Plan Review Details - Permit 22091247
Plan Review Stops For Permit 22091247
Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 7 Status F Date 2023-07-27 Cont ID  
Sent By cthroop Date 2023-07-27 Time 10:32 Rev Time 0.00
Received By cthroop Date 2023-07-27 Time 09:26 Sent To  
Notes
2023-07-27 10:34:32AFFIDAVIT REVIEW:
 AFFIDAVIT SUBMITTED FOR REVIEW, DATED 7/21/2023 STATES
 PLAN PAGE A-2 WAS REVISED. REVISION DATE - 7/21/2023:
 D-1, A-1, A-2, E-1.
 NO REVISION DATE ON PLANS. CT

Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 6 Status P Date 2023-07-06 Cont ID  
Sent By pvalenti Date 2023-07-06 Time 09:27 Rev Time 0.00
Received By pvalenti Date 2023-07-06 Time 08:59 Sent To  
Notes
***NONE***

Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 5 Status P Date 2023-06-26 Cont ID  
Sent By cthroop Date 2023-06-26 Time 11:19 Rev Time 0.00
Received By cthroop Date 2023-06-26 Time 11:10 Sent To  
Notes
***NONE***

Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 4 Status P Date 2023-06-02 Cont ID  
Sent By rbrown Date 2023-06-02 Time 09:12 Rev Time 0.00
Received By rbrown Date 2023-06-02 Time 09:12 Sent To  
Notes
***NONE***

Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 3 Status F Date 2023-05-26 Cont ID  
Sent By rgathrig Date 2023-05-26 Time 16:52 Rev Time 0.00
Received By rgathrig Date 2023-05-26 Time 16:52 Sent To  
Notes
2023-05-26 17:17:44AFFIDAVIT REVIEW FAILED 553.791 (1)(L) 553.791(6)
  
 THERE ARE SIX SHEETS MENTIONED ON THE AFFIDAVIT. D1,
 A1, A2, E1, M1, M2. OF THE SIX SHEETS ONLY FOUR ARE
 UPLOADED. THREE HAVE THE ARCHITECT???S DIGITAL
 SIGNATURE AND ARE UPLOADED IN THE SIGNATURE FOLDER (D1,
 A1, E1) AND E1 IS NOT SIGNED AND IS IN SUPPORTING DOCS
 FOLDER.
 THE AFFIDAVIT ONLY IDENTIFIES THE PLANS REVIEWED BY
 SHEET PAGE, (D1, A1, E1). THE AFFIDAVIT DOES NOT
 IDENTIFY WHO THE ARCHITECT IS OR THE DATE OF THE
 DOCUMENTS.
 IN ADDITION, THERE ARE THREE MIAMI DADE NOAS UPLOADED
 THAT THE AFFIDAVIT DOES NOT MENTION. NOA 23-0119.03
 (IMPACT GLASS DOORS), NOA 22-0719.02 (IMPACT WINDOWS),
 NOA 22-0613.00 (IMPACT FIXED WINDOWS).
  
 ALSO, THE PRIVATE PROVIDER LISTED ON THE NOTICE TO
 BUILDING OFFICIAL IS BUCK EVANS. THE AFFIDAVIT HAS BUCK
 EVANS LISTED AS THE PLANS EXAMINER AND LISTES BN
 (INSPECTOR LICENSE NUMBERS) FOR FOUR INDIVIDUALS, MR.
 EVANS IS ONE OF THE ONES LISTED AS AN INSPECTOR. THIS
 IS AN AFFIDAVIT FOR PLAN REVIEW AND MR. EVANS PLAN
 REVIEW LICENSE NUMBER SHOULD BE USED ON THE AFFIDAVIT
 AND NOT INSPECTOR LICENSE NUMBER. THE NOTARY
 DECLARATION STATES DEREK WIECHMANN ALSO APPEARED BUT
 MR. WIECHMANN PLAN REVIEW LICENSE DOES NOT APPEAR ON
 THE AFFIDAVIT
  
 PLEASE RESUBMIT
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 5618056679
  

Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 2 Status F Date 2023-05-25 Cont ID  
Sent By rgathrig Date 2023-05-25 Time 09:43 Rev Time 0.00
Received By rgathrig Date 2023-05-25 Time 09:42 Sent To  
Notes
2023-05-25 09:43:30CONTRACTOR UPLOADED ANOTHER NOTICE TO BUILDING OFFICIAL
 NOT A PLAN REVIEW AFFIDAVIT OF CODE COMPLIANCE
  
 RICHARD GATHRIGHT
  

Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 1 Status F Date 2023-05-17 Cont ID  
Sent By shill Date 2023-05-17 Time   Rev Time 0.00
Received By shill Date 2023-05-17 Time   Sent To  
Notes
2023-05-17 19:10:30FS553.791, SUBMIT THE PLAN REVIEW AFFIDAVIT. OTHER
 PRIVATE PROVIDER DOCUMENTS WERE SUBMITTED BUT I WAS
 UNABLE TO LOCATE THE AFFIDAVIT. WHEN SUBMITTING THE
 AFFIDAVIT, PRIOR TO UPLOADING PLEASE CONFIRM THAT THE
 AFFIDAVIT INCLUDES THE PAGE NUMBER, REVISION OR ISSUE
 DATE, DESIGN PROFESSIONAL. FOR INSTANCE:
 SHEET D-1 PREPARED BY MARK MCCREE DATED 3/28/23.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-06-07 Cont ID  
Sent By pvalenti Date 2023-06-07 Time 16:55 Rev Time 0.00
Received By pvalenti Date 2023-06-07 Time 16:55 Sent To  
Notes
2023-06-07 16:56:05PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING (AUDIT ONLY) APPROVED
2023-06-05 10:45:14N BUILDING STOP PER L BOND'S EMAIL
 "COULD YOU KINDLY TAKE MY NAME OFF THIS BUILDING REVIEW
 AS THERE IS A PRIVATE PROVIDER INVOLVED AND I WAS
 INSTRUCTED NOT TO REVIEW AT THIS POINT"

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-20 Cont ID  
Sent By rperdomo Date 2023-06-20 Time 15:01 Rev Time 0.00
Received By jleahy Date 2023-06-20 Time 14:15 Sent To  
Notes
2023-02-20 12:05:50 
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2023-07-27 Cont ID  
Sent By cthroop Date 2023-07-27 Time 10:34 Rev Time 0.00
Received By cthroop Date 2023-07-24 Time 09:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2023-07-11 Cont ID  
Sent By rwbrown Date 2023-07-11 Time 10:30 Rev Time 0.00
Received By rwbrown Date 2023-07-06 Time 10:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2023-07-06 Cont ID  
Sent By pvalenti Date 2023-07-06 Time 09:27 Rev Time 0.00
Received By pvalenti Date 2023-07-05 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-06-30 Cont ID  
Sent By rwbrown Date 2023-06-30 Time 08:01 Rev Time 0.00
Received By rwbrown Date 2023-06-28 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-06-26 Cont ID  
Sent By cthroop Date 2023-06-26 Time 11:20 Rev Time 0.00
Received By cthroop Date 2023-06-21 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-06-20 Cont ID  
Sent By jleahy Date 2023-06-20 Time 15:01 Rev Time 0.00
Received By jleahy Date 2023-06-01 Time 09:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-30 Cont ID  
Sent By shill Date 2023-05-30 Time 19:25 Rev Time 0.00
Received By shill Date 2023-05-25 Time 17:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-25 Cont ID  
Sent By lmarchan Date 2023-05-25 Time 10:54 Rev Time 0.00
Received By lmarchan Date 2023-05-19 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-17 Cont ID  
Sent By shill Date 2023-05-17 Time 19:10 Rev Time 0.00
Received By shill Date 2023-05-11 Time 10:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-03 Cont ID  
Sent By lbond Date 2023-03-03 Time 11:21 Rev Time 0.00
Received By lbond Date 2023-02-16 Time 12:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2023-02-20 Cont ID  
Sent By medwards Date 2023-02-20 Time 10:23 Rev Time 0.00
Received By medwards Date 2023-02-20 Time 10:23 Sent To  
Notes
2023-02-20 10:23:47NO MECHANICAL WORK SHOWN IN SCOPE OF WORK FOR THIS
 PROJECT. ME

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-07-28 Cont ID  
Sent By rwbrown Date 2023-07-28 Time 06:53 Rev Time 0.00
Received By rwbrown Date 2023-07-28 Time 06:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-07-11 Cont ID  
Sent By rwbrown Date 2023-07-11 Time 10:28 Rev Time 0.00
Received By rwbrown Date 2023-07-11 Time 09:59 Sent To  
Notes
2023-07-11 10:27:593RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - THE INFORMATION ON THE
 PERMIT DOCUMENTS SHOULD BE CLEAR IN ORDER TO REVIEW FOR
 CODE COMPLIANCE. YOU ARE LABELING SINKS THAT SHOULD BE
 LABELED AS LAVATORIES. YOU HAVE LABELED "LAV" AS WHAT
 SHOULD BE A SHOWER AND A TUB IN THE MASTER BATH. THE
 "LAV" IN THE 2ND BEDROOM BATH IS ACTUALLY A TUB, AND
 THE SINK SHOULD BE LABELED AS A LAV. "SINKS" ARE NOT
 ALLOWED TO SERVE AS WET VENTS. AND, THE OFFICE BATHROOM
 HAS A SHOWER LABELED AS A "LAV". PLEASE APPROPRIATELY
 LABEL THE FIXTURES.
  
 2. 2020 FRC P3101.2.1 - THE WATER CLOSET IN THE HALL
 BATH IS NOT VENTED TO CODE. THE FIXTURE DRAIN OF THE
 WATER CLOSET CANNOT CONNECT TO THE HORIZONTAL BRANCH
 SYSTEM WITHOUT A VENT. IT MUST CONNECT TO THE WET VENT
 SYSTEM OR HAVE ITS OWN VENT.
  
 3. 2017 WPB AMENDS 107.2.1 - THE "SINK" NEXT TO THE
 AUTOMATIC CLOTHES WASHER IS NOT DRAWN ON THE ISOMETRIC
 DRAWING.
  
 PLEASE APPROPRIATELY LABEL THE FIXTURES AND RESUMBIT A
 CODE COMPLIANT ISOMETRIC OF THE DWV SYSTEM.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-30 Cont ID  
Sent By rwbrown Date 2023-06-30 Time 07:57 Rev Time 0.00
Received By rwbrown Date 2023-06-30 Time 07:57 Sent To  
Notes
2023-06-30 07:59:421ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - THE ISOMETRIC DRAWING DOES
 NOT MATCH THE FLOOR PLAN. THE DRAWING SHOWS 5
 WATERCLOSETS AND THE FLOOR PLAN ONLY HAS 3. ALSO, YOU
 ARE INCORRECTLY LABELING THE SINKS AS LAVS. LAVS ARE
 BATHROOM SINKS ONLY. PLEASE CORRECTLY LABEL THE
 FIXTURES WITH BAR SINK, KITCHEN SINK, AUTOMATIC CLOTHES
 WASHER, LAUNDRY SINK, ETC. PLEASE CORRECT THE DRAWING
 TO MATCH THE FLOOR PLAN AND CORRECTLY LABEL THE
 FIXTURES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-16 Cont ID  
Sent By rwbrown Date 2023-06-16 Time 07:20 Rev Time 0.00
Received By rwbrown Date 2023-06-16 Time 07:20 Sent To  
Notes
2023-06-16 07:21:171ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE SUBMIT THE
 REQUIRED PLUMBING RISER DIAGRAM IN ISOMETRIC FORM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-06-07 Cont ID  
Sent By pvalenti Date 2023-06-07 Time 16:11 Rev Time 0.00
Received By pvalenti Date 2023-06-07 Time 15:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-07-11 Cont ID  
Sent By rwbrown Date 2023-07-11 Time 10:29 Rev Time 0.00
Received By rwbrown Date 2023-07-11 Time 10:29 Sent To  
Notes
2023-07-11 10:30:12SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 THE PAGES SUBMITTED ARE NOT ELECTRONICALLY SEALED BY
 THE ARCHITECT AS REQUIRED.
  
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-30 Cont ID  
Sent By rwbrown Date 2023-06-30 Time 08:01 Rev Time 0.00
Received By rwbrown Date 2023-06-30 Time 08:01 Sent To  
Notes
2023-06-30 08:01:51SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 NONE OF THE FILES ARE SHOWING AS ELECTRONICALLY SEALED.
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-25 Cont ID  
Sent By rgathrig Date 2023-05-25 Time 10:41 Rev Time 0.00
Received By rgathrig Date 2023-05-25 Time 10:41 Sent To  
Notes
2023-05-25 10:44:14SIGNATURE REVIEW FAILED. THE ELECTRONIC REVIEW SAID
 DOCUMENT HAS BEEN UPDATED SINCE SIGNED
  
 RICHARD GATHRIGHT
  
2023-05-11 10:46:31COMBINED FILES UNDER SIGNATURES FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-07 Cont ID  
Sent By lbond Date 2023-06-07 Time 16:30 Rev Time 0.00
Received By pvalenti Date 2023-06-07 Time 15:39 Sent To  
Notes
***NONE***