| Plan Review Stops For Permit 22081477 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-12-02 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-12-02 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2022-10-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-27 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-27 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2022-10-27 10:52:32 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2022-10-20 09:14:58 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE ADDRESS, PERMIT NUMBER AND ???ASBESTOS??? | | | IN THE SUBJECT LINE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-12-02 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-12-02 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-11-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-11-28 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-11-28 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-21 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-21 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-26 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-26 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2022-09-26 17:23:39 | NO ELECTRICAL WORK SHOWN JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-11-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-11-02 09:13:34 | FIRE PROVISO COMMENTS: | | | | | | (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | | | (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | | FIRE WATCH. | | | | | | (3) ALL EXITING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE | | | DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION | | | INCLUDING PAINTING. | | | | | | (4) ANY CHANGES TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS BY PROPERLY LICENSED | | | CONTRACTORS. | | | | | | (5) ANY WORK INVOLVING A FIRE RATED WALL AND/OR | | | PARTITION SHALL ENSURE THE FIRE RATING IS MAINTAINED. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-09-02 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-02 10:28:51 | FIRE PROVISO COMMENTS: | | | | | | (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | | | (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A FIRE | | | WATCH. | | | | | | (3) ALL EXISTING LIFE SAFETY SYSTEM SHALL BE PROTECTED | | | FROM DAMAGE DURING ALL PHASES OF DEMOLITION AND | | | CONSTRUCTION. | | | | | | (4) ANY CHANGES TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | (5) ANY WORK INVOLVING A FIRE RATED WALL AND/OR | | | PARTITION SHALL ENSURE THE FIRE RATING IS MAINTAINED. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-12-02 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-11-01 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-27 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-26 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-01 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-20 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-20 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-07 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-07 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-17 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-27 10:54:31 | THE SIGNATURE REVIEW SHOWS THE SIGNATURES ARE VOID | | | BECAUSE THE DOCUMENTS WERE ALTERED. IT JUST MAY BE THAT | | | THEY WERE ROTATED WHEN THEY WERE UPLOADED. THE DRAWINGS | | | MUST BE UPLOADED EXACTLY AS THEY WERE WHEN SENT OUT BY | | | THE DESIGNER. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | | DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO | | | BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF | | | THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS | | | 471 & FAC 61G15 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-20 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2022-10-20 09:06:48 | THE SIGNATURE REVIEW SHOWS THE SIGNATURES ARE VOID | | | BECAUSE THE DOCUMENTS WERE ALTERED. IT JUST MAY BE THAT | | | THEY WERE ROTATED WHEN THEY WERE UPLOADED. THE DRAWINGS | | | MUST BE UPLOADED EXACTLY AS THEY WERE WHEN SENT OUT BY | | | THE DESIGNER. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | | DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO | | | BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF | | | THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS | | | 471 & FAC 61G15 |
|
|