Plan Review Details - Permit 22090870
| Plan Review Stops For Permit 22090870 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-16 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-16 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-26 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-26 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2022-10-26 15:02:38 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A SITE PLAN WITH THE SCOPE OF WORK SPECIFIED | | | ON IT. FBC 107.2.1 | | | 2) SPECIFY THE POOL EQUIPMENT THAT IS BEING INSTALLED | | | AND HOW IT WILL BE ANCHORED FOR WIND LOADS. FBC-R 301 | | | 3) SUBMIT CUT SHEETS FOR THE POOL EQUIPMENT AND MAIN | | | DRAIN. FBC- R 4501.6.2 AND FBC- R 4501.21.3 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2022-11-08 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2022-11-07 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2022-11-08 12:42:08 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | - FOLLOW REQUIREMENTS ON NEC 2017 ARTICLE 680 (PART I | | | AND PART II). | | | - ONE LINE DIAGRAM SHOWING BONDING AND EQUIMENT | | | GROUNDING, AND EQUIPOTENTIAL BONDING. | | | | | | RUBEN P. PERDOMO | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-22 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-11-22 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-11-22 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-05-02 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-05-02 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2023-05-02 11:00:41 | POOL EQUIPMENT NOT MOVING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-16 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-11-16 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2022-11-16 11:06:12 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.3.5.1.3 - IF REPLACING THE | | | PLUMBING AND EQUIPMENT, YOU WOULD NEED TO SHOW IT IS UP | | | TO CODE. PLEASE INCLUDE: | | | A) THE TDH CALCULATIONS TO GO ALONG WITH THE PUMP CURVE | | | B) A PIPING LAYOUT | | | C) INCLUDE THE MAIN DRAIN LOCATION LAYOUT - THE ONE | | | YOU'VE SHOWN NEEDS TWO WITH ENOUGH DISTANCE BETWEEN | | | THEM TO PREVENT ENTRAPMENT | | | D) INCLUDE THE VELOCITIES AND PIPE SIZES TO SHOW | | | MAXIMUM VELOCITIES ON SUCTION AND PRESSURE PIPING | | | E) INCLUDE THE POOL SIZE AND GPM TO SHOW PROPER TURN | | | OVER RATE | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-10-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-26 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-26 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-22 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-11-22 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-11-22 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2022-11-22 11:45:11 | FAILED | | | 11/22/2022 | | | | | | POOL EQUIPMENT CANNOT BE LOCATED ON THE NEIGHBORS | | | PROPERTY | | | | | | ARTICLE X SECTION 94-305 | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR | | | FEET INTO A SETBACK. | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] | | | | | | | | | | | | |
|
|
|