| Plan Review Stops For Permit 22091110 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-11-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-11-30 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2022-11-30 11:01:26 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-07-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-06 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-06 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-05-26 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-05-26 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2023-05-26 09:31:19 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) IN THE PROVIDED PRODUCT APPROVAL FOR THE ROOFING | | | TILE - PLEASE CIRCLE THE TILE ATTACHMENT TYPE IN THE | | | PRODUCT APPROVAL - THERE ARE DIFFERENT UPLIFT PRESSURES | | | FOR 1 NAIL , 2 NAILS ETC PLEASE CHOOSE THE ATTACHMENT | | | ON THE PRODUCT APPROVAL THAT MEETS THE REQUIRED UPLIFT | | | PRESSURE - FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES | | | REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL | | | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING | | | SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE INSTALLED | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-26 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-26 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2023-04-26 15:26:28 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) IN THE PROVIDED PRODUCT APPROVAL FOR THE ROOFING | | | TILE - PLEASE CIRCLE THE TILE ATTACHMENT TYPE IN THE | | | PRODUCT APPROVAL - IF USING ADHESIVE TO ATTACH THE TILE | | | PROVIDE THE PRODUCT APPROVAL FOR THE ADHESIVE. FBC WPB | | | 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE | | | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND | | | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, | | | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND | | | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED | | | | | | 2) THE PROVIDED SIGNED AND SEALED SURVEY AND THE SIGNED | | | AND SEALED SOIL REPORT PROVIDED DO NOT SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER. SIGNED AND SEALED | | | DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-12 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-12 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2022-12-12 13:53:22 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS LISTED ON | | | THE DRAWINGS. | | | | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE ROOFING TILE - PLEASE CIRCLE | | | THE TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF | | | USING ADHESIVE TO ATTACH THE TILE PROVIDE THE PRODUCT | | | APPROVAL FOR THE ADHESIVE. | | | | | | 3) PLEASE SHOW THE ATTIC ACCESS OPENING SIZE ( 22" X | | | 30" ) - FBC R807.1 ATTIC ACCESS. | | | BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION | | | SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT | | | HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR GREATER | | | OVER AN AREA OF NOT LESS THAN 30 SQUARE FEET (2.8 M2). | | | THE VERTICAL HEIGHT SHALL BE MEASURED FROM THE TOP OF | | | THE CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE | | | ROOF FRAMING MEMBERS. THE ROUGH-FRAMED OPENING SHALL BE | | | NOT LESS THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) | | | AND SHALL BE LOCATED IN A HALLWAY OR OTHER LOCATION | | | WITH READY ACCESS. | | | | | | 4) PLEASE SHOW THE GARAGE FLOOR TO SLOPE - FBC R309.1 | | | THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR | | | OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE | | | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN | | | VEHICLE ENTRY DOORWAY. | | | | | | 5) THE WIND DESIGN IS SHOWN USING EXPOSURE "C". WITH | | | THE LOCATION OF THE PROPERTY LOCATED ON THE LARGE LAKE | | | EXPOSURE "D" SHOULD BE USED FOR THE WIND DESIGN. FBC | | | R301.2.1.4.3 EXPOSURE D SHALL APPLY WHERE THE GROUND | | | SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, | | | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT | | | LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE | | | BUILDING, WHICHEVER IS GREATER. | | | | | | 6) THE SIGNED AND SEALED SOIL REPORT PROVIDED DOES NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER. SIGNED AND | | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-06-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-06-05 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-06-05 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-05-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-05-09 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-05-09 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-12-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-14 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-14 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2022-12-14 09:41:41 | ELECTRIC REVIEW FAILED | | | 1) PLAN INDICATES TWO LOCATIONS FOR ELECTRIC PANEL, ONE | | | IN LAUNDRY ROOM AND ONE IN THE GARAGE. PLEASE CLARIFY | | | WHICH LOCATION IS TO BE USED. IN ADDITION, ELECTRIC | | | PANEL IN LAUNDRY ROOM DOES NOT APPEAR TO COMPLY WITH | | | NEC 110.26 FOR WORKING CLEARANCE. FBC 107.2 | | | 2) PLEASE DETAIL, ON THE ELECTRICAL PLAN, THE REQUIRED | | | SMOKE/CARBON ALARMS AS PER FBC 314. | | | 3) PLEASE DETAIL THE REQUIRED OUTSIDE RECEPTACLES AT | | | THE FRONT OF THE HOUSE AS REQUIRED PER NEC 210.52(E)(1) | | | 4) PLEASE DETAIL A NOTE STATING POOL AND GENERATOR | | | WIRING REQUIRE A SEPARATE PERMIT | | | 5) PLEASE DETAIL ON THE ELECTRIC PLAN THE WATER HEATER | | | LOCATION AND TYPE, GAS OR ELECTRIC. FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2023-05-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-05-30 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-05-30 |
Time |
06:09 |
Sent To |
|
|
| Notes |
| 2023-05-30 06:09:45 | GAS REMOVED FROM PLANS AND ALL ELECTRIC APPLIANCES | | | PROPOSED - PAGE G-1 LOCKED OUT |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-26 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-26 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2023-04-26 07:29:02 | 2ND GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2415.11 - "SCHEDULE 40 METALLIC PIPE" IS | | | NOT ALLOWED TO BE INSTALLED UNDERGROUND. | | | | | | 2. 2020 FRC G2415.8 - THE PIPING GOING TO THE RANGE | | | APPEARS TO BE IN A SOLID FLOOR. SHOW COMPLIANCE WITH | | | THIS SECTION OR SHOW IT GOING OVERHEAD. | | | | | | 3. 2020 FRC G2415.8 - THE PIPING GOING TO THE DRYER | | | APPEARS TO BE IN A SOLID FLOOR. SHOW COMPLIANCE WITH | | | THIS SECTION OR SHOW IT GOING OVERHEAD. | | | | | | 4. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED | | | COMBUSTION AIR CALCULATIONS FOR THE DRYER. IF THE SPACE | | | FOR THE DRYER DOES NOT HAVE ENOUGH FOR THE APPLIANCE, | | | DETAILS MUST BE SHOWN ON THE PLANS FOR | | | COMBUSTION/MAKEUP AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-05 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-12-05 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2022-12-05 14:10:30 | 1ST GASD REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (13) - GAS: PLEASE SUBMIT A | | | RISER AND GAS DETAILS. PLEASE SHOW THE METHOD USED FOR | | | PIPE SIZING. INCLUDE PIPE SIZES, MATERIALS USED, BTU | | | LOADS AND GAS PRESSURES INVOLVED. ALSO INCLUDE A | | | REFERENCE FOR THE TABLE FROM THE GAS CODE THAT WAS USED | | | FOR SIZING THE SYSTEM | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-07-06 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-07-06 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-07-05 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-06-20 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-05-25 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-05-09 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-04-25 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-10 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-11-29 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-07-12 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2023-07-12 09:24:23 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-12 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-07-12 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2022-12-12 13:29:08 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-05 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-05 |
Time |
14:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2022-12-13 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2022-12-13 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2022-12-13 13:10:22 | PLAN DENIED | | | 1) REFER TO SECTION M 1401.3 EQUIPMENT | | | AND APPLIANCE SIZING. 2020 FBC (R) | | | 2) REFER TO SECTION M1602.3 BALANCED | | | RETURN AIR MASTER BEDROOM AND STUDY. | | | 2020 FBC (R) | | | 3) REFER TO SECTION 403.3.6 AIR HANDLER UNITS | | | 2020 FLORIDA ENERGY CODE | | | 4) PROVIDE HEATER SIZE ON EQUIPMENT SCHEDULE | | | ON PLANS. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-05-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-05-30 |
Time |
06:12 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-05-30 |
Time |
06:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-26 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-26 |
Time |
07:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-05 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-12-05 |
Time |
14:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2023-07-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-06 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-06 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-05-26 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-05-26 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2023-05-26 09:34:48 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-26 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-26 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2023-04-26 15:28:44 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-12 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-12 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2022-12-12 13:29:48 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-07-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-06 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-06 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-05-26 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-05-26 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-26 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-26 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2023-04-26 15:27:34 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED- | | | | | | 1) THE PROVIDED SIGNED AND SEALED SURVEY AND THE SIGNED | | | AND SEALED SOIL REPORT PROVIDED DO NOT SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER. SIGNED AND SEALED | | | DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-12 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-12 |
Time |
13:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-20 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2023-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2023-06-20 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2023-05-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2023-05-08 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2023-01-10 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2023-01-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-10 10:53:35 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS | | | REQUIRED. SURVEY MUST CLEARLY SHOW ANY UTILITY | | | EASEMENTS ON THE PROPERTY (IF APPLICABLE) FOR | | | VERIFICATION WITH THE SITE PLAN. PLEASE NOTE THAT ANY | | | PROPOSED STRUCTURES SHALL NOT ENCROACH UPON ANY UTILITY | | | EASEMENT. | | | | | | 2.) SHOW THE SETBACK DIMENSIONS FROM THE PROPERTY | | | LINE(S) TO DEMONSTRATE COMPLIANCE WITH THE ZLDRS: A) | | | SWIMMING POOL [ZLDR S.94-304(E)]; B) MECHANICAL | | | EQUIPMENT, SUCH AS THE A/C UNIT PAD [ZLDR | | | S.94-305(B)(4)]; C) PAVED DECK [ZLDR S.94-305(B)(7)]; | | | D) DRIVEWAY [ZLDR S.94-482(D)]. | | | | | | 3.) THE PROPOSED NEW DRIVEWAY SHALL NOT EXCEED A WIDTH | | | OF 20 FT. AT THE PROPERTY LINE. [ZLDR S.94-312(C)] | | | | | | 4.) PROVIDE LANDSCAPE CALCULATIONS FOR THE FRONT YARD. | | | A MINIMUM OF 1,000 SQ. FT. OF LANDSCAPED AREA SHALL BE | | | DEDICATED WITHIN THE REQUIRED FRONT YARD (AREA WITHIN | | | THE FIRST 25 FT. OF THE FRONT PROPERTY LINE/NORTH SHORE | | | DRIVE). CALCULATIONS ARE REQUIRED FOR COMPLIANCE WITH | | | THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | [ZLDR S.94-482(A)] | | | | | | 5.) SEPARATE PERMIT SUBMISSION REQUIRED FOR LANDSCAPING | | | PRIOR TO ZONING SIGN-OFF OF THIS PERMIT. NO RECORD OF | | | LANDSCAPE PERMIT PROVIDED IN THE SYSTEM. | | | | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, DRIVEWAY, | | | SWIMMING POOL/SPA. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|