Plan Review Details - Permit 22090686
Plan Review Stops For Permit 22090686
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-30 Cont ID  
Sent By rmcdouga Date 2023-03-30 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2023-03-30 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-19 Cont ID  
Sent By rmcdouga Date 2022-12-19 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2022-12-19 Time 15:46 Sent To  
Notes
2022-12-19 15:46:55PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED.SUBMIT A LETTER FROM THE STRUCTURAL
 ENGINEER OF RECORD STATING THAT THESE LIFTS ARE
 APPROVED FOR USE IN THIS PROJECT AND THAT THE STRUCTURE
 IS CAPABLE OF SUPPORTING ALL LOADS RESULTING FROM THE
 CAR LIFTS WHEN FILLED TO CAPACITY. FBC 107.2.1
  
 2) NOT RESOLVED. SPECIFY WHAT TYPE OF VEHICLE BARRIERS
 OR GUARDS WILL BE USED TO PREVENT THE VEHICLES FROM
 FALLING FROM THE LIFTS. FBC 406.4.2
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-17 Cont ID  
Sent By rmcdouga Date 2022-11-17 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2022-11-17 Time 10:50 Sent To  
Notes
2022-11-17 15:10:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A LETTER FROM THE STRUCTURAL ENGINEER OF
 RECORD STATING THAT THESE LIFTS ARE APPROVED FOR USE IN
 THIS PROJECT AND THAT THE STRUCTURE IS CAPABLE OF
 SUPPORTING ALL LOADS RESULTING FROM THE CAR LIFTS WHEN
 FILLED TO CAPACITY. FBC 107.2.1
  
 2) SPECIFY WHAT TYPE OF VEHICLE BARRIERS OR GUARDS WILL
 BE USED TO PREVENT THE VEHICLES FROM FALLING FROM THE
 LIFTS. FBC 406.4.2
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 11:35 Rev Time 0.00
Received By mpeterso Date 2023-03-15 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-12-12 Cont ID  
Sent By mpeterso Date 2022-12-12 Time 08:42 Rev Time 0.00
Received By mpeterso Date 2022-12-12 Time 08:42 Sent To  
Notes
2022-12-12 08:44:37PREVIOUS COMMENTS NOT ADDRESSED. PLEASE PROVIDE A
 RESPONSE NARRITIVE AND APPROPRIATE DRAWINGS FOR ALL
 COMMENT RESPONSES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-05 Cont ID  
Sent By mpeterso Date 2022-10-05 Time 14:29 Rev Time 0.00
Received By mpeterso Date 2022-10-05 Time 14:29 Sent To  
Notes
2022-10-05 14:50:27ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE DETAILS AS TO LOCATION OF ALL POWER
 PACKS (IT APPEARS ONLY 2 ARE SHOWN). IN ADDITION PLEASE
 PROVIDE FLOOR PLAN DETAILING LOCATION OF ELECTRIC
 PANEL(S) FEEDING POWER PACKS, PANEL SCHEDULES , LOAD
 CALCULATIONS FOR UPSTREAM PANEL(S) AND OVERCURRENT
 PROTECTION.
 2) PLEASE CLARIFY IF THE UNITS OPERATE HYDRAULICALLY OR
 ELECTRICALLY AS THE SPECIFICATIONS LACK CLARITY AS TO
 THEIR OPERATION. SPECIFICATIONS PROVIDED DETAIL (3) 16
 AMP DELAYED ACTION MAIN FUSES PER UNIT. IF UNITS ARE
 INDIVIDUALLY ELECTRICLY POWERED , PLEASE PROVIDE
 DETAILS ON ALL 208 VOLT CONDUIT AND CONDUCTOR RUNS. IF
 HYDAULICALLY OPERATED PROVIDE DETAILS OF HYDRAULIC
 LINES.
 3) PLEASE PROVIDE CLARITY ON CACULATION DOCUMENTS
 PROVIDED STATING THAT 21 CAR LIFTS WILL BE INSTALLED AT
 LEVEL 4 AND 54 CARLIFTS ARE TO BE INSTALLED AT
 LEVEL 5 AT THE ADDRESS OF C F BRICKELL HOTEL LOCATED AT
 8TH STREET IN MIAMI FLORIDA
 4) SEE FAILED SIGNATURE REVIEW
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By pleduc Date 2022-11-17 Time   Rev Time 0.00
Received By pleduc Date 2022-11-17 Time 10:24 Sent To  
Notes
2022-11-17 10:25:32FIRE PROVISO:
  
 THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MODIFIED
 UNDER SEPARATE PERMIT & SHOP DRAWINGS.
  
 ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-30 Cont ID  
Sent By rmcdouga Date 2023-03-30 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2023-03-08 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-19 Cont ID  
Sent By rmcdouga Date 2022-12-19 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2022-12-02 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-17 Cont ID  
Sent By rmcdouga Date 2022-11-17 Time 15:11 Rev Time 0.00
Received By rmcdouga Date 2022-09-19 Time 06:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-03-09 Cont ID  
Sent By medwards Date 2023-03-09 Time 08:20 Rev Time 0.00
Received By medwards Date 2023-03-09 Time 08:20 Sent To  
Notes
2023-03-09 08:23:21PROVIDE THE INFORMATION REQUESTED IN THE LAST REVIEW
 CYCLE BELOW:
  
 PLEASE PROVIDE THE HYDRAULIC DESIGN REQUIRED FOR
 CONNECTING THESE LIFTS TOGETHER INCLUDING STORAGE FOR
 THE HYDRALUICS AND PIPE SIZES NEEDED TO PIPE THESE
 LIFTS TOGETHER, FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-13 Cont ID  
Sent By medwards Date 2022-12-13 Time 10:28 Rev Time 0.00
Received By medwards Date 2022-12-13 Time 10:28 Sent To  
Notes
2022-12-13 10:29:52PLEASE PROVIDE THE HYDRAULIC DESIGN REQUIRED FOR
 CONNECTING THESE LIFTS TOGETHER INCLUDING STORAGE FOR
 THE HYDRALUICS AND PIPE SIZES NEEDED TO PIPE THESE
 LIFTS TOGETHER, FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By medwards Date 2022-09-27 Time 15:03 Rev Time 0.00
Received By medwards Date 2022-09-27 Time 15:03 Sent To  
Notes
2022-11-16 16:44:15THIS SUBMITTAL APPEARS TO BE MISSING ALOT OF
 INFORMATION. PLEASE SUBMIT A COMPLETE DESIGN FOR THIS
 PROJECT INCLUDING STRUCTURAL DETAILS FOR THE SUPPORT OF
 THESE LIFTS, OR A LETTER FROM THE EOR STATING THAT THE
 WEIGHT OF THIS DESIGN WAS TAKEN INTO CONCIDERATION WHEN
 DESIGNING THE PARKING GARAGE FLOOR. THE HYDRAULIC
 DESIGN REQUIRED FOR CONNECTING THESE LIFTS TOGETHER
 INCLUDING STORAGE FOR THE HYDRALUICS AND PIPE SIZES
 NEEDED TO PIPE THESE LIFTS TOGETHER, PLEASE ALSO
 INCLUDE THE ELECTRICAL DESIGN FOR THIS PROJECT. THIS
 PROJECT WILL REQUIRE A BUILDING SUB PERMIT AND AN
 ELECTRICAL SUB PERMIT. PLEASE ALSO CHECK WITH THE FIRE
 CHIEF FOR THE SPRINKLER PLACEMENT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 14:07 Rev Time 0.00
Received By mpeterso Date 2023-03-15 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-13 Cont ID  
Sent By medwards Date 2022-12-13 Time 10:32 Rev Time 0.00
Received By medwards Date 2022-12-13 Time 10:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-05 Cont ID  
Sent By mpeterso Date 2022-10-05 Time 14:52 Rev Time 0.00
Received By mpeterso Date 2022-10-05 Time 14:52 Sent To  
Notes
2022-10-05 14:57:35SIGNATURE REVIEW FAILED
 DOCUMENT SUBMITTED , CALCULATIONS FOR KLAUS LIFT
 ANCHORAGE TO CONCRETE APPEARS TO BE A COPY OF ENGINEERS
 DIGITAL SIGNATURE AS IT CANNOT BE VERIFIED WITH EITHER
 BLUEBEAM OR ADOBE SOFTWARE. PLEASE CORRECT AS
 APPLICABLE. PLEASE NOTE IT APPEARS TO BE A DOCUMENT FOR
 A DIFFERENT PROJECT IN MIAMI FLORIDA
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  