Plan Review Details - Permit 22090265
Plan Review Stops For Permit 22090265
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 16:09 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-31 16:08:51TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 16:07 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-31 16:07:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22090265
 ADD: 610 CLEMATIS ST. # 716
 CONT: PROJECT & PROPERTY LLC
 TEL: 561-908-1235
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 31/2022
 ACTION: DENIED
  
 1) FAIR HOUSINGACT DESIGN MANUAL
 P. 7.34 IF THERE IS ONLY ONE BATHROOM, THE BUILDER MAY
 FOLLOW THE SPECIFICATIONS A OR B. HOWEVER. WHILE NOT
 REQUIRED BY THE GUIDELINES, IT IS RECOMMENDED THAT
 SPECIFICATION B WHICH IS THE HIGHER LEVEL OF
 ACCESSIBILITY, BE USED. PLEASE SPECIFY WHICH
 SPECIFICATION IS USED FOR THIS BATHROOM,
 PAGE. 7.35
 SPECIFICATION A. IF SPECIFICATION A IS USED IT APPLIES
 TO ALL BATHROOMS, AND ALL FIXTURES IN THOSE BATHROOMS
 MUST BE USABLE.
 SPECIFICATION B. IF SPECIFICATION BIS USED, IT APPLIES
 TO ONE BATHROOM, AND ONLY ONE OF EACH TYPE OF FIXTURES
 MUST BE USABLE; ADDITIONAL BATHROOMS IN THE UNIT ARE
 EXEMPT ONLY FROM MANEUVERING AND CLEAR FLOOR SPACE
 REQUIREMENTS AT FIXTURES.
  
  
 FAIR HOUSING GUIDELINES. FAIR HOUSING ACT DESIGN AND
 CONSTRUCTION REQUIREMENTS. FOR PURPOSES OF THIS
 SECTION, A COVERED MULTIFAMILY DWELLING SHALL BE DEEMED
 TO BE DESIGNED AND CONSTRUCTED FOR FIRST OCCUPANCY ON
 OR BEFORE MARCH 13, 1991, IF THEY ARE OCCUPIED BY THAT
 DATE OR IF THE LAST BUILDING PERMIT OR RENEWAL THEREOF
 FOR THE COVERED MULTIFAMILY DWELLINGS IS ISSUED BY A
 STATE, COUNTY OR LOCAL GOVERNMENT ON OR BEFORE JANUARY
 13, 1990.
 FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER:
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER???S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
 2) THE DESIGNER OF RECORD INDICATES NEW TILE FLOOR OVER
 THE EXISTING FLOOR. PLEASE SHOW COMPLIANCE WITH FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-22 Cont ID  
Sent By pleduc Date 2022-09-22 Time   Rev Time 0.00
Received By pleduc Date 2022-09-22 Time 11:23 Sent To  
Notes
2022-09-22 12:17:15FIRE PROVISO:
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS
 ARE MAINTAINED & REPAIRED IF DAMAGED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-10-31 Time   Rev Time 0.00
Received By cdecoeur Date 2022-09-21 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-30 Cont ID  
Sent By ccole Date 2022-09-30 Time 10:30 Rev Time 0.00
Received By ccole Date 2022-09-30 Time 10:26 Sent To  
Notes
2022-09-30 10:34:011ST REVIEW FBC- 2020 PLUMBING
 PERMIT- 22090265
 9/30/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FAIR HOUSING ACT COMPLIANCE: THE CONDOMINIUMS AT 610
 CLEMATIS ST.ARE SUBJECT TO COMPLIANCE WITH FAIR HOUSING
 ACCESSIBILITY GUIDELINES WHICH CAME INTO EFFECT FOR
 MULTIFAMILY HOUSING BUILT FOR FIRST OCCUPANCY AFTER
 MARCH 13, 1991. THE BATHTUB TO SHOWER CONVERSION MUST
 BE REVIEWED IN ACCORDANCE WITH THE FHDA GUIDELINES IN
 ORDER TO VERIFY COMPLIANCE WITH THE GUIDELINES IS BEING
 MAINTAINED FOR THE CONDOMINIUM. BASED ON THE FLOOR
 PLAN, IT APPEARS BATH 2 MAY HAVE BEEN DESIGNED AS A
 SPECIFICATION B TYPE BATHROOM WHICH PROVIDES GREATER
 ACCESS TO THE SHOWER. PLEASE CONFIRM THERE IS A
 30X48-INCH CLEAR FLOOR SPACE PARALLEL TO THE SHOWER AND
 THE SHOWER HAS EXISTING GRAB BAR REINFORCEMENT. PLACE
 THE REQUIRED INFORMATION ON THE PLAN WHICH WILL EXEMPT
 THE NEW SHOWER FROM HAVING TO MEET COMPLIANCE ITEMS # 2
 & 3 BELOW.
 PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE
 GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND
 DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE
 A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 2) REFER TO PAGES 7.56- 7.59 OF THE FHDA MANUAL AND
 PROVIDE AN ENLARGED DRAWING FOR THE BATHROOM THAT SHOWS
 THE DIMENSIONS OF THE SHOWER AND THE REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAM POSITIONED
 PARALLEL TO THE SHOWER AND FLUSH WITH THE CONTROL WALL.
 IT IS ALSO REQUIRED THAT NO OTHER FIXTURES SHALL
 OBSTRUCT THE CLEAR FLOOR SPACE REQUIRED FOR THE SHOWER
 WITH THE EXCEPTION OF A LAVATORY WHICH MAY OVERLAP BY
 6-INCHES. THE LAVATORY SHALL BE A WALL HUNG WITH KNEE
 AND TOE CLEARANCES OR HAVE A REMOVABLE CABINET.
  
 3) PROVIDE AN ELEVATION DETAIL FOR THE SHOWER THAT
 SHOWS THE LOCATIONS OF REQUIRED GRAB BAR REINFORCEMENTS
 IN ACCORDANCE WITH PAGE 6.13.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-30 Cont ID  
Sent By ccole Date 2022-09-30 Time 10:30 Rev Time 0.00
Received By ccole Date 2022-09-30 Time 10:26 Sent To  
Notes
***NONE***