| Plan Review Stops For Permit 22090899 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-08 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-08 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-03 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-02 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2022-11-03 15:52:40 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE CABANA. | | | | | | 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-04-10 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-04-10 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-10-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-13 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-13 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-21 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-21 |
Time |
17:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-10-21 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-10-21 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2022-10-21 13:36:59 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PER HPB DECISION, WINDOWS MUST BE WHITE FRAMES, CLEAR | | | GLASS (LOW E PERMITTED ON SIDES AND REAR) WITH OGEE OR | | | PYRAMID MUNTINS. PLEASE REVISE PLANS OR PROVIDE LETTER | | | VERIFYING THAT WINDOWS WILL COMPLY TO THESE CONDITIONS. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-04-11 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-11 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-30 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-27 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-02-14 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-03 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-26 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-04-13 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-22 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2023-04-12 11:15:54 | RECEIPT - MU-2023-012804 - $1945.04 PAID | | 2023-03-22 15:33:39 | 3/22/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-02 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-02 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2022-11-02 16:47:31 | IMPACT FEES | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-06 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-06 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-02-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-20 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-20 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2023-02-20 11:32:18 | 1ST REVIEW FMC | | | PERMIT: 22090899 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A COMPLETE SCOPE OF WORK FOR EACH PROJECT. | | | FBC 107.3.5 | | | | | | 2) PROVIDE A DEMO DRAWING ALONG WITH THE NEW PROPOSED | | | WORK DRAWING. FBC 107.3.5 | | | | | | 3) PROVIDE THE ENERGY CALCULATIONS FOR THE ADDITION | | | SHOWN ON THE PERMIT APPLICATION AND IDENTIFY THIS ON | | | THE MECHANICAL DRAWING. FEC R402 | | | | | | 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THE NEW MECHANICAL SYSTEMS. FEC R403.7 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-04 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-04 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2022-10-04 12:38:47 | NOTHING WAS SUBMITTED FOR THE MECHANICAL WORK OF THIS | | | PROJECT. PLEASE SUBMIT A MECHANICAL SCOPE OF WORK ALONG | | | WITH THE COMPLETE DESIGN FOR THE MECHANICAL SYSTEM OF | | | THIS PROJECT. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-15 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-15 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-05 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-05 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2022-10-05 15:45:17 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC P3108.1 - THE LAUNDRY IS CURRENTLY RUNNING | | | PAST THE SHOWER AND WATER CLOSET. THE LAUNDRY CANNOT BE | | | INCLUDED IN THE WET VENT SYSTEM, BUT RATHER SHALL | | | DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-02 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-02 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2022-11-02 16:46:48 | PROVISO ON PLAN PAGE S-6: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
N |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-31 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-31 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2023-03-31 14:21:24 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | SIGNATURE REVIEW NOT REQUIRED. PAPER PLAN SHEET E-1G IS | | | NOT REQUIRED TO HAVE A DESIGN PROFESSIONAL'S | | | SIGNATURE/SEAL. THIS PLAN SHEET HAS BEEN UPLOADED TO | | | PROJECT DOX. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-15 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-15 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2023-02-15 09:53:43 | PAPER DAWINGS, SIGNATURES APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-27 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-27 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2022-09-27 08:52:10 | SIG/SEAL ON PAPER PLANS APPROVED AND SENT TO STORAGE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-21 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-21 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2023-03-21 17:01:13 | **ALL DRIVEWAYS, POOLS, MECHANICAL EQUIPMENT, | | | LANDSCAPING, PAVING TO BE DONE UNDER SEPARATE PERMIT** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-10-21 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-10-21 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2022-10-21 13:40:21 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | THE VALUE OF CONSTRUCTION EXCEEDS 50% OF THE | | | IMPROVEMENT VALUE OF THE STRUCTURE, THEREFORE A | | | SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE | | | SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD | | | | | | SEC 94-441 (B) | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|