Plan Review Details - Permit 22090235
Plan Review Stops For Permit 22090235
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2022-11-07 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By rmcphers Date 2022-12-16 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2022-12-16 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2022-11-07 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 10:47 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By mpeterso Date 2022-10-24 Time 13:00 Rev Time 0.00
Received By mpeterso Date 2022-10-24 Time 10:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-13 Cont ID  
Sent By pleduc Date 2022-12-13 Time   Rev Time 0.00
Received By pleduc Date 2022-12-13 Time 14:04 Sent To  
Notes
2022-12-13 14:06:08FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 ANY NEW HOOD AND SUPPRESSION SYSTEMS SHALL BE SUBMITTED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-21 Cont ID  
Sent By pleduc Date 2022-09-21 Time   Rev Time 0.00
Received By pleduc Date 2022-09-20 Time 15:32 Sent To  
Notes
2022-09-20 15:32:21FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 ANY NEW HOOD AND SUPPRESSION SYSTEMS SHALL BE SUBMITTED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-10-13 Cont ID  
Sent By rwbrown Date 2022-10-13 Time 15:32 Rev Time 0.00
Received By rwbrown Date 2022-10-13 Time 15:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 10:53 Rev Time 0.00
Received By mpeterso Date 2022-12-12 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2022-09-19 Time 08:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2022-11-07 Time 15:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-12-27 Cont ID  
Sent By medwards Date 2022-12-27 Time 15:41 Rev Time 0.00
Received By medwards Date 2022-12-27 Time 15:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 13:53 Rev Time  
Received By medwards Date   Time   Sent To  
Notes
2022-10-18 13:53:411) IT APPEARS THIS IS MOSTLY A KITCHEN HOOD AND GREASE
 DUCT PROJECT BUT THIS IS NOT EXPLAINED IN A SCOPE OF
 WORK. A KITCHEN HOOD AND GREASE DUCT PERMIT IS REQUIRED
 TO HAVE A SEPARATE APPLICATION AND PLAN REVIEW. THE
 MECHANICAL SYSTEM WILL BE REVIEWED UNDER THIS PERMIT
 BUT THE KITCHEN HOOD AND GREASE DUCTS WILL NOT.
 THE PLANS SUBMITTED ARE COPIES OF THE ORIGINAL
 DRAWINGS. A COPY OF THE ORIGINAL REMOVES THE ORIGINAL
 DIGITAL SIGNATURE OF THE DESIGNER. PROVIDE THE ORIGINAL
 DIGITALLY SIGN DOCUMENTS. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-12-13 Cont ID  
Sent By rwbrown Date 2022-12-13 Time 13:59 Rev Time 0.00
Received By rwbrown Date 2022-12-13 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-10-13 Cont ID  
Sent By rwbrown Date 2022-10-13 Time 15:32 Rev Time 0.00
Received By rwbrown Date 2022-10-13 Time 15:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By rmcphers Date 2022-12-16 Time 13:55 Rev Time 0.00
Received By rmcphers Date 2022-12-16 Time 13:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 13:57 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 13:57 Sent To  
Notes
2022-10-18 13:58:10THE PLANS SUBMITTED ARE COPIES OF THE ORIGINAL
 DRAWINGS. A COPY OF THE ORIGINAL REMOVES THE ORIGINAL
 DIGITAL SIGNATURE OF THE DESIGNER. PROVIDE THE ORIGINAL
 DIGITALLY SIGN DOCUMENTS. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2023-03-21 Cont ID  
Sent By dbattles Date 2023-03-21 Time 15:31 Rev Time 0.00
Received By dbattles Date 2023-03-21 Time 15:31 Sent To  
Notes
2023-03-21 15:31:19SPECIAL INSPECTOR

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-27 Cont ID  
Sent By eschneid Date 2022-12-27 Time 17:26 Rev Time 0.25
Received By eschneid Date 2022-12-27 Time 17:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-21 Cont ID  
Sent By eschneid Date 2022-09-21 Time 15:07 Rev Time 0.25
Received By eschneid Date 2022-09-21 Time 15:07 Sent To  
Notes
2022-09-21 15:13:09FAILED
  
 RESOLUTION NO. 99-16, THE DEVELOPMENT ORDER FOR GOOD
 SAMARITAN HOSPITAL, REQUIRES THAT ALL NEW ROOF MOUNTED
 MECHANICAL EQUIPMENT BE SCREENED FROM VIEW OF THE
 PUBLIC. PLEASE DEMONSTRATED THAT THE NEW ROOFTOP
 EQUIPMNENT WILL BE SCREENED TO ITS FULL HEIGHT (PROVIDE
 THE DIMENSION OF THE EQUIPMENT AND ANY CURBS).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]