Plan Review Details - Permit 22081395
Plan Review Stops For Permit 22081395
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-16 Cont ID  
Sent By ppetty Date 2022-09-16 Time 10:47 Rev Time 0.00
Received By ppetty Date 2022-09-16 Time 10:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-02 Cont ID  
Sent By cwalker Date 2022-09-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-09-02 13:47:17FIRE PROVISO COMMENTS:
  
 (1) MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 5?
 OF EACH EXIT DOORWAY.
  
 MANUAL FIRE ALARM BOXES SHALL BE CONSPICUOUS AND
 UNOBSTRUCTED.
  
 NFPA 72, 17.14
  
 (2) THE FIRE ALARM SYSTEM SHALL PASS 24- HOUR BATTERY
 TESTING COMPLIANT WITH NFPA 72 14.4.3.2
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-16 Cont ID  
Sent By ppetty Date 2022-09-16 Time 10:47 Rev Time 0.00
Received By ppetty Date 2022-09-01 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 14:24 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 14:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 14:24 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 14:24 Sent To  
Notes
***NONE***