROOM OUTDOOR AIR RATE FOR CFM/FT2 SHOULD BE CALCULATED
 AT .18 NOT .12. THIS WOULD MAKE THE TOTAL OUTDOOR AIR
 FOR THIS AREA TO BE 261 CFM???S. FMC TABLE 403.3.1.1
  
 9) THE OUTDOOR AIR CALCULATIONS FOR THE KITCHEN SHOULD
 SHOW 79 CFM???S OF OUTDOOR AIR REQUIRED WITH 197
 CFM???S OF REQUIRED EXHAUST FOR THIS KITCHEN. FMC TABLE
 403.3.1.1
  
 10) PLEASE PROVIDE THE AIR BALANCE DESIGN FOR THIS
 TENANT SPACE. FMC 508.1.2
  
 11) THE NEW FLOOR PLAN ON 1.1A INDICATES A NEW WALL
 OPENING INTO THE TENANT SPACE BESIDE OF THIS TENANT.
 PROVIDE THE OCCUPANCY AND USE OF SPACE FOR THIS TENANT
 SPACE ALONG WITH THE MECHANICAL SYSTEM SIZING. FMC
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-25 Cont ID  
Sent By rwbrown Date 2023-01-25 Time 06:20 Rev Time 0.00
Received By rwbrown Date 2023-01-25 Time 06:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-18 Cont ID  
Sent By rwbrown Date 2022-10-18 Time 13:09 Rev Time 0.00
Received By rwbrown Date 2022-10-18 Time 12:46 Sent To  
Notes
2022-10-18 13:09:091ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK,
 DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES
 THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE
 GOING TO THE SANITARY AND NOT TO THE GREASE WASTE.
 PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF
 GREASE WASTE AND SANITARY WASTE.
  
 2. 2020 FPC 404.1 - PLEASE SHOW THE REQUIREMENTS FOR
 ADA BATHROOMS AND YOUR METHOD OF PROVIDING THEM FOR
 EACH SEX. YOU'VE INDICATED THAT YOU ARE PROVIDING ONE
 MEN'S AND ONE WOMEN'S BATHROOM, NEITHER OF WHICH APPEAR
 TO MEET THE ADA CLEARANCES.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 06:44 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 06:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By medwards Date 2023-01-26 Time 16:43 Rev Time 0.00
Received By medwards Date 2023-01-26 Time 16:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 13:37 Rev Time 0.00
Received By medwards Date 2022-11-01 Time 13:37 Sent To  
Notes
2022-11-01 13:38:57THE DIGITAL SIGNATURE IS NOT GOOD AS THE DOCUMENTS HAVE
 CHANGED AFTER THE SIGNATURE WAS ADDED. PROVIDE THE
 ORIGINAL DIGITALLY SIGNED DRAWINGS. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-02-27 Cont ID  
Sent By ckimmerl Date 2023-02-27 Time 16:50 Rev Time 0.00
Received By ckimmerl Date 2023-02-27 Time 16:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-31 Cont ID  
Sent By ckimmerl Date 2023-01-31 Time 09:15 Rev Time 0.00
Received By ckimmerl Date 2023-01-31 Time 09:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By ckimmerl Date 2022-11-21 Time 12:54 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 12:48 Sent To  
Notes
***NONE***