Plan Review Details - Permit 22091216
Plan Review Stops For Permit 22091216
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By mpeterso Date 2022-11-15 Time 11:24 Rev Time 0.00
Received By mpeterso Date 2022-11-15 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By mpeterso Date 2022-10-20 Time 13:21 Rev Time 0.00
Received By mpeterso Date 2022-10-20 Time 10:02 Sent To  
Notes
2022-10-20 13:39:28ELECTRIC REVIEW FAILED
 1) ELECTRICAL DRAWINGS APPEAR TO BE PREPARED BY THE
 GENERAL CONTRACTOR. PLEASE DETAIL UNDER WHAT STATUTE
 THIS IS STATUTE COMPLIANT AND DOES NOT REQUIRE
 PROFESSIONAL ENGINEERED DRAWINGS. IN ADDITION THIS
 DRAWING STATES NO FIRE ALARM WORK IS TO BE DONE,
 HOWEVER, IT IS NOT DETAILED HOW THE REPLACED DAMPER IN
 THE EQUIPMENT ROOM IS CONTROLLED. IF IT IS VIA THE FIRE
 ALARM THEN THIS SHOULD BE STATED AND MAY ALSO REQUIRE
 PROFESSIONAL ENGINEER. FSS 471.003 FSS 489
 2 PLANS DO NOT DETAIL VOLTAGES OR SPECS OF CONTROLLER
 AND ATS DISCONNECTS. IF ANY 480 VOLT WORK IS TO BE
 DONE, THEN, PLEASE CLARIFY HOW PREPARED DRAWINGS COMPLY
 WITH FS 471.003 (H) 2(A)
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-15 Cont ID  
Sent By mpeterso Date 2022-11-15 Time 11:31 Rev Time 0.00
Received By mpeterso Date 2022-10-26 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-20 Cont ID  
Sent By mpeterso Date 2022-10-20 Time 13:44 Rev Time 0.00
Received By mpeterso Date 2022-10-03 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 10:46 Rev Time 0.00
Received By medwards Date 2022-11-08 Time 10:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-10-21 Cont ID  
Sent By medwards Date 2022-10-21 Time 10:35 Rev Time 0.00
Received By medwards Date 2022-10-21 Time 10:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By mpeterso Date 2022-11-15 Time 11:24 Rev Time 0.00
Received By mpeterso Date 2022-11-15 Time 11:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By mpeterso Date 2022-10-20 Time 13:39 Rev Time 0.00
Received By mpeterso Date 2022-10-20 Time 13:39 Sent To  
Notes
2022-10-20 13:44:08SIGNATURE REVIEW FAILED
  
 PROFESSIONAL ENGINEERED PLANS MAY BE REQUIRED WITH
 APPLICABLE SEALS AND SIGNATURES FS 471.003
  
 SIGNATURE REVIEW FAILED
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  