Plan Review Details - Permit 22090535
Plan Review Stops For Permit 22090535
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-12 Cont ID  
Sent By cthroop Date 2023-06-12 Time 14:26 Rev Time 0.00
Received By cthroop Date 2023-06-12 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-16 Cont ID  
Sent By cthroop Date 2023-03-16 Time 15:05 Rev Time 0.00
Received By cthroop Date 2023-03-16 Time 14:55 Sent To  
Notes
2023-03-16 15:06:09NOTICE: BUILDING REVIEW APPROVAL IS PENDING THE
 APPROVAL OF THE SIGNATURE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By cthroop Date 2023-01-30 Time 17:06 Rev Time 0.00
Received By cthroop Date 2023-01-30 Time 14:39 Sent To  
Notes
2023-01-30 17:08:591ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1.PROVIDE SMOKE ALARMS.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
  
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-06-12 Cont ID  
Sent By cthroop Date 2023-06-12 Time 13:57 Rev Time 0.00
Received By cthroop Date 2023-06-12 Time 13:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-04-12 Cont ID  
Sent By rperdomo Date 2023-04-12 Time 16:34 Rev Time 0.00
Received By rperdomo Date 2023-04-12 Time 16:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By rperdomo Date 2023-03-08 Time 10:48 Rev Time 0.00
Received By rperdomo Date 2023-03-08 Time 09:42 Sent To  
Notes
2023-03-08 10:48:03FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW LOAD CALCULATION PROVIDED. NEC PART IV
 OPTIONAL FEEDER AND SERVICE LOAD CALCULATIONS 220.82
 (A)(B)(C)
  
 2. PANEL SCHEDULE PROVIDED IS NOT IN ACCORDANCE WITH
 ELECTRICAL PLAN PROVIDED. NEC 408.4(A).
  
 3. PROVIDE INFORMATION OF EXISTING SERVICE (FOR
 EXAMPLE: SERVICE CONDUCTORS AND PROTECTION). FBC
 107.3.5.3
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By rperdomo Date 2023-01-06 Time 08:24 Rev Time 0.00
Received By rperdomo Date 2023-01-06 Time 08:11 Sent To  
Notes
2023-01-06 08:24:39FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 220.
  
 2. PROVICE PANEL SCHEDULE IN ACCORDANCE WITH 408.4(A).
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-06-12 Cont ID  
Sent By cthroop Date 2023-06-12 Time 14:26 Rev Time 0.00
Received By cthroop Date 2023-06-09 Time 14:15 Sent To  
Notes
2023-06-09 14:16:2406/09/23 UPLOADED TO PROJECTDOX DRAWINGS EMAILED FROM
 RUSTEM SHAMSUTDINOV P.E. WITH NEW SIGNATURE. JG.
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-09 Cont ID  
Sent By jgomez Date 2023-06-09 Time 10:08 Rev Time 0.00
Received By jgomez Date 2023-06-09 Time 09:43 Sent To I
Notes
2023-06-09 09:49:2206/09/23 UPLOADED TO PROJECTDOX DRAWINGS EMAILED FROM
 MADINA GILFANOVA P.E. WITH NEW SIGNATURE. JG.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 11:51 Rev Time 0.00
Received By medwards Date 2023-04-11 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-16 Cont ID  
Sent By cthroop Date 2023-03-16 Time 15:06 Rev Time 0.00
Received By cthroop Date 2023-03-07 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-30 Cont ID  
Sent By cthroop Date 2023-01-30 Time 17:09 Rev Time 0.00
Received By cthroop Date 2023-01-05 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-06-12 Cont ID  
Sent By cthroop Date 2023-06-12 Time 14:05 Rev Time 0.00
Received By cthroop Date 2023-06-12 Time 13:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 11:50 Rev Time 0.00
Received By medwards Date 2023-04-14 Time 11:50 Sent To  
Notes
2023-04-14 11:50:54PLEASE ADDRESS PREVIOUS COMMENT BELOW:
  
 THE DOCUMENTS HAVE BEEN ALTERED AFTER THE DIGITAL
 SIGNATURE WAS APPLIED. PROVIDE UNALTERED DIGITALLY
 SIGNED DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By medwards Date 2023-03-08 Time 09:36 Rev Time 0.00
Received By medwards Date 2023-03-08 Time 09:36 Sent To  
Notes
2023-03-08 09:37:42THE DOCUMENTS HAVE BEEN ALTERED AFTER THE DIGITAL
 SIGNATURE WAS APPLIED. PROVIDE UNALTERED DIGITALLY
 SIGNED DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By medwards Date 2023-01-06 Time 14:53 Rev Time 0.00
Received By medwards Date 2023-01-06 Time 14:53 Sent To  
Notes
2023-01-06 14:54:29ENGINEER OF RECORD MUST DIGITALLY SIGN THE MECHANICAL
 DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-06-12 Cont ID  
Sent By ccole Date 2023-06-12 Time 12:51 Rev Time 0.00
Received By ccole Date 2023-06-12 Time 12:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-12 Cont ID  
Sent By rwbrown Date 2023-04-12 Time 09:54 Rev Time 0.00
Received By rwbrown Date 2023-04-12 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-08 Cont ID  
Sent By rwbrown Date 2023-03-08 Time 12:19 Rev Time 0.00
Received By rwbrown Date 2023-03-08 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By rwbrown Date 2023-01-06 Time 12:05 Rev Time 0.00
Received By rwbrown Date 2023-01-06 Time 12:05 Sent To  
Notes
2023-01-06 12:09:281ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE SUBMIT THE
 REQUIRED RISER DIAGRAM FOR THE NEW PLUMBING. THE FLOOR
 PLAN VIEW YOU'VE SHOWN DOES NOT INDICATE THE REQUIRED
 VENTING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-06-09 Cont ID  
Sent By jgomez Date 2023-06-09 Time 14:31 Rev Time 0.00
Received By jgomez Date 2023-06-09 Time 14:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-06-09 Cont ID  
Sent By jgomez Date 2023-06-09 Time 10:07 Rev Time 0.00
Received By jgomez Date 2023-06-09 Time 09:46 Sent To  
Notes
2023-06-09 10:08:18SIGNATURE REVIEW
  
 PREVIOUS COMMENT:
 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 RESPONSE:
 REVISED SIGNATURE NOW HAS THE REQUIRED TEXT BOX BUT
 THERE ARE TWO THINGS THAT NEED TO BE REVISED:
 A)THE TEXT BOX LANGUAGE MUST BE IDENTICAL TO THE
 SAMPLES PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-A
 ND-SEALING-ENGINEERING-DOCUMENTS/ AND REVISE AS
 REQUIRED TO MATCH.
  
 B) THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE
 DIGITAL SIGNATURE ITSELF.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE AS REQUIRED TO MATCH.
  
 NOTE:
 THESE COMMENTS WERE VERIFIED WITH THE FBPE
 INVESTIGATOR. THE TEXT BOX REQUIREMENTS APPLY.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-06-06 Cont ID  
Sent By jgomez Date 2023-06-06 Time 14:56 Rev Time 0.00
Received By jgomez Date 2023-06-06 Time 14:50 Sent To  
Notes
2023-06-06 14:57:06SIGNATURE REVIEW
  
 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- SIGNATURE SHOWS AS SIGNATURE INVALID, DOCUMENT
 ALTERED.
 THE DOCUMENT HAS BEEN UPDATED SINCE SIGNATURE.
 NEED TO SUBMIT PLANS WITH VERIFIABLE DIGITAL SIGNATURE.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 11:49 Rev Time 0.00
Received By medwards Date 2023-04-14 Time 11:49 Sent To  
Notes
2023-04-14 11:50:05PLEASE ADDRESS PREVIOUS COMMENT BELOW:
  
 THE DOCUMENTS HAVE BEEN ALTERED AFTER THE DIGITAL
 SIGNATURE WAS APPLIED. PROVIDE UNALTERED DIGITALLY
 SIGNED DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By medwards Date 2023-03-08 Time 09:38 Rev Time 0.00
Received By medwards Date 2023-03-08 Time 09:38 Sent To  
Notes
2023-03-08 09:38:31THE DOCUMENTS HAVE BEEN ALTERED AFTER THE DIGITAL
 SIGNATURE WAS APPLIED. PROVIDE UNALTERED DIGITALLY
 SIGNED DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By rwbrown Date 2023-01-30 Time 08:28 Rev Time 0.00
Received By rwbrown Date 2023-01-30 Time 08:28 Sent To  
Notes
2023-01-30 08:29:18SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  