| Plan Review Stops For Permit 22090686 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-03-30 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-03-30 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-12-19 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-12-19 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2022-12-19 15:46:55 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED.SUBMIT A LETTER FROM THE STRUCTURAL | | | ENGINEER OF RECORD STATING THAT THESE LIFTS ARE | | | APPROVED FOR USE IN THIS PROJECT AND THAT THE STRUCTURE | | | IS CAPABLE OF SUPPORTING ALL LOADS RESULTING FROM THE | | | CAR LIFTS WHEN FILLED TO CAPACITY. FBC 107.2.1 | | | | | | 2) NOT RESOLVED. SPECIFY WHAT TYPE OF VEHICLE BARRIERS | | | OR GUARDS WILL BE USED TO PREVENT THE VEHICLES FROM | | | FALLING FROM THE LIFTS. FBC 406.4.2 | | | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-17 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-17 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2022-11-17 15:10:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A LETTER FROM THE STRUCTURAL ENGINEER OF | | | RECORD STATING THAT THESE LIFTS ARE APPROVED FOR USE IN | | | THIS PROJECT AND THAT THE STRUCTURE IS CAPABLE OF | | | SUPPORTING ALL LOADS RESULTING FROM THE CAR LIFTS WHEN | | | FILLED TO CAPACITY. FBC 107.2.1 | | | | | | 2) SPECIFY WHAT TYPE OF VEHICLE BARRIERS OR GUARDS WILL | | | BE USED TO PREVENT THE VEHICLES FROM FALLING FROM THE | | | LIFTS. FBC 406.4.2 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-15 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-15 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-12-12 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-12 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-12 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2022-12-12 08:44:37 | PREVIOUS COMMENTS NOT ADDRESSED. PLEASE PROVIDE A | | | RESPONSE NARRITIVE AND APPROPRIATE DRAWINGS FOR ALL | | | COMMENT RESPONSES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-05 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-05 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2022-10-05 14:50:27 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE DETAILS AS TO LOCATION OF ALL POWER | | | PACKS (IT APPEARS ONLY 2 ARE SHOWN). IN ADDITION PLEASE | | | PROVIDE FLOOR PLAN DETAILING LOCATION OF ELECTRIC | | | PANEL(S) FEEDING POWER PACKS, PANEL SCHEDULES , LOAD | | | CALCULATIONS FOR UPSTREAM PANEL(S) AND OVERCURRENT | | | PROTECTION. | | | 2) PLEASE CLARIFY IF THE UNITS OPERATE HYDRAULICALLY OR | | | ELECTRICALLY AS THE SPECIFICATIONS LACK CLARITY AS TO | | | THEIR OPERATION. SPECIFICATIONS PROVIDED DETAIL (3) 16 | | | AMP DELAYED ACTION MAIN FUSES PER UNIT. IF UNITS ARE | | | INDIVIDUALLY ELECTRICLY POWERED , PLEASE PROVIDE | | | DETAILS ON ALL 208 VOLT CONDUIT AND CONDUCTOR RUNS. IF | | | HYDAULICALLY OPERATED PROVIDE DETAILS OF HYDRAULIC | | | LINES. | | | 3) PLEASE PROVIDE CLARITY ON CACULATION DOCUMENTS | | | PROVIDED STATING THAT 21 CAR LIFTS WILL BE INSTALLED AT | | | LEVEL 4 AND 54 CARLIFTS ARE TO BE INSTALLED AT | | | LEVEL 5 AT THE ADDRESS OF C F BRICKELL HOTEL LOCATED AT | | | 8TH STREET IN MIAMI FLORIDA | | | 4) SEE FAILED SIGNATURE REVIEW | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-11-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-11-17 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2022-11-17 10:25:32 | FIRE PROVISO: | | | | | | THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MODIFIED | | | UNDER SEPARATE PERMIT & SHOP DRAWINGS. | | | | | | ENSURE COMPLIANCE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-03-30 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-03-08 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-12-19 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-12-02 |
Time |
16:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-17 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-19 |
Time |
06:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-09 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-09 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2023-03-09 08:23:21 | PROVIDE THE INFORMATION REQUESTED IN THE LAST REVIEW | | | CYCLE BELOW: | | | | | | PLEASE PROVIDE THE HYDRAULIC DESIGN REQUIRED FOR | | | CONNECTING THESE LIFTS TOGETHER INCLUDING STORAGE FOR | | | THE HYDRALUICS AND PIPE SIZES NEEDED TO PIPE THESE | | | LIFTS TOGETHER, FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-13 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-13 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2022-12-13 10:29:52 | PLEASE PROVIDE THE HYDRAULIC DESIGN REQUIRED FOR | | | CONNECTING THESE LIFTS TOGETHER INCLUDING STORAGE FOR | | | THE HYDRALUICS AND PIPE SIZES NEEDED TO PIPE THESE | | | LIFTS TOGETHER, FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-27 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-27 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2022-11-16 16:44:15 | THIS SUBMITTAL APPEARS TO BE MISSING ALOT OF | | | INFORMATION. PLEASE SUBMIT A COMPLETE DESIGN FOR THIS | | | PROJECT INCLUDING STRUCTURAL DETAILS FOR THE SUPPORT OF | | | THESE LIFTS, OR A LETTER FROM THE EOR STATING THAT THE | | | WEIGHT OF THIS DESIGN WAS TAKEN INTO CONCIDERATION WHEN | | | DESIGNING THE PARKING GARAGE FLOOR. THE HYDRAULIC | | | DESIGN REQUIRED FOR CONNECTING THESE LIFTS TOGETHER | | | INCLUDING STORAGE FOR THE HYDRALUICS AND PIPE SIZES | | | NEEDED TO PIPE THESE LIFTS TOGETHER, PLEASE ALSO | | | INCLUDE THE ELECTRICAL DESIGN FOR THIS PROJECT. THIS | | | PROJECT WILL REQUIRE A BUILDING SUB PERMIT AND AN | | | ELECTRICAL SUB PERMIT. PLEASE ALSO CHECK WITH THE FIRE | | | CHIEF FOR THE SPRINKLER PLACEMENT. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-15 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-15 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-13 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-13 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-05 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-05 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2022-10-05 14:57:35 | SIGNATURE REVIEW FAILED | | | DOCUMENT SUBMITTED , CALCULATIONS FOR KLAUS LIFT | | | ANCHORAGE TO CONCRETE APPEARS TO BE A COPY OF ENGINEERS | | | DIGITAL SIGNATURE AS IT CANNOT BE VERIFIED WITH EITHER | | | BLUEBEAM OR ADOBE SOFTWARE. PLEASE CORRECT AS | | | APPLICABLE. PLEASE NOTE IT APPEARS TO BE A DOCUMENT FOR | | | A DIFFERENT PROJECT IN MIAMI FLORIDA | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|