Plan Review Details - Permit 22090720
Plan Review Stops For Permit 22090720
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-02-27 Cont ID  
Sent By cpuell Date 2023-02-27 Time 15:32 Rev Time 0.00
Received By cpuell Date 2023-02-27 Time 15:32 Sent To  
Notes
2023-02-27 15:33:19ALL ADDRESSES FOR THE SOUTH OLIVE SIDE HAVE BEEN
 READDRESSED, THIS AREA OF WORK WILL NOW HAVE THE
 ADDRESS OF 101 S OLIVE AVE

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-11-30 Cont ID  
Sent By cpuell Date 2022-11-30 Time 08:57 Rev Time 0.00
Received By cpuell Date 2022-11-30 Time 08:57 Sent To  
Notes
2022-11-30 09:08:47SPOKE WITH PAUL SNITKIN, PROPOSED NEW ADDRESSES FOR ALL
 THE SUITES WOULD NOT AGREE TO ANY OF THE PROPOSED
 ADDRESSES. ADDRESSES PROPOSED WERE 300 CLEMATIS ST, 103
 S OLIVE AVE, 105 S OLIVE AVE, 107 S OLIVE AVE, 107 S
 OLIVE AVE SUITE 200 AND 107 S OLIVE AVE SUITE 300. PAUL
 SNITKIN STATED HE WOULD GIVE ME THE OWNERS INFORMATION
 SO THAT I COULD DISCUSS THE ADDRESSES, HAVE NOT
 RECIEVED THAT INFORMATION. NEW SUITE ADDRESSES NEED TO
 BE ESTABLISHED FOR ALL THE TENANT SPACES. PLEASE HAVE
 OWNERS CONTACT [email protected] OR CALL
 561-805-6659

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-11-08 Cont ID  
Sent By cpuell Date 2022-11-08 Time 13:21 Rev Time 0.00
Received By cpuell Date 2022-11-08 Time 13:21 Sent To  
Notes
2022-11-08 13:23:07YOUR RESPONCE:
 THE PROCESS OF DETERMINING THE NEW ADDRESSES FOR THESE
 FIRST FLOOR SUITES IS BEING REVIEW BY THE NECESSARY
 PARTIES AND MAY BE PRESENTED AT A LATER DATE.
  
 ADDRESSING RESPONCE:
 WE ARE WAITING FOR RESPONCES FROM THE APPLICANT ON THIS
 ISSUE, THE PERMIT NEEDS TO HAVE ASSIGNED SUITE
 ADDRESSES, OR IT CANNOT BE ISSUED. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By cpuell Date 2022-10-25 Time 11:40 Rev Time 0.00
Received By cpuell Date 2022-10-25 Time 11:40 Sent To  
Notes
2022-10-25 11:41:02A SUITE ADDRESS NEEDS TO BE ASSIGNED TO THIS OFFICE
 AREA. PLEASE PROVIDE A FLOOR PLAN FOR THE WHOLE FLOOR
 THAT THE OFFICE SPACE WILL OCCUPY, SHOWING THE CURRENT
 ADDRESSES FOR ALL TENANTS. THE SECOND FLOOR ALSO NEEDS
 TO BE ASSIGNED ADDRESSES, PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-11-08 Cont ID  
Sent By jwitmer Date 2022-11-08 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2022-11-08 Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 09:43 Rev Time  
Received By jwitmer Date 2022-10-25 Time   Sent To  
Notes
2022-10-25 09:43:34COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-03-20 Cont ID  
Sent By jwitmer Date 2023-03-20 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2023-03-20 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-11-29 Cont ID  
Sent By jwitmer Date 2022-11-29 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2022-11-29 Time 10:39 Sent To  
Notes
2022-11-29 09:17:32WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22090720
 ADD: 300 CLEMATIS ST, SUITE:
 CONT: GREAT DANE PETROLEUM
 TEL: 954-214-4087
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. NOV. 29TH/ 2022
 ACTION: DENIED
  
 1) 3RD REQUEST. PLEASE NOTE A ADDRESSING STOP WILL BE
 ADDED TO THIS PERMIT, THE COVERSHEET & TITLE BLOCK JUST
 STATES THE ADDRESS OF 300 CLEMATIS ST. ADD A UNIT
 NUMBER FOR THE FIRST FLOOR UNIT WHERE WORK IS OCCUR
 UNDER THIS PERMIT. THIS IS A 3-STORY BUILDING WITH THE
 LIFE SAFETY PLAN STATING FIRST LEVEL SAFETY PLAN. IT IS
 HARD TO DISTINGUISH WHERE THE WORK IS TO OCCUR, ON
 WHICH FLOOR. 2020 FBC-B 501.2 ADDRESS IDENTIFICATION.
 NEW AND EXISTING BUILDINGS SHALL BE PROVIDED WITH
 APPROVED ADDRESS IDENTIFICATION.
  
 2) COMPLIED.
  
 3) 3RD REQUEST, 3A-3F. THE RESPONSE LETTER STATES THE
 NEW TENANT SEPARATION WALL AND EXTERIOR WALL AND (2)
 NEW EXTERIOR DOORS ARE TO BE UNDER SEPARATE PERMIT. THE
 COMMENTS STAND UNTIL THE SEPARATE PERMIT IS APPLIED FOR
 AND THE NEW PERMIT NUMBER APPLIED TO SHEETS A100A &
 A101, STATING THIS WORK IS UNDER PERMIT 2012XXXX.
  
 2ND REVIEW. SEMI-COMPLIED. WITH THE EXISTING FLOOR PLAN
 IT IS APPARENT THAT THERE WILL BE ONE NEW EXTERIOR DOOR
 AND A EXTERIOR DOUBLE SET OF DOORS BEING REMOVED AND A
 NEW OUTSWING DOOR BEING ADDED.
 1ST ROUND OF COMMENTS. PLEASE PROVIDE A EXISTING FLOOR
 PLAN AND PROPOSED FLOOR PLAN TO SEE EXISTING AND
 PROPOSED WORK. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 3A) PLEASE PROVIDE A DETAIL FOR THE NEW DISMISSING
 TENANT WALL. THE EXISTING TENANT SEPARATION WALL
 SEPARATES THE STAIRWELL FORM THE PROPOSED TENANT SPACE.
 THE FUTURE TENANT SEPARATION WALL IS NEW AND NEEDS A
 DETAIL FOR THE TYPE OF WALL AND IF THE DESIGNER
 REQUIRES THE TENANT SEPARATION WALL TO BE FIRE RATED.
 2020 FBC-BUILDING CODE SECTION 708.1.
  
 3B) SINCE THE EXTERIOR OF THE BUILDING (DOORS) ARE NEW
 AND RELOCATED PLEASE PROVIDE THE WIND DESIGN CRITERIA,
 NOTE NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF, (3
 STORY BUILDING).
 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3B1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3B2. RISK CATEGORY.
  
 3B3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 3B4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3B5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3B6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3C) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
  
 3D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3E) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3F) PLEASE PROVIDE A STRUCTURAL WALL DETAIL FOR THE
 PORTION OF EXTERIOR WALL THAT IS BEING REFRAMED WITH
 TWO NEW DOOR LOCATIONS. IT APPEARS TO BE FRAMED INTO
 EITHER AN EXTERIOR DOOR OR WINDOW. HOW WILL THIS BE
 FRAMED TO MEET WIND LOADING. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-08 Cont ID  
Sent By jwitmer Date 2022-11-08 Time 10:40 Rev Time 0.00
Received By jwitmer Date 2022-11-08 Time   Sent To  
Notes
2022-11-08 10:40:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22090720
 ADD: 300 CLEMATIS ST, SUITE:
 CONT: GREAT DANE PETROLEUM
 TEL: 954-214-4087
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 08TH/ 2022
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE NOTE A ADDRESSING STOP WILL BE
 ADDED TO THIS PERMIT, THE COVERSHEET & TITLE BLOCK JUST
 STATES THE ADDRESS OF 300 CLEMATIS ST. ADD A UNIT
 NUMBER FOR THE FIRST FLOOR UNIT WHERE WORK IS OCCUR
 UNDER THIS PERMIT. THIS IS A 3-STORY BUILDING WITH THE
 LIFE SAFETY PLAN STATING FIRST LEVEL SAFETY PLAN. IT IS
 HARD TO DISTINGUISH WHERE THE WORK IS TO OCCUR, ON
 WHICH FLOOR. 2020 FBC-B 501.2 ADDRESS IDENTIFICATION.
 NEW AND EXISTING BUILDINGS SHALL BE PROVIDED WITH
 APPROVED ADDRESS IDENTIFICATION.
  
 2) COMPLIED.
  
 3) SEMI-COMPLIED. WITH THE EXISTING FLOOR PLAN IT IS
 APPARENT THAT THERE WILL BE ONE NEW EXTERIOR DOOR AND A
 EXTERIOR DOUBLE SET OF DOORS BEING REMOVED AND A NEW
 OUTSWING DOOR BEING ADDED.
 1ST ROUND OF COMMENTS. PLEASE PROVIDE A EXISTING FLOOR
 PLAN AND PROPOSED FLOOR PLAN TO SEE EXISTING AND
 PROPOSED WORK. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 3A) PLEASE PROVIDE A DETAIL FOR THE NEW DISMISSING
 TENANT WALL. THE EXISTING TENANT SEPARATION WALL
 SEPARATES THE STAIRWELL FORM THE PROPOSED TENANT SPACE.
 THE FUTURE TENANT SEPARATION WALL IS NEW AND NEEDS A
 DETAIL FOR THE TYPE OF WALL AND IF THE DESIGNER
 REQUIRES THE TENANT SEPARATION WALL TO BE FIRE RATED.
 2020 FBC-BUILDING CODE SECTION 708.1.
 3B) SINCE THE EXTERIOR OF THE BUILDING (DOORS) ARE NEW
 AND RELOCATED PLEASE PROVIDE THE WIND DESIGN CRITERIA,
 NOTE NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF, (3
 STORY BUILDING).
 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3B1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3B2. RISK CATEGORY.
  
 3B3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 3B4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3B5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3B6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3C) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
  
 3D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3E) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3F) PLEASE PROVIDE A STRUCTURAL WALL DETAIL FOR THE
 PORTION OF EXTERIOR WALL THAT IS BEING REFRAMED WITH
 TWO NEW DOOR LOCATIONS. IT APPEARS TO BE FRAMED INTO
 EITHER AN EXTERIOR DOOR OR WINDOW. HOW WILL THIS BE
 FRAMED TO MEET WIND LOADING. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 10:08 Rev Time 0.00
Received By jwitmer Date 2022-10-25 Time 09:03 Sent To  
Notes
2022-10-25 10:08:54WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22090720
 ADD: 300 CLEMATIS ST, SUITE:
 CONT: GREAT DANE PETROLEUM
 TEL: 954-214-4087
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 25TH/ 2022
 ACTION: DENIED
  
 1) PLEASE NOTE A ADDRESSING STOP WILL BE ADDED TO THIS
 PERMIT, THE COVERSHEET & TITLE BLOCK JUST STATES THE
 ADDRESS OF 300 CLEMATIS ST. THIS IS A 3-STORY BUILDING
 WITH THE LIFE SAFETY PLAN STATING FIRST LEVEL SAFETY
 PLAN. IT IS HARD TO DISTINGUISH WHERE THE WORK IS TO
 OCCUR, ON WHICH FLOOR. 2020 FBC-B 501.2 ADDRESS
 IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE
 PROVIDED WITH APPROVED ADDRESS IDENTIFICATION.
  
 2) PLEASE NOTE ON THE LIFE SAFETY PLAN THERE ARE 2
 DIRECTION NORTH ARROWS ONE DOES POINT NORTH (LEFT SIDE
 OF PAGE) WHILE THE NORTH ARROW (RIGHT SIDE OF PAGE)
 ACTUALLY POINTS WEST.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3) PLEASE PROVIDE A EXISTING FLOOR PLAN AND PROPOSED
 FLOOR PLAN TO SEE EXISTING AND PROPOSED WORK. 2020 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-24 Cont ID  
Sent By mpeterso Date 2023-03-24 Time 15:52 Rev Time 0.00
Received By mpeterso Date 2023-03-24 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-21 Cont ID  
Sent By mpeterso Date 2023-03-21 Time 10:01 Rev Time 0.00
Received By mpeterso Date 2023-03-21 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By mpeterso Date 2022-10-24 Time 08:15 Rev Time 0.00
Received By mpeterso Date 2022-10-24 Time 08:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-03-16 Cont ID  
Sent By pleduc Date 2023-03-16 Time   Rev Time 0.00
Received By pleduc Date 2023-03-16 Time 09:37 Sent To  
Notes
2023-03-16 09:37:39FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 ACCESS CONTROL/CARD READERS SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS COMPLYING WITH NFPA
 101 CH. 7 MEANS OF EGRESS WERE APPLICABLE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-11-29 Cont ID  
Sent By pleduc Date 2022-11-29 Time   Rev Time 0.00
Received By pleduc Date 2022-11-29 Time 10:25 Sent To  
Notes
2022-11-29 10:26:17FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 ACCESS CONTROL/CARD READERS SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS COMPLYING WITH NFPA
 101 CH. 7 MEANS OF EGRESS WERE APPLICABLE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-08 Cont ID  
Sent By pleduc Date 2022-11-08 Time   Rev Time 0.00
Received By pleduc Date 2022-11-08 Time 11:36 Sent To  
Notes
2022-11-08 11:37:05FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 ACCESS CONTROL/CARD READERS SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS COMPLYING WITH NFPA
 101 CH. 7 MEANS OF EGRESS WERE APPLICABLE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By pleduc Date 2022-10-06 Time   Rev Time 0.00
Received By pleduc Date 2022-10-05 Time 12:58 Sent To  
Notes
2022-10-05 13:10:26FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 ACCESS CONTROL/CARD READERS SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS COMPLYING WITH NFPA
 101 CH. 7 MEANS OF EGRESS WERE APPLICABLE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-03-24 Cont ID  
Sent By mpeterso Date 2023-03-24 Time 15:53 Rev Time 0.00
Received By mpeterso Date 2023-03-23 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-23 Cont ID  
Sent By medwards Date 2023-03-23 Time 09:05 Rev Time 0.00
Received By medwards Date 2023-03-22 Time 06:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-21 Cont ID  
Sent By mpeterso Date 2023-03-21 Time 10:10 Rev Time 0.00
Received By mpeterso Date 2023-03-14 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-30 Cont ID  
Sent By cpuell Date 2022-11-30 Time 09:08 Rev Time 0.00
Received By cpuell Date 2022-11-28 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-14 Cont ID  
Sent By medwards Date 2022-11-14 Time 06:49 Rev Time 0.00
Received By medwards Date 2022-11-06 Time 07:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-25 Cont ID  
Sent By cpuell Date 2022-10-25 Time 11:41 Rev Time 0.00
Received By cpuell Date 2022-10-04 Time 10:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 09:43 Rev Time  
Received By jwitmer Date 2022-10-15 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-03-23 Cont ID  
Sent By medwards Date 2023-03-23 Time 09:05 Rev Time 0.00
Received By medwards Date 2023-03-23 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-03-16 Cont ID  
Sent By medwards Date 2023-03-16 Time 14:34 Rev Time 0.00
Received By medwards Date 2023-03-16 Time 14:34 Sent To  
Notes
2023-03-16 14:35:47THE ENGINEER OF RECORD MUST DIGITALLY SIGN EACH
 DRAWING. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-11-30 Cont ID  
Sent By medwards Date 2022-11-30 Time 05:49 Rev Time 0.00
Received By medwards Date 2022-11-30 Time 05:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-14 Cont ID  
Sent By medwards Date 2022-11-14 Time 06:44 Rev Time 0.00
Received By medwards Date 2022-11-14 Time 06:44 Sent To  
Notes
2022-11-14 06:47:20PROVIDE A DAWING SHOWING THE LOCATION OF THE CONDENSING
 UNIT. FBC 107.3.5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 10:22 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 10:22 Sent To  
Notes
2022-10-18 10:22:171ST REVIEW FMC
 PERMIT: 22090720
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR THE MECHANICAL DESIGN.
 FBC 107.3.5
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. FEC C403.2.1
  
 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 PROJECT. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 4) PROVIDE A MECHANICAL DEMO PLAN FOR THE WORK BEING
 REMOVED OR CHANGED. FBC 107.3.5
  
 5) PROVIDE INFORMATION FOR THE MECHANICAL SYSTEMS
 SHOWING THEM MEET THE SPACE HEATING REQUIREMENTS OF FMC
 309.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-03-23 Cont ID  
Sent By rwbrown Date 2023-03-23 Time 06:39 Rev Time 0.00
Received By rwbrown Date 2023-03-23 Time 06:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-17 Cont ID  
Sent By rwbrown Date 2023-03-17 Time 09:29 Rev Time 0.00
Received By rwbrown Date 2023-03-17 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-10-11 Cont ID  
Sent By rwbrown Date 2022-10-11 Time 14:50 Rev Time 0.00
Received By rwbrown Date 2022-10-11 Time 14:49 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By dbattles Date 2022-12-08 Time 09:02 Rev Time 0.00
Received By dbattles Date 2022-12-08 Time 09:02 Sent To  
Notes
2022-12-08 09:03:01INSPECTIONS
 PAPERWORK SENT TO FILENET

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-03-24 Cont ID  
Sent By mpeterso Date 2023-03-24 Time 15:52 Rev Time 0.00
Received By mpeterso Date 2023-03-24 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-03-23 Cont ID  
Sent By rwbrown Date 2023-03-23 Time 06:42 Rev Time 0.00
Received By rwbrown Date 2023-03-23 Time 06:42 Sent To  
Notes
2023-03-23 06:43:03SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 THE ELECTRICAL PAGES ARE NOT DIGITALLY SEALED
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-03-21 Cont ID  
Sent By mpeterso Date 2023-03-21 Time 10:05 Rev Time 0.00
Received By mpeterso Date 2023-03-21 Time 10:01 Sent To  
Notes
2023-03-21 10:10:30SIGNATYRE REVIEW FAILED
 1) THE SHEETS CONTAINING THE EOR SEAL FOR VALAZQUEZ AND
 MORAS DO NOT DETAIL THE REQUIRED DIGITAL SIGNATURES.
 PLEASE CORRECT AS OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2023-03-16 14:36:08THE ENGINEER OF RECORD MUST DIGITALLY SIGN EACH
 DRAWING. FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-30 Cont ID  
Sent By medwards Date 2022-11-30 Time 05:49 Rev Time 0.00
Received By medwards Date 2022-11-30 Time 05:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-14 Cont ID  
Sent By medwards Date 2022-11-14 Time 06:49 Rev Time 0.00
Received By medwards Date 2022-11-14 Time 06:48 Sent To  
Notes
2022-11-14 06:47:59MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By mpeterso Date 2022-10-24 Time 08:16 Rev Time 0.00
Received By mpeterso Date 2022-10-24 Time 08:16 Sent To  
Notes
2022-10-24 08:17:12ALL PLANS PASSED SIGNATURE REVIEW
2022-10-18 10:23:24MECHANICAL DIGITAL SIGNATURES APPROVED ME
  