| Plan Review Stops For Permit 22090286 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-02-02 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-02-02 |
Time |
12:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-15 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-11-15 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2022-11-15 16:47:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHOW COMPLIANCE WITH FBCR 4501.17 FOR REQUIRED | | | SWIMMING POOL BARRIER. SPECIFY THE METHOD OR | | | COMBINATION OF METHODS THAT WILL BE USED. NOTE: FENCES | | | THAT ARE TO BE USED AS POOL BARRIRES ARE REQUIRED TO BE | | | LOCATED ON THE POOL OWNER'S PROPERTY AND UNDER THE | | | CONTROL OF THE POOL OWNER. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2023-01-30 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2023-01-30 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-10-06 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-10-06 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2022-10-06 10:58:00 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | 2.PROVIDE ALL PIPE AND WIRE SIZES | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-09-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-30 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-30 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2022-09-30 11:57:04 | SEPARATE PERMIT AND PLAN SUBMITTAL REQUIRED FOR GAS | | | PIPING INSTALLATION TO THE POOL HEATER. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-01-31 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-01-31 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-01-31 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-09-30 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-09-30 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-09-30 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-02-07 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-01-24 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-11-15 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-20 |
Time |
05:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-25 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-25 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-09-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-30 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-30 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2022-09-30 09:05:18 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22090286 | | | 9/30/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS 1-5: PLEASE NOTE THE PLUMBING PLANS CANNOT BE | | | APPROVED UNTIL DIGITALLY SIGNED AND SEALED PLANS ARE | | | RESUBMITTED. PLEASE SEE THE FAILED SIGNATURE REVIEW | | | COMMENT- SEC. 107.2.1 WPB. | | | | | | 2) SHEET 1 OR 2: PROVIDE THE PUMP CURVE ON THE SHEET | | | MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- | | | SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & | | | R4501.7.3 FBC RES. | | | | | | 3) SHEET 2: UPDATE THE REFERENCED STANDARDS IN THE | | | NOTES TO INCLUDE THE ANSI/APSP/ICC3; ANSI/APSP/ICC 4; | | | ANSI/APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC 7. | | | | | | 4) PLEASE NOTE THAT THE GAS HEATER SHALL BE INSTALLED | | | UNDER A SEPARATE PERMIT- SECS. 105.1, 107.2.1, | | | 107.3.5.3 WPB. | | | | | | 5) PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL BE | | | INSTALLED AT THE METER TO PROTECT THE POTABLE WATER | | | SERVICE- SECS. C, D, & E WPB CROSS CONNECTION MANUAL. | | | THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE. A PVB | | | BACKFLOW DEVICE IS ALSO REQUIRED FOR AUTOFILL | | | INSTALLATIONS- SEC. P2908.3 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-25 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-25 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2023-01-24 16:18:58 | DIGITALLY SIGNED FILES UNDER SIGNATURES FOLDER |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-09-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-30 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-30 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2022-09-30 09:06:09 | ELECTRONIC/DIGITAL SIGNATURE REVIEW FBC- 2020 | | | PERMIT- 22090286 | | | 9/30/22 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE POOL PLANS SHEETS 1-5 SHALL BE DIGITALLY SIGNED | | | AND SEALED BY THE ENGINEER OF RECORD- FL. STATUTE | | | 471.025 AND SECTION 61G15-23.005 FAC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-02-07 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-02-07 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-09-22 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-09-22 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2022-09-22 15:11:03 | 09/22/22 FAILED | | | | | | NEED TO PROVIDE THE SETBACK OF THE POOL EQUIPMENT. PER | | | CITY CODE, MECHANICAL EQUIPMENT CANNOT PROTRUDE MORE | | | THAN 4 FT INTO ANY SETBACK. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|