Plan Review Details - Permit 22090633
Plan Review Stops For Permit 22090633
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-23 Cont ID  
Sent By pleduc Date 2022-09-23 Time   Rev Time 0.00
Received By pleduc Date 2022-09-23 Time 11:10 Sent To  
Notes
2022-09-23 11:21:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED
 CODE: 603
  
 CITY OF WEST PALM BEACH
  
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/
 DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR
 LEAKS
 & INSPECTOR DRAIN AFTER 2 HRS)
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-09-27 Time   Rev Time 0.00
Received By cdecoeur Date 2022-09-21 Time 07:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-27 Cont ID  
Sent By ccole Date 2022-09-27 Time 13:26 Rev Time 0.00
Received By ccole Date 2022-09-27 Time 13:23 Sent To  
Notes
***NONE***