Plan Review Stops For Permit 22090891
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-20 Cont ID  
Sent By rmcphers Date 2022-10-20 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-10-20 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By shill Date 2022-10-17 Time 10:17 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 10:17 Sent To  
Notes
2022-10-17 10:24:28WINDOWS - DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) FLORIDA PRODUCT APPROVALS
 THAT ARE LISTED ON THE WINDOW - DOOR SHOP DRAWINGS.
  
 2) THE WINDOW - DOOR SHOP DRAWINGS NEED TO BE SIGNED
 AND SEALED BY THE DESIGNER. FBC WPB 107 - - -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-12 Cont ID  
Sent By bdolan Date 2022-10-12 Time   Rev Time  
Received By bdolan Date 2022-10-11 Time 14:08 Sent To  
Notes
2022-10-12 12:41:27PLANS RESUBMITTED AND APPROVED.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
2022-10-11 14:09:12PLAN NOTES ILLEGIBLE. PLEASE RE-UPLOAD.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 10:26 Rev Time 0.00
Received By rmcphers Date 2022-09-23 Time 14:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-10-20 Cont ID  
Sent By rmcphers Date 2022-10-20 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-10-20 Time 11:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 10:24 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 10:24 Sent To  
Notes
2022-10-17 10:26:51SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ENGINEERED WINDOW / DOOR SHOP DRAWINGS DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  