Plan Review Details - Permit 22091175
Plan Review Stops For Permit 22091175
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 10:05 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By jwitmer Date 2022-12-20 Time 14:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 10:33 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-01 10:33:30WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22091175
 ADD: 1400 CENTREPARK BLVD # 900
 CONT: HOLT LEE CONSTRUCTION
 TEL: 954-725-4881
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 01/2022
 ACTION: DENIED
 1) SHEET G1.02 PLEASE REVIEW THE MAIN ENTRY THERE ARE
 (2) SETS OF DOORS, A PAIR OF DOUBLE DOORS AND A SINGLE
 DOOR. THE DOORS IN THEIR SWING DO NOT KEEP A FOUR-FOOT
 DISTANCE BETWEEN THE SETS OF DOORS.
 2020 FBC-ACCESS. CODE 404.2.6 DOORS IN SERIES. THE
 DISTANCE BETWEEN 2 HINGED DOORS OR PIVOTED DOORS IN
 SERIES SHALL BE 48 INCHES MINIMUM PLUS THE WIDTH OF
 DOORS SWINGING INTO THE SPACE. SEE FIGURE 404.2.6.
  
 2) SHEET G1.02 & 1.01BOTH SHOW AT THE BOTTOM OF THE
 TENANT SPACE OPEN AREA 02, IT APPEARS THERE IS A TENANT
 SEPARATION WALL WITH A DOOR OPENING INTO THE GRAY AREA
 OF ANOTHER TENANT WITH NO DOORWAY TO THE PUBLIC
 CORRIDOR?
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-22 Cont ID  
Sent By mpeterso Date 2022-12-22 Time 11:54 Rev Time 0.00
Received By mpeterso Date 2022-12-22 Time 11:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By mpeterso Date 2022-10-17 Time 15:17 Rev Time 0.00
Received By mpeterso Date 2022-10-17 Time 15:17 Sent To  
Notes
2022-10-17 16:07:54ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL THE NEW LOCATION THE 30KVA TRANSFORMER
 FEEDING PANEL "A" INSIDE SUITE 900. PLEASE INDICATE ON
 THE FLOOR PLAN WHERE IT HAS BEEN RELOCATED FROM. FBC
 107.2
 2) PLEASE INDICATE PRIMARY AND SECONDARY CONDUCTOR
 SIZES FOR 3O KVA TRANSFORMER AND SYSTEM BONDING JUMPER.
 NEC 215.5
 3) PLEASE INDICATE ON FLOOR PLAN AND RISER DIAGRAM THAT
 THE REQUIRED LABELS WILL BE IN PLACE DESIGNATING THE
 PRIMARY DISCONNECT LOCATION AND THAT IT IS LOCKABLE AS
 PER NEC 450.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-01-19 Cont ID  
Sent By mpeterso Date 2023-01-19 Time 09:05 Rev Time 0.00
Received By mpeterso Date 2023-01-19 Time 09:05 Sent To  
Notes
2023-01-19 09:06:26PASSED FOR VOICE AND DATA ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-15 Cont ID  
Sent By cwalker Date 2022-12-15 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-12-15 08:54:11FIRE PROVISO COMMENTS:
  
 (1) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
  
 (3) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS BY PROPERLY LICENSED AND CERTIFIED
 CONTRACTORS.
  
 (4) ANY INSTALLATION OF AN ACCESS CONTROL SYSTEM SHALL
 BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY
 PROPERLY CERTIFIED CONTRACTORS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-30 Cont ID  
Sent By cwalker Date 2022-09-30 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-09-30 11:09:49FIRE PROVISO COMMENTS:
  
 (1) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (3) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS BY PROPERLY LICENSED AND CERTIFIED
 CONTRACTORS.
  
 (4) ANY INSTALLATION OF AN ACCESS CONTROL SYSTEM SHALL
 BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY
 PROPERLY CERTIFIED CONTRACTORS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-22 Cont ID  
Sent By mpeterso Date 2022-12-22 Time 11:55 Rev Time 0.00
Received By mpeterso Date 2022-12-14 Time 09:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2022-09-29 Time 04:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 10:06 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 08:12 Rev Time 0.00
Received By medwards Date 2022-12-21 Time 08:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By medwards Date 2022-10-06 Time 11:02 Rev Time 0.00
Received By medwards Date 2022-10-06 Time 10:48 Sent To  
Notes
2022-10-06 11:02:121) THE OUTDOOR AIR CALCULATIONS MUST INCLUDE EACH USE
 OF SPACE IN THIS TENANT SPACE. PROVIDE OUTDOOR AIR
 CALCULATIONS FOR EACH USE OF SPACE. FMC 403.3.1.1 AND
 TABLE 403.3.1.1.
 2) PROVIDE THE DUCT SIZES ON THE DRAWING. FBC 107.3.5
 3) THE DRAWINGS MUST BE DIGITALLY SIGNED BY THE EOR. IT
 APPEARS THE DRAWINGS HAVE BEEN ALTERED WHICH MAKES THE
 SIGNATURE A COPY OF THE ORIGINAL. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-12-15 Cont ID  
Sent By rwbrown Date 2022-12-15 Time 07:43 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By rwbrown Date 2022-10-06 Time 11:56 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-06 12:02:07NEED SIGNED AND SEALED PAGES, OTHERWISE OKAY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-22 Cont ID  
Sent By mpeterso Date 2022-12-22 Time 11:55 Rev Time 0.00
Received By mpeterso Date 2022-12-22 Time 11:55 Sent To  
Notes
2022-12-21 08:13:21MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By rwbrown Date 2022-10-06 Time 11:57 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-06 12:01:00 
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 THE PAGES SUBMITTED DO NOT HAVE A ELECTRONIC SEAL ON
 THE FILE. THEY HAVE PRINTED DIGITAL SIGNATURE WHICH
 DOES NOT COMPLY. EACH PAGE NEEDS TO HAVE A VERIFIABLE
 ELECTRONIC SEAL IN ACCORDANCE WITH THE ABOVE REFERENCED
 FLORIDA ADMINISTRATIVE CODE.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
2022-10-06 11:02:58MECHANICAL WILL NEED TO BE DIGITALLY SIGNED BY THE EOR.