Plan Review Details - Permit 22090497
Plan Review Stops For Permit 22090497
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By rmcdouga Date 2022-11-17 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2022-11-17 Time 15:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcdouga Date 2022-10-27 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2022-10-27 Time 14:43 Sent To  
Notes
2022-10-27 15:37:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TWO TEST REPORTS FOR SOUND WERE DONE WITH
 SUSPENDED CEILINGS BELOW THE SIX INCH CONCRETE SLABS.
 THE TESTS HAVE TO REPRESENT THE CONDITIONS AT THE SITE
 WHERE THE PRODUCT IS BEING INSTALLED. SUBMIT THE
 APPROPRIATE TEST REPORTS.
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By pleduc Date 2022-10-31 Time   Rev Time 0.00
Received By pleduc Date 2022-10-31 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-09-16 Cont ID  
Sent By pleduc Date 2022-09-16 Time   Rev Time 0.00
Received By pleduc Date 2022-09-16 Time 11:28 Sent To  
Notes
2022-09-16 11:30:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED LAMINATE FLOORING.
  
 LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD AND
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE LAMINATE
 FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED
 LAMINATE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-17 Cont ID  
Sent By rmcdouga Date 2022-11-17 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2022-10-28 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-27 Cont ID  
Sent By rmcdouga Date 2022-10-27 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2022-09-15 Time 15:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET