Plan Review Details - Permit 22090333
Plan Review Stops For Permit 22090333
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-28 Cont ID  
Sent By shill Date 2022-12-28 Time 17:45 Rev Time 0.00
Received By shill Date 2022-12-28 Time 17:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-20 Cont ID  
Sent By shill Date 2022-12-20 Time 19:40 Rev Time 0.00
Received By shill Date 2022-12-20 Time 19:40 Sent To  
Notes
2022-12-20 19:41:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST, I WAS UNABLE TO LOCATE
  
 1. FBC B 1609, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA.
  
 IF THE PLAN WAS REVISED TO INCLUDE, PLEASE NOTIFY WHICH
 ON WHICH PAGE THIS CAN BE FOUND.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 15:36 Rev Time 0.00
Received By shill Date 2022-11-16 Time 15:34 Sent To  
Notes
2022-11-16 15:38:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA.
  
 2. FS471, UPLOAD DIGITALLY SIGNED PLANS. IF THE
 ENGINEER NICHOLAS A. RAMPHOS, PE DOES NOT HAVE A
 DIGITAL SIGNATURE, PLEASE HAVE HIM SEND AN EMAIL TO
 [email protected].
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By mpeterso Date 2022-12-16 Time 16:40 Rev Time 0.00
Received By mpeterso Date 2022-12-16 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By mpeterso Date 2022-10-13 Time 10:40 Rev Time 0.00
Received By mpeterso Date 2022-10-13 Time 10:40 Sent To  
Notes
2022-10-13 10:53:45ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL COMPLIANCE WITH NEC 600.6, SIGN
 DISCONNECTING MEANS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-30 Cont ID  
Sent By ajones Date 2022-12-30 Time 09:32 Rev Time 0.00
Received By ajones Date 2022-12-06 Time 06:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 15:38 Rev Time 0.00
Received By shill Date 2022-09-22 Time 07:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By shill Date 2022-12-20 Time 19:41 Rev Time 0.00
Received By shill Date 2022-12-20 Time 19:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-09-21 Cont ID  
Sent By rmcdouga Date 2022-09-21 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 17:08 Sent To  
Notes
2022-09-21 17:10:45THE PAPER PLANS DO NOT HAVE THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-30 Cont ID  
Sent By ajones Date 2022-12-30 Time 09:32 Rev Time 0.00
Received By ajones Date 2022-12-30 Time 09:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-29 Cont ID  
Sent By afowlkes Date 2022-09-29 Time 16:05 Rev Time 0.00
Received By afowlkes Date 2022-09-29 Time 16:05 Sent To  
Notes
2022-09-29 16:07:3209/29/22 FAILED
  
 NEEED TO PROVIDE HEIGHT OF THE BUILDING SO I CAN
 DETERMINE MAXIMUM ALLOWED SIGNAGE.
  
 TOTAL SIGN SIZE CALCULATED TO BE 16.91
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431