| 2022-10-13 06:51:31 | 1ST GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | ALTHOUGH THE GAS DRAWING WAS NOT SUBMITTED WITH THIS |
| | REVISION, IT WAS NOTICED THAT THERE IS A UNVENTED GAS |
| | FIREPLACE IN THE BEDROOM WHICH IS NOT ALLOWED PER 2020 |
| | FRC G2406.2. SO A RE-REVIEW OF THE ORIGINAL PLANS HAVE |
| | FOUND THE FOLLOWING. |
| | |
| | 1. 2020 FRC G2406.2 - AN UNVENTED FIREPLACE CANNOT BE |
| | IN A BEDROOM UNLESS IT FALLS UNDER ONE OF THE |
| | EXCEPTIONS OF THIS CODE SECTION. IN SAYING IT IS |
| | UNVENTED, IT DOES NOT FIT ONE OF THE EXCEPTIONS. |
| | HOWEVER, ON PAGE 13 AC-2 AC 2ND FLOOR PLAN OF THE |
| | MASTER SET, THERE'S A NOTE THAT STATES THIS IS AN |
| | "URBANA U50I-NG"?. IF THIS IS THE CASE, SUBMIT THE |
| | VENTING DETAILS ASSOCIATED WITH THIS FIREPLACE TO SHOW |
| | COMPLIANCE WITH THE CODE. |
| | |
| | 2. 2020 FRC G2413.3 - I WAS UNABLE TO FIND THE PIPE |
| | SIZING CALCULATIONS ON THE ORIGINAL SET OF PLANS. |
| | PLEASE AMEND PAGE 35 P-8 PLUMBING SPECIFICATIONS AND |
| | SHOW THE PIPE SIZING CALCULATIONS. INCLUDE THE SIZING |
| | METHOD USED, PIPE SIZES, LONGEST RUN, PIPE PRESSURES, |
| | ETC. |
| | |
| | 3. 2020 FRC G2415.11.1 - THERE IS A NOTE ON PAGE 35 P-8 |
| | THAT SAYS "ALL GAS PIPING TO BE GALVANIZED OR STEEL - |
| | SCHD 40". HOWEVER, YOUR DETAILS APPEAR TO SHOW |
| | UNDERGROUND GAS PIPING. STEEL THREADED PIPE AND/OR |
| | GALVANIZED IS NOT ALLOWED UNDERGROUND UNLESS IT MEETS |
| | SEVERAL STANDARDS AND PROTECTION LEVELS IN ACCORDANCE |
| | WITH G2415.11.2, WHICH IS EXTREMELY UNUSUAL. PLEASE |
| | DETAIL THE PIPING DIAGRAM TO SHOW COMPLIANCE WITH |
| | UNDERGROUND PIPING. |
| | |
| | 4. 2020 FRC G2439.5 - PLEASE INCLUDE WITH THE SET OF |
| | PLANS DETAILS SHOWING COMPLIANCE WITH, OR THE LACK OF |
| | NEED FOR MAKE UP AIR ASSOCIATED WITH THIS CODE SECTION |
| | FOR THE TWO DRYERS. |
| | |
| | |
| | PLEASE RESUBMIT WITH ALL GAS DRAWINGS AND DETAILS FOR |
| | REVIEW. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |