Plan Review Details - Permit 22090958
Plan Review Stops For Permit 22090958
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 07:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2023-01-26 Time   Rev Time 0.00
Received By aoliver Date 2023-01-26 Time 09:09 Sent To  
Notes
2023-01-26 09:09:46COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By jwitmer Date 2022-11-16 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2022-11-15 Time 15:20 Sent To  
Notes
2022-11-16 07:28:39COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 08:19 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-10 Cont ID  
Sent By jwitmer Date 2023-01-10 Time 11:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-10 11:14:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22090958
 ADD: 695 S. OLIVE AVE.
 CONT: DC GREEN LLC
 TEL: 561-531-9692
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JAN. 10TH/2022
 ACTION: DENIED
  
 1) COMPLIED.
 2) BOTH THE LIFE SAFETY PLAN AND A-03 THE OUTDOOR
 SEATING AREA ARE MISSING THE ACCESSIBLE SEATING FOR
 BOTH DINING AREAS. PLEASE SHOW COMPLIANCE 2020
 FBC-ACCESSIBILITY CODE FOR THE FOLLOWING:
  
 2A) 2ND REQUEST. 2020 ACCESSIBILITY CODE 226.1 WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "CODE SECTIONS
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION".
  
 2B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES
 "CODE SECTIONS SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 2C) SEMI-COMPLIED. 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 BARS, INCLUDING RAISED OR SUNKEN DINING AREAS, AND
 OUTDOOR DINING AREAS. THE FLOOR PLAN DOES NOT SHOW
 WHERE THE ACCESSIBLE SEATING LOCATIONS.
  
 2D) 902.1. DINING SURFACES SHALL COMPLY WITH 902.2 AND
 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE,
 BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS,
 AND BOOTHS. ACCESSIBLE SEATING LOCATIONS NOT SHOWN.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2E) COMPLIED.
  
 3) COMPLIED.
  
 4) SHEET A-04 DETAIL 2. BUILDING PROVISO: NOTE C. THE
 CONTRACTORS DELEGATE ENGINEER SHALL DESIGN ALL COLD
 FORMED STEEL AND ITS CONNECTIONS TO THE BUILDING
 STRUCTURE, REFER TO ARCHITECTURAL AND STRUCTURAL
 DRAWINGS FOR REQUIRED COLD FORMED STEEL.
  
 5) COMPLIED.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By jwitmer Date 2022-11-16 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2022-11-15 Time 15:20 Sent To  
Notes
2022-11-15 15:21:07WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22090958
 ADD: 695 S. OLIVE AVE.
 CONT: DC GREEN LLC
 TEL: 561-531-9692
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV.16/2022
 ACTION: DENIED
  
 1) SHEET A-02:
 1A) ENTRY INTO RESTROOM 104 NEEDS TO SHOW THE
 MANEUVERING CLEARANCES SHOWN IN FIGURE404.2.4.1(G) 2020
 FBC-ACCESS. CODE WITH THE WIDTH OF 48 INCHES NOT 3.5
 FEET.
  
 1B) TOILET ROOMS 104 & 105 BOTH SHOW IN SWING DOORS BUT
 NOT THE 30X48 CLEAR FLOOR SPACE BEYOND THE SWING OF THE
 DOOR. PLEASE REVIEW SECTION 603.2.3. DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCES REQUIRED
 FOR ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO
 THE REQUIRED TURNING SPACE. PLEASE SEE EXCEPTION 2.
 WHERE TOILET ROOMS ARE FOR INDIVIDUAL USE AND A CLEAR
 FLOORS SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN
 THE ROOM BEYOND THE ARC OF THE DOOR SWING. WHAT IS
 MISSING IS THE REQUIRED 30X48 INCH CLEAR FLOOR SPACE
 BEYOND THE ARC OF THE DOOR. USUALLY AT A 45% ANGLE TO
 THE DOOR ENTRANCE.
  
 1C) NEITHER THE LIFE SAFETY PLAN NOR A-03 FLOOR PLAN
 IDENTIFY THE DOORS WITH DOOR IDENTIFICATION TAGS. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 1D) THE INTERIOR DINING ROOM 100 HAS 2 EXIT DOORS, ONE
 OF THESE DOORS EXITS OUT INTO THE EXTERIOR DINING ROOM
 106 WITH A OCCUPANT LOAD OF 73 PLUS 39 OF THE OCCUPANTS
 FROM THE INTERIOR DINING ROOM A TOTAL OCCUPANT LOAD OF
 102 WITH ONLY ONE EXIT. THIS OUTDOOR AREA DOES HAVE A
 RAIL/ FENCE ENCLOSURE. PLEASE SHOW COMPLIANCE WITH 2020
 FBC-BUILDING TABLE 1006.2.1 THE MAXIMUM OCCUPANT LOAD
 FOR ASSEMBLY WITH ONE DOOR IS 49 PERSONS.
  
 1E) ON BOTH THE LIFE SAFETY PLAN AND A-03 THE OUTDOOR
 SEATING AREA, THE OUTSWING DOOR CROSSES THE BUILDING
 LINE, PLEASE PROVIDE A SURVEY SHOWING WHERE THE
 PROPERTY LINE IS LOCATED. 2020 FBC-BUILDING CODE
 SECTION 320202 DOORS AND WINDOWS SHALL NOT PROJECT INTO
 THE PUBLIC-RIGHT-OF-WAY.
  
 2) BOTH THE LIFE SAFETY PLAN AND A-03 THE OUTDOOR
 SEATING AREA ARE MISSING THE ACCESSIBLE SEATING FOR
 BOTH DINING AREAS. PLEASE SHOW COMPLIANCE 2020
 FBC-ACCESSIBILITY CODE FOR THE FOLLOWING:
  
 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, BARS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2D) 902.1. DINING SURFACES SHALL COMPLY WITH 902.2 AND
 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE,
 BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS,
 AND BOOTHS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2E) SHEET A-03 SHOWS A DETAIL OF THE BAR A-05. ON SHEET
 A-05 DETAIL 8 DOES SHOW A ELEVATION AREA OF DROPPED BAR
 TO A HEIGHT OF 2 FEET 10 INCHES, WHAT IS MISSING A CUT
 SECTION THROUGH THE BAR FOR COMPLIANCE WITH 3-6.2 TOE &
 306.3 KNEE CLEARANCE.
  
 3) SHEET A-03 SEE DETAIL 1 ON SHEET A-05. SHEET A-05
 DETAILS 2-5 SHOW THE ELEVATIONS FOR THE RESTROOMS BUT
 THERE ARE NO DIMENSIONS FOR ACCESSIBILITY COMPLIANCE:
 2020 FBC-ACCESSIBILITY CODE SECTIONS:
  
 3A) 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3B) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 3C) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 3D) 603.3 MIRRORS. 2020 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3E) GRAB BARS/ RESTROOMS. 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 3F) 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE
 SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 3G) 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR
 WALL. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE.
  
 3H) TOILET PAPER DISPENSERS. 604.7. THE TOILET PAPER
 DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. THE
 OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND
 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT
 BE LOCATED BEHIND THE GRAB BARS.
  
 4) SHEET A-04 DETAILS 2 & 3 BOTH SHOW SOFFITS AND
 DROPPED CEILINGS, BUT THE SOFFIT DETAILS DO NOT SHOW
 THE STUD SIZES, SPACING, ANCHORAGE TO THE DECK ABOVE,
 TOP TRACK, SIZE OF ANCHOR, SPACING OF ANCHOR, ARE
 WASHERS REQUIRED SO NOT TO BLOW THROUGH THE TRACK, STUD
 TO STUD CONNECTION, TYPE OF SCREWS, QUANTITY OF SCREWS
 PER CONNECTION. 2020 FBC-BUILDING TABLE 2508.1 STEEL
 FRAMING FOR GYPSUM BOARD.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) PLEASE PROVIDE A ROOM FINISH SCHEDULE FOR WALLS IN
 COMPLIANCE WITH 2020 FBC-BUILDING, TABLE 803.1.1 SHOW
 ELEVATIONS, AND TYPE OF MATERIALS.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 10:45 Rev Time 0.00
Received By mpeterso Date 2023-02-08 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By mpeterso Date 2023-01-11 Time 14:08 Rev Time 0.00
Received By mpeterso Date 2023-01-11 Time 13:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By mpeterso Date 2022-11-17 Time 11:23 Rev Time 0.00
Received By mpeterso Date 2022-11-17 Time 11:23 Sent To  
Notes
2022-11-17 12:40:41ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL ALL RECEPTACLES IN KITCHEN AND BAR
 AREA AS GFI PROTECTED AS PER NEC 210.8 (B)(2) KITCHENS
 AND 210.8(B)(5) SINKS. PROVISIONS FOR NEC 210.8(B)(5)
 STATE,
 (B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREE PHASE RECEPTACLES RATED 150
 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS INSTALLED
 IN THE FOLLOWING LOCATIONS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL
  
 ONE OF THE KEY WORDS BEING ALL RECEPTACLES
  
 PROVISIONS FOR NEC 210.8(B)(5) SINKS, STATE,
 (5) SINKS ??? WHERE RECEPTACLES ARE INSTALLED WITHIN
 1.8 M (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF
 THE SINK
  
 THE KEY CONCEPT IS 6 FEET. THAT WOULD MEAN EVEN THAT
 THE RECEPTACLES ON THE OUTSIDE OF THE BAR IF THEY ARE
 WITHIN THE 6 FOOT RANGE OF THE SINK
  
 2) PLEASE INSERT A NOTE ON THE ELECTRICAL POWER PLAN
 THAT STATES, ALL VOICE, DATA, SECURITY, FIRE ALARM,
 ACCESS CONTROL, SIGNS, WALK IN COOLERS AND KITCHEN HOOD
 SYSTEM WIRING REQUIRE SEPARATE PERMITS
 3) PLEASE DETAIL THE REQUIRED CLEAR WORKING SPACE IN
 FRONT OF ELECTRICAL PANELS ON ELECTRIC POWER PLAN. NEC
 110.26
 4) AS APPLICABLE, PLEASE DETAIL TAMPER RESISTANT
 RECEPTACLES TO COMPLY WITH NEC 406.12 AS APPLIED TO NEC
 518.2 ASSEMBLY OCCUPANCIES
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By pleduc Date 2023-02-06 Time   Rev Time 0.00
Received By pleduc Date 2023-02-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-01-09 Cont ID  
Sent By pleduc Date 2023-01-09 Time   Rev Time 0.00
Received By pleduc Date 2023-01-09 Time 10:09 Sent To  
Notes
2023-01-09 10:14:35THERE ARE NO INDICATIONS THAT FIRE COMMENTS WERE
 ADDRESSED/CORRECTED.
  
 THE PREVIOUS COMMENTS FROM FIRE ARE PROVIDED BELOW.
  
 PLEASE PROVIDE SPECFIC RESPONSES TO EACH COMMENT.
  
 *******************************************************
 **********************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 02 - THERE IS AN INDICATION OF AN EXIT FROM
 THE KITCHEN INTO A PARKING GARAGE; HOWEVER, THERE IS NO
 INDICATION FO THE TRAVEL DISTANCE NOR TRAVEL PATH FROM
 THE EXIT DOOR THROUGH THE PARKING GARAGE.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THETRAVEL PATH
 & TRAVEL DISTANCE PER NFPA 101, CH 12 & CH 7 MEANS OF
 EGRESS, TO A PUBLIC WAY.
  
  
  
 2) SHEETS A 02 & A 03 - THERE ARE NO INDICATIONS OF 3
 DOOR #'S ON THE FLOOR PLAN CORRESPONDING TO THE DOOR
 SCHEDULE.
  
 THOUGH THEY MAY BE EXISTING THEY NEED TO ID'D ON THE
 DOOR SCHEDULE SHOWING COMPLIANCE WITH THE REQUIRED EXIT
 LOCK/LATCH/HARDWARE PER NFPA 101, CH 12 & CH 7 MEANS OF
 EGRESS.
  
 PLEASE EPROVIDE THE REQUIRED DETAILS.
  
  
  
 3) SHEET FS 0 & 1 - THE HOOD AND FIRE SUPPRESSION
 SYSTEMS SHALL BE SUBMITTED UNDER SEPARATE PEMITST AND
 SHOP DRAWINGS PER NFPA 96 & 17A
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT & COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By pleduc Date 2022-10-25 Time   Rev Time 0.00
Received By pleduc Date 2022-10-24 Time 16:10 Sent To  
Notes
2022-10-24 16:13:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 02 - THERE IS AN INDICATION OF AN EXIT FROM
 THE KITCHEN INTO A PARKING GARAGE; HOWEVER, THERE IS NO
 INDICATION FO THE TRAVEL DISTANCE NOT TRAVEL PATH FROM
 THE EXIT DOOR THROUGH THE PARKING GARAGE.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THETRAVEL PATH
 & TRAVEL DISTANCE PER NFPA 101, CH 12 & CH 7 MEANS OF
 EGRESS, TO A PUBLIC WAY.
  
  
  
 2) SHEETS A 02 & A 03 - THERE ARE NO INDICATIONS OF 3
 DOOR #'S ON THE FLOOR PLAN CORRESPONDING TO THE DOOR
 SCHEDULE.
  
 THOUGH THEY MAY BE EXISTING THEY NEED TO ID'D ON THE
 DOOR SCHEDULE SHOWING COMPLIANCE WITH THE REQUIRED EXIT
 LOCK/LATCH/HARDWARE PER NFPA 101, CH 12 & CH 7 MEANS OF
 EGRESS.
  
 PLEASE EPROVIDE THE REQUIRED DETAILS.
  
  
  
 3) SHEET FS 0 & 1 - THE HOOD AND FIRE SUPPRESSION
 SYSTEMS SHALL BE SUBMITTED UNDER SEPARATE PEMITST AND
 SHOP DRAWINGS PER NFPA 96 & 17A
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT & COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-01-09 Cont ID  
Sent By rwbrown Date 2023-01-09 Time 07:09 Rev Time 0.00
Received By rwbrown Date 2023-01-09 Time 07:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 12:33 Rev Time 0.00
Received By rwbrown Date 2022-11-01 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-13 Cont ID  
Sent By aoliver Date 2023-02-13 Time 09:31 Rev Time 0.00
Received By aoliver Date 2023-02-03 Time 12:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-26 Cont ID  
Sent By aoliver Date 2023-01-26 Time 09:10 Rev Time 0.00
Received By aoliver Date 2023-01-06 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By cthroop Date 2022-11-22 Time 14:23 Rev Time 0.00
Received By cthroop Date 2022-10-21 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By medwards Date 2023-02-06 Time 08:59 Rev Time 0.00
Received By medwards Date 2023-02-06 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-11 Cont ID  
Sent By medwards Date 2023-01-11 Time 13:37 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 13:37 Sent To  
Notes
2023-01-11 13:41:092ND REVIEW FMC
 PERMIT: 22090958
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-02: AHU-1 SERVES THE BAR AND DINING ROOM.
 BOTH WILL NEED OUTDOOR AIR. PLEASE SHOW THE OUTDOOR AIR
 DUCT AND TERMINATION LOCATION FOR AHU-1. FMC 403.3.1.1
  
 2) IT APPEARS THAT THE AHU-3 IS INSTALLED ABOVE THE
 CEILING AT THE BATHROOMS LOCATION. SHOW THE ACCESS FOR
 SERVICING FOR THIS UNIT AND ALL OF THE AHU???S. FMC
 306.1
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM THE DINING ROOM
 BACK TO AHU-3. FMC 601.6
  
 4) SHEET M-03: PROVIDE DETAILS ABOUT THE PROTECTION OF
 THE CONDENSING UNITS LOCATION IN THE PARKING GARAGE.
 FMC 303.4
  
 5) SHEET M-04: AIR BALANCE SCHEDULE HAS A NOTE AT THE
 TOP OF THE SCHEDULE THAT STATES - OUTDOOR DOOR WILL
 OPEN DURING BUSINESS OF OPERATION. WHY IS THIS NOTE
 HERE? WHAT ARE YOU TRYING TO ACHIEVE? FMC 508.1
  
 6) SHEET M-04: SHOW THE REQUIRED MAKE-UP AIR AND THAT
 IT MEETS THE TEMPERATURE LIMITATION OF FMC 508.1.1
  
 7) SHEET M-04: THE AIR BALANCE SCHEDULE LISTS KITCHEN
 MAKE-UP AIR AS 1,800. PLEASE SHOW HOW THIS MAKE-UP AIR
 IS BEING INTRODUCED TO THE HOODS. FMC 508.1
  
 MECHANICAL MAKEUP AIR SYSTEMS SHALL BE AUTOMATICALLY
 CONTROLLED TO START AND OPERATES SIMULTANEOUSLY WITH
 THE EXHAUST SYSTEM.
  
 8) PLEASE EXPLAIN THE 1 INCH INTERNAL INSULATION INSIDE
 THE OUTDOOR AIR DUCT FOR AHU-3.
  
 9) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE IN THIS TENANT SPACE. INCLUDE THE BAR IN THE
 OUTDOOR AIR CALCULATIONS FMC 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 09:53 Rev Time 0.00
Received By medwards Date 2022-11-08 Time 09:53 Sent To  
Notes
2022-11-08 09:53:271ST REVIEW FMC
 PERMIT: 22090958
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS REVIEWER COULD NOT COMPLETE THE REVIEW AS THERE IS
 MISSING INFORMATION.
  
 1) THE APPLICATION STATE THIS APPLICATION IS FOR AN
 INTERIOR BUILD-OUT OF A RESTAURANT PER PLANS. THE PLANS
 PROVIDED DO NOT SHOW ANY DUCTWORK FOR THIS TENANT
 BUILD-OUT. PROVIDE MECHANICAL DRAWINGS THAT INCLUDE ALL
 DUCTWORK INSTALLED IN THIS TENANT SPACE. FBC 107.3.5
  
 2) PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR
 THE KITCHEN IN THIS TENANT SPACE. THE OCCUPANCY
 ACCORDING TO FMC TABLE 403.3.1.1 IS 15. PLEASE ADJUST
 THE CALCULATIONS TO COMPLY WITH THE MINIMUM OCCUPANTS
 ACCORDING TO TABLE 403.3.1.1
  
 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.
  
 4) IS THIS A CHANGE OF USE FOR THIS AREA OF THE
 BUILDING?
  
 5) ADD A NOTE OF THE MECHANICAL DRAWING STATING THAT
 THE KITCHEN HOODS AND GREASE DUCT WILL NEED A SEPARATE
 PERMIT AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED
 UNDER THIS PERMIT.
  
 6) ADD A NOTE OF THE MECHANICAL DRAWING STATING THAT
 THE REFRIGERATION AND WALK-IN COOLER WILL NEED A
 SEPARATE PERMIT AND PLAN REVIEW AS THEY WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 7) SHEET M-03: PLEASE SHOW THAT THE CONDENSING UNITS
 THAT ARE SHOWN IN THE 2ND FLOOR GARAGE WILL HAVE THE
 MANUFACTURERS REQUIRED VENTILATION AT EACH UNIT. IS
 THIS AN OPEN GARAGE? FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 06:45 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-09 Cont ID  
Sent By rwbrown Date 2023-01-09 Time 07:09 Rev Time 0.00
Received By rwbrown Date 2023-01-09 Time 07:05 Sent To  
Notes
2023-01-09 07:09:012ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. NOT COMPLIED. THIS COMMENT ADDRESSES ALL WATER
 COMING FROM THE WATER HEATER. THERE SHOULD BE A MIXING
 DEVICE ADDED TO THE WATER HEATER. IT SHOULD BE SHOWN ON
 THE WATER HEATER DETAIL AND THE ISOMETRIC. THE DETAIL
 YOU HAVE FOR THE PUBLIC LAVS SHOULD SHOW COMPLIANCE
 WITH 1070 ONLY, NOT 1017, 1070 AND 1069.
 PAGE P-08 - 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE
 WITH THE LIMITING FOR HOT WATER DELIVERY. THE
 THERMOSTAT ON THE WATER CANNOT SERVE AS THE LIMITING
 MEANS FOR HOT OR TEMPERED WATER. A MIXING DEVICE IS
 REQUIRED FOR THIS SECTION AND IS IN ADDITION TO THE
 LIMITING DEVICE REQUIRED FOR TEMPERED PUBLIC
 HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE 1017 AND
 MUST BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC
 613.1.
  
 3. DONE
  
 4. DONE
  
 5. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rwbrown Date 2022-11-01 Time 12:18 Rev Time 0.00
Received By rwbrown Date 2022-11-01 Time 08:19 Sent To  
Notes
2022-11-01 12:18:131ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINKS, ICE
 BINS, WATER HEATER PAN DRAIN, COFFEE MAKER AND OTHER
 DEVICES THAT ARE NOT DESIGNED TO RECEIVE F.O.G
 DISCHARGES ARE GOING TO THE SANITARY AND NOT TO THE
 GREASE WASTE. PLEASE CLARIFY YOUR DRAWING TO SHOW THE
 SEPARATION OF GREASE WASTE AND SANITARY WASTE.
  
 2. PAGGE P-08 - 2020 FPC 607.1.1 - PLEASE SHOW
 COMPLIANCE WITH THE LIMITING FOR HOT WATER DELIVERY.
 THE THERMOSTAT ON THE WATER CANNOT SERVE AS THE
 LIMITING MEANS FOR HOT OR TEMPERED WATER. A MIXING
 DEVICE IS REQUIRED FOR THIS SECTION AND IS IN ADDITION
 TO THE LIMITING DEVICE REQUIRED FOR TEMPERED PUBLIC
 HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE 1017 AND
 MUST BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC
 613.1.
  
 3. 2017 WPB AMENDS 107.2.1 - THE "AHU CONDENSATE DRAIN
 CONNECTION" DETAIL ON PAGE P-08 SAYS "SEE SHEET P1.1
 FOR CONTINUTATION AND P1.1 DOES NOT EXIST. PLEASE
 DETAIL THE CONDESATE DRAIN DISPOSAL LOCATION. NOTE:
 CONDENSATE CANNOT DISCHARGE TO THE SANITARY.
  
 4. 2020 FEC C404.5.1 - PLEASE SHOW THE RECIRCULATING
 LINE IN COMPLIANCE WITH THIS SECTION. ACCORDING TO THE
 SIZES SHOWN, THE HOT LOOP NEEDS TO BE WITHIN 2 FEET OF
 THE PUBLIC LAVS AND 43 FEET OF OTHER FIXTURES.
  
 5. 2020 FEC C404.4 INSULATION OF PIPING SHALL BE IN
 COMPLIANCE WITH TABLE C403.2.10. PLEASE SHOW DETAILS
 FOR PIPING INSULATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-02-08 Cont ID  
Sent By mpeterso Date 2023-02-08 Time 10:52 Rev Time 0.00
Received By mpeterso Date 2023-02-08 Time 10:52 Sent To  
Notes
2023-02-08 10:55:47ALL PLANS PASSED SIGNATURE REVIEW. MP
2023-02-06 09:00:32MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-11 Cont ID  
Sent By mpeterso Date 2023-01-11 Time 14:15 Rev Time 0.00
Received By mpeterso Date 2023-01-11 Time 14:08 Sent To  
Notes
2023-01-11 14:18:20SIGNATURE REVIEW FAILED
  
 ALL PLANS PASSED SIGNATURE EXCEPT TWO FIRE PROTECTION
 SHEETS DO NOT DETAIL THE REQUIRED DIGITAL SIGNATURE.
 PLEASE CORRECT AS OUTLINED BELOW
  
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2023-01-11 13:41:51MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-11-16 Cont ID  
Sent By rwbrown Date 2022-11-16 Time 07:11 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-16 07:12:11SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-22 Cont ID  
Sent By aoliver Date 2022-11-22 Time 16:01 Rev Time  
Received By aoliver Date   Time   Sent To  
Notes
2022-11-08 09:54:08MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2023-02-10 Cont ID  
Sent By ckimmerl Date 2023-02-10 Time 10:26 Rev Time 0.00
Received By ckimmerl Date 2023-02-10 Time 10:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-25 Cont ID  
Sent By ckimmerl Date 2023-01-25 Time 11:48 Rev Time 0.00
Received By ckimmerl Date 2023-01-25 Time 11:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By ckimmerl Date 2022-11-21 Time 12:36 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 12:36 Sent To  
Notes
***NONE***