Plan Review Details - Permit 22091037
Plan Review Stops For Permit 22091037
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-10-05 Cont ID  
Sent By cpuell Date 2022-10-05 Time 16:02 Rev Time 0.00
Received By cpuell Date 2022-10-05 Time 16:02 Sent To  
Notes
2022-10-05 16:06:14NEW ADDRESS GIVEN TO BUILDING 725 S CONGRESS AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By cpuell Date 2022-10-04 Time 09:03 Rev Time 0.00
Received By cpuell Date 2022-10-04 Time 09:03 Sent To  
Notes
2022-10-04 09:05:40APPLICATION FORM STATES WORK IS FOR BUILDING 2 SITE
 PLAN DOES NOT HAVE A BUILDING 2 INDICATED ON IT. COULD
 YOU PLEASE PROVIDE A SITE PLAN SHOWING THE AREA OF
 WORK. PLEASE RESPOND TO [email protected] OR CALL
 561-805-6659

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By swelter Date 2023-02-21 Time 09:54 Rev Time 0.00
Received By swelter Date 2023-02-22 Time 15:38 Sent To  
Notes
2023-02-21 09:59:07 
 DEVELOPER SATISFIED PUBLIC ART REQUIREMENT -
 CONTRIBUTION INTO FUND ON 3.22.23
  
 PRIVATE DEVELOPMENT SUBJECT TO PUBLIC ART ASSESSMENT.
 CONTACT PUBLIC ART ADMINISTRATOR, SYBILLE WELTER AT
 561.822.1521 [email protected]
  
 1% TOTAL CONSTRUCTION COSTS APPLIED VALUE $605,000
 1% 6,050
 (-25%) (-1,512.50)
 $4,537.50
 DUE AT TIME OF BUILDING PERMIT FEES ??? CONTACT
 [email protected] FOR INVOICE TO BE PAID SEPARATELY AT
 CITY HALL.
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2022-11-28 Cont ID  
Sent By swelter Date 2022-11-28 Time 14:21 Rev Time 0.00
Received By swelter Date 2022-11-28 Time 14:25 Sent To  
Notes
2022-11-28 14:23:48ART ASSESSMENT INVOICE SENT TO BRETT COLEMAN CC:
 REBECCA MILLER AND LIAM MCGUIRE ON 11.17.2022 - PAYMENT
 FOR 1% IS DUE NOW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-03-07 Cont ID  
Sent By rmcphers Date 2023-03-07 Time 07:40 Rev Time 0.00
Received By rmcphers Date 2023-03-07 Time 07:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-02-06 Cont ID  
Sent By rmcphers Date 2023-02-06 Time 10:53 Rev Time 0.00
Received By rmcphers Date 2023-02-06 Time 10:53 Sent To  
Notes
2023-02-06 10:56:10NEW AUTO SERVICE BAY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE PRODUCT APPROVAL PROVIDED FOR THE ROOFING - THE
 ROOFING SYSTEM CIRCLED SHOWS LIGHT WEIGHT CONCRETE -
 THE DRAWINGS DO NOT SHOW LIGHT WEIGHT CONCRETE - NEED
 TO REVISE DRAWINGS OR CIRCLE A DIFFERENT ROOFING SYSTEM
 IN THE PRODUCT APPROVAL.
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 10:24 Sent To  
Notes
2023-01-10 10:28:31NEW AUTO SERVICE BAY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL NOTE ON THE PRODUCT APPROVAL.
  
 2) DRAWING A0.0 - BUILDING DATA - 1 STORY WITH PARTIAL
 UPPER LEVEL OFFICE AREA - DRAWINGS DO NOT SHOW AN UPPER
 LEVEL - PLEASE CLARIFY.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-31 Cont ID  
Sent By rmcphers Date 2022-10-31 Time 16:58 Rev Time 0.00
Received By rmcphers Date 2022-10-31 Time 14:38 Sent To  
Notes
2022-10-31 16:58:26NEW AUTO SERVICE BAY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT FBC 1803.1
  
 2) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL NOTE ON THE PRODUCT APPROVAL.
  
 3) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP SINK
 - FBC 1210.2.2WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 4) PLEASE SHOW THE DISTANCE FROM THE EXISTING BUILDING
 - FBC 602.1GENERAL.
 BUILDINGS AND STRUCTURES ERECTED OR TO BE ERECTED,
 ALTERED OR EXTENDED IN HEIGHT OR AREA SHALL BE
 CLASSIFIED IN ONE OF THE FIVE CONSTRUCTION TYPES
 DEFINED IN SECTIONS 602.2 THROUGH 602.5. THE BUILDING
 ELEMENTS SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS
 THAN THAT SPECIFIED IN TABLE 601 AND EXTERIOR WALLS
 SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS THAN THAT
 SPECIFIED IN TABLE 602.
  
 FBC 705.5 FIRE-RESISTANCE RATINGS.
 EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN
 ACCORDANCE WITH TABLES 601 AND 602 AND THIS SECTION.
 THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR WALLS
 WITH A FIRE SEPARATION DISTANCE OF GREATER THAN 10 FEET
 (3048 MM) SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE
 INSIDE. THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR
 WALLS WITH A FIRE SEPARATION DISTANCE OF LESS THAN OR
 EQUAL TO 10 FEET (3048 MM) SHALL BE RATED FOR EXPOSURE
 TO FIRE FROM BOTH SIDES.
  
 FBC 705.8 OPENINGS.
 OPENINGS IN EXTERIOR WALLS SHALL COMPLY WITH SECTIONS
 705.8.1 THROUGH 705.8.6.
  
 5) FIRE SPRINKLERS - FBC 903.2.9.1REPAIR GARAGES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS USED AS REPAIR GARAGES IN
 ACCORDANCE WITH SECTION 406, AS SHOWN: A GROUP S-1 FIRE
 AREA USED FOR THE REPAIR OF COMMERCIAL MOTOR VEHICLES
 WHERE THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464 M2).
  
 6) DRAWING A0.0 - BUILDING DATA - 1 STORY WITH PARTIAL
 UPPER LEVEL OFFICE AREA - DRAWINGS DO NOT SHOW AN UPPER
 LEVEL - PLEASE CLARIFY.
  
 7) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 8) PLEASE PROVIDE A SURVEY.
  
 9) ACCESSIBLE RESTROOM - PLEASE SHOW MAXIMUM GRAB BAR
 HEIGHTS TO THE TOP OF THE GRIPPING SURFACE - NOT THE
 CENTER OF THE BAR AS SHOWN ON THE DRAWING - FBC A 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 10) PLEASE SHOW THE DIMENSION OF THE TOILET PAPER
 HOLDER FROM THE FACE OF THE TOILET PER FBC A 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-16 Cont ID  
Sent By mpeterso Date 2023-02-16 Time 09:50 Rev Time 0.00
Received By mpeterso Date 2023-02-16 Time 09:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By mpeterso Date 2023-01-11 Time 09:12 Rev Time 0.00
Received By mpeterso Date 2023-01-11 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By mpeterso Date 2022-11-07 Time 15:53 Rev Time 0.00
Received By mpeterso Date 2022-11-07 Time 13:36 Sent To  
Notes
2022-11-07 16:20:20ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL ALL RECEPTACLES IN GARAGE BAY 150
 VOLTS TO GROUND OR LESS, 50 AMPERES OR LESS, AS GFI
 PROTECTED AS PER NEC 511.12 NEC 210.8(B)(8), IE QUAD
 RECEPTACLES
 2) PLEASE DETAIL THE CLASSIFICATION OF THE OIL/
 EQUIPMENT ROOM, IF NO CLASSIFICATION IS REQUIRED PLEASE
 STATE NOT CLASSIFIED. FBC 107.2
 3) PLEASE CLARIFY AS TO WHY NO ELECTRIC METERING IS
 DETAILED ON RISER DIAGRAM. FBC 107.2
 4) PLEASE DETAIL A NOTE UNDERGROUND WIRING BELOW
 CLASSIFIED AREA IS TO COMPLY WITH NEC 511.8
 5) PLEASE PROVIDE A NOTE STATING FIRE ALARM, ACCESS
 CONTROL, SIGN OR OTHER LOW VOLTAGE WIRING REQUIRE
 SEPARATE PERMITS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2023-03-06 Cont ID  
Sent By rrossano Date 2023-03-06 Time   Rev Time 0.00
Received By rrossano Date 2023-03-06 Time   Sent To  
Notes
2023-03-06 15:18:12UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2023-02-06 Cont ID  
Sent By rrossano Date 2023-02-06 Time   Rev Time 0.00
Received By rrossano Date 2023-02-06 Time   Sent To  
Notes
2023-02-06 12:00:47UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-01-03 Cont ID  
Sent By rrossano Date 2023-01-03 Time   Rev Time 0.00
Received By rrossano Date 2023-01-03 Time   Sent To  
Notes
2023-01-03 08:46:00FORRMAL ENGINEERING SUBMITTAL REQUIRED AFTER SITE PLAN
 APPROVAL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By rrossano Date 2022-10-13 Time   Rev Time  
Received By rrossano Date 2022-10-13 Time   Sent To  
Notes
2022-10-13 12:35:50FORMAL ENGINEERING SUBMITTAL REQUIRED AFTER SITE PLAN
 APPROVAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By cwalker Date 2023-03-03 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-03-03 09:16:55SEE PREVIOUS PROVISO COMMENTS BY B. DOLAN

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By   Date 2022-10-17 Time   Rev Time  
Received By bdolan Date 2022-10-17 Time 12:16 Sent To  
Notes
2022-10-17 12:21:22ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 FOR PURPOSES OF FIRE ALARM PROGRAMMING AND FIRE
 DEPARTMENT RESPONSE, THE MAIN PROPERTY ADDRESS (2301
 OKEECHOBEE BLVD, BLDG #) SHOULD BE THE ADDRESS USED TO
 AVOID CONFUSION AND DELAYED RESPONSE IN THE CASE OF AN
 EMERGENCY RESPONSE CALL. SOUTH CONGRESS AVENUE DIRECTS
 UNITS TO LOCATION SOUTH OF OKEECHOBEE BLVD.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-14 Cont ID  
Sent By lmarchan Date 2023-03-14 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2023-03-02 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-23 Cont ID  
Sent By lmarchan Date 2023-02-23 Time 11:45 Rev Time 0.00
Received By lmarchan Date 2023-02-03 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-19 Cont ID  
Sent By aoliver Date 2023-01-19 Time 09:08 Rev Time 0.00
Received By aoliver Date 2022-12-27 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By aoliver Date 2022-11-22 Time 10:10 Rev Time 0.00
Received By aoliver Date 2022-10-03 Time 10:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rmcphers Date 2022-11-01 Time 08:20 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 08:20 Sent To  
Notes
2022-11-01 08:21:18PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-02-17 Cont ID  
Sent By medwards Date 2023-02-17 Time 06:45 Rev Time 0.00
Received By medwards Date 2023-02-17 Time 06:45 Sent To  
Notes
2023-02-17 06:48:39APPROVED WITH PRIVISOS:
  
 THE CONTRACTOR WILL NEED TO PROVIDE GUARDS AT ALL
 EQUIPMENT ON THE ROOF THAT IS WITHIN THE ROOFS EDGE.
 FMC 304.11
  
 KEYNOTES 7 AND 8 WILL NOW REQUIRE A SEPARATE PERMIT AND
 REVIEW OF THE SOURCE CAPTURE CONTAINMENT SYSTEM. THIS
 SYSTEM SHALL BE ABLE TO SUPPORT EVERY BAY IN THIS
 FACILITY. FMC 502.14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 06:14 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 06:14 Sent To  
Notes
2023-01-11 06:14:492ND REVIEW FMC
 PERMIT: 22091037
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED ENERGY CALCULATIONS WERE NOT IN THIS 2ND
 SUBMITTAL. PLEASE ADDRESS THE FIRST CYCLE REVIEW
 COMMENT BELOW:
 1) THE ENERGY CALCULATIONS FAIL TO MENTION ANY DOORS IN
 THE CALCULATIONS. ALL AREAS THAT ARE TO BE CONDITIONED
 MUST MEET THE FEC. PLEASE INCLUDE ALL DOORS IN THE
 CALCULATIONS. FEC C402
  
 2) THE REVISED HEAT LOAD CALCULATIONS WERE NOT IN THIS
 2ND SUBMITTAL. PLEASE ADDRESS THE FIRST CYCLE COMMENT
 BELOW:
  
 2) THE MECHANICAL EQUIPMENT CALCULATIONS ARE ONE PAGE
 AND ONLY FOR 593 SQ. FT. THE ENERGY CALCULATIONS
 INDICATE THAT 5739 SQ. FT. WILL BE CONDITIONED. PROVIDE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR ALL AREAS
 THAT ARE TO BE CONDITIONED. FEC C403.2.1
  
 3) PLEASE UNDERSTAND THAT THE SOURCE CAPTURE
 CONTAINMENT SYSTEM DESIGN STILL NEEDS TO BE ADDRESSED,
 SEE BELOW:
 SOURCE CAPTURE SYSTEM. A MECHANICAL EXHAUST SYSTEM
 DESIGNED AND CONSTRUCTED TO CAPTURE AIR CONTAMINANTS AT
 THEIR SOURCE AND TO EXHAUST SUCH CONTAMINANTS TO THE
 OUTDOOR ATMOSPHERE. A HOSE THROUGH A HOLE IN A GARAGE
 IS NOT CONSIDERED A SYSTEM.
  
 502.14 MOTOR VEHICLE OPERATION. IN AREAS WHERE MOTOR
 VEHICLES OPERATE, MECHANICAL VENTILATION SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 403. ADDITIONALLY, AREAS IN
 WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS
 DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEMS.
  
 SUCH SYSTEM SHALL BE ENGINEERED BY A REGISTERED DESIGN
 PROFESSIONAL OR SHALL BE FACTORY-BUILT EQUIPMENT
 DESIGNED AND SIZED FOR THE PURPOSE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By medwards Date 2022-11-07 Time 14:06 Rev Time 0.00
Received By medwards Date 2022-11-07 Time 14:06 Sent To  
Notes
2022-11-07 14:06:381ST REVIEW FMC
 PERMIT: 22091037
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS FAIL TO MENTION ANY DOORS IN
 THE CALCULATIONS. ALL AREAS THAT ARE TO BE CONDITIONED
 MUST MEET THE FEC. PLEASE INCLUDE ALL DOORS IN THE
 CALCULATIONS. FEC C402
  
 2) THE MECHANICAL EQUIPMENT CALCULATIONS ARE ONE PAGE
 AND ONLY FOR 593 SQ. FT. THE ENERGY CALCULATIONS
 INDICATE THAT 5739 SQ. FT. WILL BE CONDITIONED. PROVIDE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR ALL AREAS
 THAT ARE TO BE CONDITIONED. FEC C403.2.1
  
 3) PLEASE SHOW THAT THE DESIGN OF THE MECHANICAL SYSTEM
 AND MORE PRECISELY THE EXHAUST FOR THE REPAIR GARAGE
 WILL COMPLY WITH FMC 401.3. THE DESIGN WITH THE SENSORS
 IS COVERED IN FMC 404 PARKING GARAGES. A PARKING GARAGE
 AND A REPAIR GARAGE ARE NOT THE SAME THING AND HAVE
 DIFFERENT REQUIREMENTS IN THE FMC. THE REPAIR GARAGE
 WILL NEED TO MEET THE EXHAUST REQUIREMENTS OF TABLE
 403.3.1.1.
  
 401.3 WHEN REQUIRED. VENTILATION SHALL BE PROVIDED
 DURING THE PERIODS THAT THE ROOM OR SPACE IS OCCUPIED.
  
 4) PLEASE PROVIDE THE SOURCE CAPTURE SYSTEM FOR THE
 REPAIR GARAGE. FMC 502.14
  
 502.14 MOTOR VEHICLE OPERATION. IN AREAS WHERE MOTOR
 VEHICLES OPERATE, MECHANICAL VENTILATION SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 403. ADDITIONALLY, AREAS IN
 WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS
 DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEMS. SUCH
 SYSTEM SHALL BE ENGINEERED BY A REGISTERED DESIGN
 PROFESSIONAL OR SHALL BE FACTORY-BUILT EQUIPMENT
 DESIGNED AND SIZED FOR THE PURPOSE.
  
 EXCEPTIONS:
 1. THIS SECTION SHALL NOT APPLY WHERE THE MOTOR
 VEHICLES BEING OPERATED OR REPAIRED ARE ELECTRICALLY
 POWERED.
 2. THIS SECTION SHALL NOT APPLY TO ONE- AND TWO-FAMILY
 DWELLINGS.
 3. THIS SECTION SHALL NOT APPLY TO MOTOR VEHICLE
 SERVICE AREAS WHERE ENGINES ARE OPERATED INSIDE THE
 BUILDING ONLY FOR THE DURATION NECESSARY TO MOVE THE
 MOTOR VEHICLES IN AND OUT OF THE BUILDING.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 07:04 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 07:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-12-28 Cont ID  
Sent By rwbrown Date 2022-12-28 Time 06:47 Rev Time 0.00
Received By rwbrown Date 2022-12-28 Time 06:47 Sent To  
Notes
2022-12-28 06:48:542ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THIS COMMNET NOT SATISFIED - THE 1070 DEVICE ON THE
 PUBLIC LAV DOES NOT COMPLY THIS COMMENT - THERE NEEDS
 TO BE A 1017 MIXING DEVICE ON THE WATER HEATER.
  
 2020 FPC 607.1.1 - THE THERMOSTAT ON THE WATER CANNOT
 SERVE AS THE LIMITING MEANS FOR HOT OR TEMPERED WATER.
 A MIXING DEVICE IS REQUIRED FOR THIS SECTION AND IS IN
 ADDITION TO THE LIMITING DEVICE REQUIRED FOR TEMPERED
 PUBLIC HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE
 1017 AND MUST BE INSTALLED AT THE HOT WATER SOURCE PER
 2020 FPC 613.1. PLEASE MAKE THE CHANGES ON THE WATER
 HEATER DETAIL ON PAGE P0.1 AND THE ISOMETRIC ON PAGE
 P5.1.
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-29 Cont ID  
Sent By rwbrown Date 2022-10-29 Time 09:13 Rev Time 0.00
Received By rwbrown Date 2022-10-29 Time 09:04 Sent To  
Notes
2022-10-29 09:18:261ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1 - THE THERMOSTAT ON THE WATER
 CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR TEMPERED
 WATER. A MIXING DEVICE IS REQUIRED FOR THIS SECTION AND
 IS IN ADDITION TO THE LIMITING DEVICE REQUIRED FOR
 TEMPERED PUBLIC HANDWASHING. THE DEVICE MUST COMPLY
 WITH ASSE 1017 AND MUST BE INSTALLED AT THE HOT WATER
 SOURCE PER 2020 FPC 613.1. PLEASE MAKE THE CHANGES ON
 THE WATER HEATER DETAIL ON PAGE P0.1 AND THE ISOMETRIC
 ON PAGE P5.1.
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2023-03-07 Cont ID  
Sent By rmcphers Date 2023-03-07 Time 07:41 Rev Time 0.00
Received By rmcphers Date 2023-03-07 Time 07:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2023-02-06 Cont ID  
Sent By rmcphers Date 2023-02-06 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2023-02-06 Time 11:03 Sent To  
Notes
2023-02-06 11:04:00SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 10:29 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 10:29 Sent To  
Notes
2023-01-10 10:29:24SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rmcphers Date 2022-11-01 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 08:21 Sent To  
Notes
2022-11-01 08:21:52SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-07 Cont ID  
Sent By rmcphers Date 2023-03-07 Time 07:41 Rev Time 0.00
Received By rmcphers Date 2023-03-07 Time 07:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By rmcphers Date 2023-02-06 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2023-02-06 Time 11:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 10:37 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 10:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-01 Cont ID  
Sent By rmcphers Date 2022-11-01 Time 08:32 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 08:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-02-16 Cont ID  
Sent By jroach Date 2023-02-16 Time 15:21 Rev Time 0.00
Received By jroach Date 2023-02-16 Time 15:21 Sent To  
Notes
2023-02-16 15:25:18PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE APPROVED.
  
 IT APPEARS THAT THIS PERMIT APPLICATION COVERS ONLY A
 SMALL PORTION OF AN OVERALL EXPANSION ON THE SITE.
 STAFF WOULD LIKE TO HAVE DISCUSSION AS TO HOW THE
 OVERALL DEVELOPMENT THAT IS IN REVIEW AS PART OF THE
 AMENDMENT IS PROPOSED TO BE PHASED TO ENSURE THAT THE
 PROJECT MANTAINS COMPLIANCE THROUGHOUT EACH PHASE.
 THROUGHOUT THE AMENDMENT PROCESS, THERE HAS BEEN NO
 MENTION THAT THE PROJECT WOULD BE PHASED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-01-18 Cont ID  
Sent By jroach Date 2023-01-18 Time 12:59 Rev Time 0.00
Received By jroach Date 2023-01-18 Time 12:59 Sent To  
Notes
2023-01-18 12:59:19PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE APPROVED.
  
 IT APPEARS THAT THIS PERMIT APPLICATION COVERS ONLY A
 SMALL PORTION OF AN OVERALL EXPANSION ON THE SITE.
 STAFF WOULD LIKE TO HAVE DISCUSSION AS TO HOW THE
 OVERALL DEVELOPMENT THAT IS IN REVIEW AS PART OF THE
 AMENDMENT IS PROPOSED TO BE PHASED TO ENSURE THAT THE
 PROJECT MANTAINS COMPLIANCE THROUGHOUT EACH PHASE.
 THROUGHOUT THE AMENDMENT PROCESS, THERE HAS BEEN NO
 MENTION THAT THE PROJECT WOULD BE PHASED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By jroach Date 2022-11-17 Time 12:18 Rev Time 0.00
Received By jroach Date 2022-11-17 Time 12:18 Sent To  
Notes
2022-11-17 12:20:33PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MAJOR
 AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE APPROVED.
  
 IT APPEARS THAT THIS PERMIT APPLICATION COVERS ONLY A
 SMALL PORTION OF AN OVERALL EXPANSION ON THE SITE.
 STAFF WOULD LIKE TO HAVE DISCUSSION AS TO HOW THE
 OVERALL DEVELOPMENT THAT IS IN REVIEW AS PART OF THE
 AMENDMENT IS PROPOSED TO BE PHASED TO ENSURE THAT THE
 PROJECT MANTAINS COMPLIANCE THROUGHOUT EACH PHASE.
 THROUGHOUT THE AMENDMENT PROCESS, THERE HAS BEEN NO
 MENTION THAT THE PROJECT WOULD BE PHASED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  
  