Plan Review Details - Permit 22090134
| Plan Review Stops For Permit 22090134 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-29 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-29 |
Time |
13:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-04 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-04 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2022-10-04 10:22:29 | ELECTRICAL REVIEW FAILED | | | 1) PLAN DOES NOT DETAIL THE SYSTEM CLASSIFICATION | | | GENERATOR IS INTENDED TO POWER. IF GENERATOR IS | | | INTENDED TO POWER EMERGENCY SYSTEMS PLEASE DETAIL | | | COMPLIANCE WITH NEC 700.3(F) , TEMPORARY SOURCE OF | | | POWER FOR MAINTENANCE. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-11-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-11-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-11-14 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-09-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-09-08 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-30 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-30 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2022-11-30 09:06:07 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22090134 | | | 11/30/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED GENERATOR SPECS DO NOT INDICATE THE | | | GENERATOR IS UL 2200 LISTED- SEC. 616.1 FBC FG. PLEASE | | | PROVIDE ADDITIONAL DOCUMENTATION TO VERIFY COMPLIANCE. | | | | | | 2) SHEET ME1: INDICATE THE BTU LOAD OF THE GENERATOR | | | AND INPUT PRESSURE IN THE NOTES OR ON THE PLAN. CLARIFY | | | IF A NEW REGULATOR AND A LISTED FLEX LINE WILL BE | | | INSTALLED AND PROVIDE THESE DETAILS- TYPE AND SIZE OF | | | EXISTING SUPPLY LINE, INPUT AND OUTPUT PRESSURES AT THE | | | REGULATOR, TYPE AND SIZE OF FLEX LINE- SECS. 402.1, | | | 410.2 & 616.2 FBC FG. | | | | | | 3) ME1: REFER TO THE MANUFACTURER'S GUIDELINES AND | | | PROVIDE EXHAUST DUCT DETAILS AS RECOMMENDED BY THE | | | MANUFACTURER- SEC. 616.1 FBC FG. INDICATE THE TYPE AND | | | GAUGE OF METAL EXHAUST DUCT AND DETAIL METHOD OF DUCT | | | ATTACHMENT AND SEALING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-30 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-13 |
Time |
17:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-04 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-09-07 |
Time |
06:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-30 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-30 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-29 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-29 |
Time |
13:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-04 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-04 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-11-18 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-11-18 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-11-18 |
Time |
17:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-09-13 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-09-13 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-09-13 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy