| 2023-02-28 17:45:32 | RESIDENTIAL (R2) FITH BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22090533 |
| | 3650 WHITEHALL DR #404 |
| | |
| | 1- WINDOW MULLIONS: |
| | |
| | PREVIOUS COMMENT: |
| | DESIGN PRESSURES WERE RESUBMITTED TO REFLECT THE |
| | CORRECT BUILDING HEIGHT WHICH IS 45 FEET. BASED ON |
| | RESUBMITTED CALCULATIONS, THE SPECIFIED MULLION DOESN'T |
| | MEET THE CALCULATED DESIGN PRESSURES. THEREFORE, WINDOW |
| | MULLION SIZE NEEDS TO BE REVISED TO MEET THE ENGINEER'S |
| | DESIGN PRESSURES. |
| | NOTE: THE CORNER MULLION IS AN STRUCTURAL MULLION. THIS |
| | WAS DISCUSSED WITH ROBERT BROWN (BUILDING OFFICIAL). IF |
| | THIS MULLION IS GOING TO BE REPLACED, THEN IT NEEDS TO |
| | BE REPLACED WITH THE EXACT SAME SPECIFICATIONS. |
| | CONTRACTOR TO PROVIDE COMPLETE SPECIFICATIONS OF THE |
| | EXISTING MULLION. |
| | OTHERWISE, PROVIDE ENGINEERING FOR STRUCTURAL MULLION. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | A) ENGINEERED MULLION CALCULATIONS CALCULATED BY EMMA |
| | T. MELLINGER, P.E. FOR OPENINGS 3,4 AND 4,5 SPECIFY 1X4 |
| | X 0.125 MULLION. MULLION NOA 19-0405.10 SUBMITTED |
| | DOESN'T MEET THE CALCULATED DESIGN PRESSURES. REVISE AS |
| | REQUIRED. SEC. 1609.1 FBC-BUILDING. |
| | NOTE: THE WINDOW WIDTH (W)=W1+W2 DIVIDED BY 2. |
| | |
| | B)ENGINEERED MULLION CALCULATIONS CALCULATED BY EMMA T. |
| | MELLINGER, P.E. FOR OPENING 5,6 SPECIFY 3X3X0.125 |
| | MULLION. PROVIDE PRODUCT APPROVAL FOR THIS MULLION |
| | SIZE. SEC. 61G20.3.001 F.A.C. |
| | |
| | C)ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | PREVIOUS COMMENT: |
| | 2- WINDOW OPENING CONTROL DEVICES: WINDOW OPENING |
| | CONTROL DEVICES ARE REQUIRED WHEN THE WINDOW SILL OF AN |
| | OPERABLE WINDOW IS AT A HEIGHT LESS THAN 36 INCHES |
| | ABOVE THE FINISHED FLOOR. |
| | WINDOW OPENING CONTROL DEVICES NEED TO COMPLY WITH ASTM |
| | F2090. |
| | CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE |
| | WINDOW SILL IS LESS THAN 36" ABOVE THE FINISH FLOOR. |
| | SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. |
| | |
| | RESPONSE: |
| | THIS WILL BE VERIFIED IN THE FIELD BY THE BUILDING |
| | INSPECTOR. THIS COMMENT IS JUST TO GIVE HEADS UP ABOUT |
| | THIS REQUIREMENT. |
| | |
| | 3- FBC- B 1405.4, A FLASHING DETAIL OR SPECIFICATION IS |
| | REQUIRED. THIS COMMENT CAN BE RESOLVED BY DOING ONE OF |
| | THE FOLLOWING: |
| | |
| | REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED |
| | AND NOTE THE CODE REFERENCE - EXAMPLE "FLASHING IN |
| | ACCORDANCE WITH FBC-B 1405.4 WILL BE INSTALLED". |
| | PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS |
| | MAY INCLUDE MORE THAN ONE OPTION |
| | PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN |
| | ONE OPTION |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |