Plan Review Details - Permit 22090982
Plan Review Stops For Permit 22090982
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-09-27 Cont ID  
Sent By cpuell Date 2022-09-27 Time 16:24 Rev Time 0.00
Received By cpuell Date 2022-09-27 Time 16:24 Sent To  
Notes
2022-09-27 16:25:06ADDRESS APPROPRIATE FOR PROJECT.TWO BUILDINGS ON THIS
 PARCEL, 550 NORTHWOOD RD UNDER PERMIT 22090979 AND 602
 NORTHWOOD RD UNDER PERMIT 22090982.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-01-09 Cont ID  
Sent By pvalenti Date 2023-01-09 Time 07:51 Rev Time 0.00
Received By pvalenti Date 2023-01-09 Time 07:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-12-08 Cont ID  
Sent By pvalenti Date 2022-12-08 Time 07:10 Rev Time 0.00
Received By pvalenti Date 2022-12-08 Time 07:10 Sent To  
Notes
2022-12-08 07:13:22PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW DENIED:
  
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 10:01 Rev Time 0.00
Received By pvalenti Date 2022-10-03 Time 09:55 Sent To  
Notes
2022-10-03 10:04:27PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 FAILED ASBESTOS PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-
 QUALITY/ASBESTOS-DEMOLITION-RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-03-13 Cont ID  
Sent By pvalenti Date 2023-03-13 Time 10:38 Rev Time 0.00
Received By pvalenti Date 2023-03-13 Time 09:06 Sent To  
Notes
2023-03-13 10:42:44PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 FBC B 107.2.1, TO BE CLEAR, AS PER PLAN SUBMITTAL SHEET
 (HP S-1.0B), THE FRONT DOOR FOR 550 IS REQUIRED TO BE
 PRESERVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-01-26 Cont ID  
Sent By pvalenti Date 2023-01-26 Time 12:48 Rev Time 0.00
Received By pvalenti Date 2023-01-26 Time 12:36 Sent To  
Notes
2023-01-26 12:48:51PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 4. SEWER LATERAL CAPPING PERMIT(22121171) FINAL
 PLUMBING INSPECTION #703 IS REQUIRED
 SCHEDULE A FINAL PLUMBING INSPECTION FOR THE SEWER
 LATERAL CAPPING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-09 Cont ID  
Sent By pvalenti Date 2023-01-09 Time 08:17 Rev Time 0.00
Received By pvalenti Date 2023-01-09 Time 08:16 Sent To  
Notes
2023-01-09 08:23:04PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW FOR DEMO DENIED:
  
 4. SEWER LATERAL CAPPING PERMIT(22121171) FINAL
 PLUMBING INSPECTION #703 IS REQUIRED
 SCHEDULE A FINAL PLUMBING INSPECTION FOR THE SEWER
 LATERAL CAPPING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-08 Cont ID  
Sent By pvalenti Date 2022-12-08 Time 07:13 Rev Time 0.00
Received By pvalenti Date 2022-12-08 Time 07:13 Sent To  
Notes
2022-12-08 07:14:37PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION.
  
 3. WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFORMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 10:10 Rev Time 0.00
Received By pvalenti Date 2022-10-03 Time 09:55 Sent To  
Notes
2022-10-03 10:19:15PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFORMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT
 DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED
 FOR RODENTS.
 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART
 MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2023-04-20 Cont ID  
Sent By lquinone Date 2023-04-20 Time 13:23 Rev Time 0.00
Received By lquinone Date 2023-04-20 Time 13:23 Sent To  
Notes
2023-04-20 13:24:24PASSED WITH PROVISO: SEE NOTES ON REVISION 4.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-01-17 Cont ID  
Sent By rrossano Date 2023-01-17 Time   Rev Time 0.00
Received By rrossano Date 2023-01-17 Time   Sent To  
Notes
2023-01-17 10:16:20DEMO PROVISOS
  
 APPROVAL IS FOR SITE WORK ONLY (NO RIGHT OF WAY).
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2023-01-09 Cont ID  
Sent By rrossano Date 2023-01-09 Time   Rev Time 0.00
Received By rrossano Date 2023-01-09 Time   Sent To I
Notes
2023-01-09 12:57:59PROJECT IS UNDER SITE PLAN REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-11-21 Cont ID  
Sent By rrossano Date 2022-11-21 Time   Rev Time 0.00
Received By rrossano Date 2022-11-21 Time   Sent To  
Notes
2022-11-21 10:16:58PROJECT IS UNDER SITE PLAN REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-09-27 Cont ID  
Sent By rrossnao Date 2022-09-27 Time   Rev Time  
Received By rrossano Date 2022-09-27 Time   Sent To  
Notes
2022-09-27 11:01:39PROJECT IS STILL UNDER SITE PLAN REVIEW.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By amhamilt Date 2022-10-06 Time 16:37 Rev Time 0.00
Received By amhamilt Date 2022-10-06 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-05-15 Cont ID  
Sent By lmarchan Date 2023-05-15 Time 16:40 Rev Time 0.00
Received By lmarchan Date 2023-04-12 Time 17:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-04-12 Cont ID  
Sent By lmarchan Date 2023-04-12 Time 10:49 Rev Time 0.00
Received By lmarchan Date 2023-03-07 Time 13:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-07 Cont ID  
Sent By lmarchan Date 2023-03-07 Time 07:46 Rev Time 0.00
Received By lmarchan Date 2023-01-12 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-10 Cont ID  
Sent By lmarchan Date 2023-01-10 Time 08:10 Rev Time 0.00
Received By lmarchan Date 2023-01-06 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-08 Cont ID  
Sent By pvalenti Date 2022-12-08 Time 07:19 Rev Time 0.00
Received By pvalenti Date 2022-11-18 Time 07:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-11 Cont ID  
Sent By aoliver Date 2022-10-11 Time 08:43 Rev Time 0.00
Received By aoliver Date 2022-09-27 Time 05:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 10:25 Rev Time 0.00
Received By pvalenti Date 2022-10-03 Time 09:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status P Date 2023-05-15 Cont ID  
Sent By eschneid Date 2023-05-15 Time 16:05 Rev Time 0.25
Received By eschneid Date 2023-05-15 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2023-04-11 Cont ID  
Sent By eschneid Date 2023-04-11 Time 12:22 Rev Time 0.25
Received By eschneid Date 2023-04-11 Time 12:10 Sent To  
Notes
2023-04-11 12:23:50FAILED
  
 1) PRIOR TO THE DEMOLITION OF THE BUILDING ON THIS
 PARCEL, A PERMIT FOR CONSTRUCTION ACTIVITY MUST BE
 ISSUED. THE VIBRO PERMIT FOR THIS PARCEL IS 22120842,
 WHICH IS PART OF MASTER VIBRO PERMIT 22100245. THESE
 PERMITS HAVE NOT BEEN ISSUED, SO THIS DEMOLITION PERMIT
 CANNOT BE ISSUED.
  
 2) THE HISTORIC PRESERVATION FINAL ORDER REQUIRES THAT
 THE DOORWAY SECTION OF THE BUILDING LOCATED AT EAST END
 OF THE SITE BE PRESERVED IN PLACE.
  
 A. SHEET C1.04 WAS NOT UPDATED IN THE DRAWINGS FOLDER
 TO REFLECT THE PRESERVED DOORWAY. ALL PLANS NEED TO
 SHOW THE ACCURATE CONDITIONS.
 B. SHEET C1.14 EROSION CONTROL PLAN, WAS NOT UPDATED TO
 INCLUDE THE PRESERVED DOORWAY AND DOES NOT SHOW HOW THE
 SILT FENCE WILL BE INSTALLED AROUND THE PROTECTED
 DOORWAY.
  
 3) THE EROSION CONTROL PLANS MUST BE UPDATED TO REMOVE
 BROADWAY, THE BROADWAY/NORTHWOOD ROAD INTERSECTION, THE
 TWO PARCELS EAST OF BROADWAY, THE ALLEY BETWEEN THE
 PARCELS AND THE 24TH STREET AND NORTHWOOD ROAD FRONTING
 THESE PARCELS THAT ARE NOT INCLUDED WITHIN THE APPROVED
 LIMITS OF WORK AS SHOWN IN THE CONSTRUCTION FENCE
 PERMIT THAT IS UNDER REVIEW.
  
 4) THE DOORWAY PRESERVED AS PART OF THE 550 DEMOLITION
 MAY NOT BE REMOVED OR DAMAGED AS PART OF THIS
 DEMOLITION.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2023-03-06 Cont ID  
Sent By eschneid Date 2023-03-06 Time 17:12 Rev Time 0.25
Received By eschneid Date 2023-03-06 Time 17:11 Sent To  
Notes
2023-03-06 17:12:38FAILED
  
 1) PRIOR TO THE DEMOLITION OF THE BUILDING ON THIS
 PARCEL, A PERMIT FOR CONSTRUCTION ACTIVITY MUST BE
 ISSUED. THE VIBRO PERMIT FOR THIS PARCEL IS 22120842,
 WHICH IS PART OF MASTER VIBRO PERMIT 22100245, HAS NOT
 BEEN RESUBMITTED.
  
 2) THE HISTORIC PRESERVATION FINAL ORDER REQUIRES THAT
 THE DOORWAY SECTION OF THE BUILDING LOCATED AT EAST END
 OF THE SITE BE PRESERVED IN PLACE. THE DEMOLITION PLAN
 SHOWS THE DOORWAY BEING REMOVED, WHICH IS NOT
 PERMITTED. THE DEMOLITION PLANS MUST CLEARLY CALL OUT
 THE PRESERVATION OF THE DOORWAY AND INCLUDE DETAILS NOT
 ONLY OF HOW THE DOORWAY IS TO BE PRESERVED DURING THE
 DEMOLITION OF THE REMAINDER OF THE BUILDING, BUT ALSO
 THE DETAILS OF THE PERSERVED DOORWAY. THE DETAILS SHALL
 INCLUDE DIMENSIONS FOR THE HEIGHT, WIDTH AND DEPTH OF
 THE DOORWAY PORTION OF BE PRESERVED. THIS SHALL BE
 SHOWN ON PLAN AND IN ELEVATION.
  
 3) THE DOORWAY PRESERVATION DETAILS MUST BE REFLECTED
 ON THE ENGINEERING PLANS SUBMITTED WITH THE SITE PLAN
 APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-06 Cont ID  
Sent By eschneid Date 2023-01-06 Time 14:19 Rev Time 0.25
Received By eschneid Date 2023-01-06 Time 14:19 Sent To  
Notes
2023-01-06 14:51:171) PRIOR TO ANY DEMOLITION ON THIS PARCEL:
  
 A) A PERMIT FOR CONSTRUCTION ACTIVITY MUST BE ISSUED.
 B) THE SUBMITTED TREE ALTERATION PERMIT MUST BE
 APPROVED BY THE CITY'S PLANNING DIVISION.
  
 2) THE HISTORIC PRESERVATION FINAL ORDER REQUIRES THAT
 THE DOORWAY SECTION OF 550 NORTHWOOD ROAD BE PRESERVED
 IN PLACE. THE DEMOLITION PLANS MUST PROVIDE DETAILS OF
 HOW THE DOORWAY IS TO BE PROTECTED DURING THE
 DEMOLITION OF THIS BUILDING.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-12-07 Cont ID  
Sent By amhamilt Date 2022-12-07 Time 15:58 Rev Time 0.00
Received By amhamilt Date 2022-12-07 Time 15:58 Sent To  
Notes
2022-12-07 15:58:52THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PER NMUD REGULATIONS, (SEE PREVIOUS COMMENT) A BUILDING
 PERMIT MUST BE FULLY APPROVED PRIOR TO ZONING APPROVAL
 BEING GIVEN FOR DEMOLITION.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By amhamilt Date 2022-10-06 Time 16:36 Rev Time 0.00
Received By amhamilt Date 2022-10-06 Time 16:36 Sent To  
Notes
2022-10-06 16:36:54THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 SEC 94-210 (D)(5)
 "EXISTING BUILDINGS MAY NOT BE DESTROYED OR REMOVED
 UNTIL A BUILDING PERMIT HAS BEEN ISSUED FOR A
 REPLACEMENT BUILDING WHICH COMPLIES WITH THE NMUD
 REGULATIONS"
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  