| 2022-10-24 06:24:30 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND - 107.3.5 - PLEASE PROVIDE SPEC SHEET |
| | FOR THE BACKFLOW DEVICE TO BE INSTALLED. IT NEEDS TO |
| | INDICATE IT IS LEAD FREE AND USC APPROVED. BE SURE TO |
| | HIGHLIGHT THE MAKE, MODEL, AND SIZE OF THE DEVICE. |
| | |
| | 2. 2017 WPB AMEND - 107.3.5 - PLEASE PROVIDE A BASIC |
| | SITE PLAN SHOWING THE LOCATION OF THE BACKFLOW |
| | PREVENTER |
| | |
| | 3. A CERTIFICATION SHEET IS NOT REQUIRED IN PLAN |
| | REVIEW. THE BACKFLOW IS NOT ALLOWED TO BE INSTALLED |
| | UNTIL THE PERMIT IS ISSUED UNLESS CONSIDERED AN |
| | "EMERGENCY REPAIR". IN ORDER TO QUALIFY FOR AN |
| | EMERGENCY REPAIR, YOU WOULD HAVE NEEDED TO NOTIFY |
| | DEVELOPEMENT SERVICES AT [email protected] (AND COPY ME AS A |
| | CONVENIENCE - [email protected]) |
| | AND THEN SUBMIT FOR PERMIT APPLICATION WITHIN 24 HOURS |
| | OR ONE BUSINESS DAY. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |