| 2022-10-19 10:24:37 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R32 |
| | HAS BEEN REVISED TO FL5259-R36. PLEASE PROVIDE A |
| | COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF |
| | COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT |
| | LIMITATIONS. SELECT OPTIONS FROM EACH CATEGORY TO BE |
| | USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R32 |
| | (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| | WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| | CONSIDER USING FL5259-R36 (NON-HVHZ). |
| | 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL477-R12 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT). |
| | 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL477-R12 SYSTEM NO. W-22 DOES NOT MEET THE |
| | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| | FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| | EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF |
| | HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE |
| | DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |