Plan Review Details - Permit 22081328
Plan Review Stops For Permit 22081328
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-17 Cont ID  
Sent By fgiaquin Date 2022-09-17 Time 19:44 Rev Time 0.00
Received By fgiaquin Date 2022-09-17 Time 17:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-31 Cont ID  
Sent By cwalker Date 2022-08-31 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-08-31 11:22:47FIRE PROVISO COMMENTS:
  
 ALL INSTALLED EQUIPMENT SHALL FUNCTION PER THE
 FOLLOWING REQUIREMENTS AND CONFIRMED AT THE TIME OF
 INSPECTION.
  
 THE FOLLOWING SECTIONS OF NFPA 101, THE LIFE SAFETY
 CODE ARE REQUIRED FOR COMPLIANCE:
  
 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS.
 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING
 SYSTEMS SHALL BE PERMITTED TO BE INSTALLED ON DOOR
 ASSEMBLIES SERVING
 LOW AND ORDINARY HAZARD CONTENTS IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC FIRE
 DETECTION
 SYSTEM IN ACCORDANCE WITH SECTION 9.6 OR AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION
 9.7, AND WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS UPON ACTUATION OF ONE OF THE FOLLOWING: (A)
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7 (B) NOT MORE THAN ONE HEAT
 DETECTOR OF AN APPROVED, SUPERVISED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH SECTION 9.6 (C) NOT
 MORE THAN TWO SMOKE DETECTORS OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION 9.6 (2) THE DOOR LEAVES SHALL
 UNLOCK IN THE DIRECTION OF EGRESS UPON LOSS OF POWER
 CONTROLLING THE LOCK OR LOCKING MECHANISM. (3)*AN
 IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN THE
 DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30 SECONDS
 WHERE APPROVED BY THE AUTHORITY HAVING JURISDICTION,
 UPON APPLICATION OF A FORCE TO THE RELEASE DEVICE
 REQUIRED IN 7.2.1.5.10 UNDER ALL OF THE FOLLOWING
 CONDITIONS: (A) THE FORCE SHALL NOT BE REQUIRED TO
 EXCEED 15 LBF (67 N). (B) THE FORCE SHALL NOT BE
 REQUIRED TO BE CONTINUOUSLY APPLIED FOR MORE THAN 3
 SECONDS. (C) THE INITIATION OF THE RELEASE PROCESS
 SHALL ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE
 DOOR OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE FORCE TO THE RELEASING DEVICE, RELOCKING SHALL
 BE BY
 MANUAL MEANS ONLY. (4)*A READILY VISIBLE, DURABLE SIGN
 IN LETTERS NOT LESS THAN 1 IN. (25 MM) HIGH AND NOT
 LESS THAN 1?8 IN. (3.2 MM) IN STROKE WIDTH ON A
 CONTRASTING BACKGROUND SHALL BE LOCATED ON THE DOOR
 LEAF ADJACENT TO THE RELEASE DEVICE IN THE DIRECTION OF
 EGRESS, AND SHALL READ AS FOLLOWS: (A) PUSH UNTIL ALARM
 SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS, FOR DOORS
 THAT SWING IN THE DIRECTION OF EGRESS TRAVEL (B) PULL
 UNTIL ALARM SOUNDS, DOOR CAN BE
 OPENED IN 15 SECONDS, FOR DOORS THAT SWING AGAINST THE
 DIRECTION OF EGRESS TRAVEL (5) THE EGRESS SIDE OF DOORS
 EQUIPPED WITH DELAYED-EGRESS LOCKS SHALL BE PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.
 7.2.1.6.1.2 THE PROVISIONS OF 7.2.1.6.2 FOR
 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES SHALL NOT
 APPLY TO DOOR ASSEMBLIES WITH
 DELAYED-EGRESS LOCKING SYSTEMS.
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET: (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF
 THE ACCESS CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF THE FOLLOWING CRITERIA: (A) THE MANUAL RELEASE
 DEVICE SHALL BE LOCATED ON THE EGRESS SIDE, 40 IN. TO
 48 IN. (1015 MM TO 1220 MM) VERTICALLY ABOVE THE FLOOR,
 AND WITHIN 60 IN.
 (1525 MM) OF THE SECURED DOOR OPENINGS. (B) THE MANUAL
 RELEASE DEVICE SHALL BE READILY ACCESSIBLE AND CLEARLY
 IDENTIFIED BY A SIGN THAT READS AS FOLLOWS: PUSH TO
 EXIT. (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE
 SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO THE
 LOCK ? INDEPENDENT OF THE LOCKING SYSTEM
 ELECTRONICS?AND THE LOCK SHALL REMAIN UNLOCKED FOR NOT
 LESS THAN 30 SECONDS. (4) ACTIVATION OF THE BUILDING
 FIRE-PROTECTIVE SIGNALING SYSTEM, IF PROVIDED, SHALL
 AUTOMATICALLY UNLOCK THE DOOR LEAVES IN THE DIRECTION
 OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN UNLOCKED
 UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN
 MANUALLY RESET. (5) THE ACTIVATION OF MANUAL FIRE ALARM
 BOXES THAT ACTIVATE THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM SPECIFIED IN 7.2.1.6.2(4) SHALL NOT BE
 REQUIRED TO UNLOCK THE DOOR LEAVES. (6) ACTIVATION OF
 THE BUILDING AUTOMATIC SPRINKLER OR FIRE DETECTION
 SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM HAS BEEN MANUALLY RESET. (7) THE
 EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS, OTHER
 THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE WITH
 SECTION 7.9
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-20 Cont ID  
Sent By shill Date 2022-09-20 Time 18:32 Rev Time 0.00
Received By shill Date 2022-08-29 Time 06:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-17 Cont ID  
Sent By fgiaquin Date 2022-09-17 Time 19:44 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***