| 2022-08-26 14:46:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATION OF AN EMERGENCY EXIT/SERVICE |
| | GATE WITH A 53FT STORAGE CONTAINER IN FRONT OF |
| | IT/BLOCKING IT FROM VIEW FROM INSIDE THE FENCED AREA. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE REVIEW, MOVE THE CONTAINER SO THE EXIT CAN BE |
| | CLEARLY SEEN FROM INSIDE THE FENCED AREA. |
| | |
| | |
| | 1A) EXITS SHALL NOT BE LOCKED NOR RESTRICTED AND SHALL |
| | BE FREE OF SPECIAL KNOWLEDGE TO EGRESS THROUGH. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF ANY PROPOSED SIDES TO |
| | EACH OF THE TENTS AND IF SO, PLEASE PROVIDE FOR THE |
| | DOORWAYS AND EXIT SIGNS OVER THOSE DOORWAYS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF ANY FLAME CERTIFICATIONS |
| | FOR THE TENT?S FABRICS. |
| | |
| | NFPA 1 CH 25 |
| | |
| | 25.2.2 FLAME PROPAGATION PERFORMANCE. |
| | 25.2.2.1 ALL TENT FABRIC SHALL MEET THE FLAME |
| | PROPAGATION PERFORMANCE CRITERIA CONTAINED IN TEST |
| | METHOD 2 OF NFPA 701, |
| | STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF |
| | TEXTILES AND |
| | FILMS. [101: 11.11.2.1 |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 4) THERE SHALL BE NO HAY/STRAW OR SHAVINGS NOR |
| | COMBUSTIBLE MATERIALS UNDER ANY TENT UNLESS PROVIDED |
| | PROOF OF THE REQUIREMENTS: |
| | |
| | NFPA 1 CH 25 |
| | |
| | 25.1.5.3 HAY, STRAW, SHAVINGS, OR SIMILAR COMBUSTIBLE |
| | MATERIALS |
| | THAT HAVE NOT BEEN TREATED TO MAKE THEM FLAME RETARDANT |
| | TO A |
| | DEGREE ACCEPTABLE TO THE AHJ SHALL NOT BE PERMITTED |
| | WITHIN |
| | ANY STRUCTURE USED AS AN ASSEMBLY OCCUPANCY. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE OR PROVIDE PROOF OF |
| | FLAME RETARDANT. |
| | |
| | 5) THERE ARE NO INDICATIONS OF NO SMOKING SIGNS. |
| | |
| | NFPA 1 CH 25 |
| | |
| | 25.1.5.2 WHERE PROHIBITED BY THE AHJ, SMOKING SHALL NOT |
| | BE PERMITTED IN ANY TEMPORARY MEMBRANE STRUCTURE. [101: |
| | 11.10.2.2] |
| | |
| | 25.2.4.2 SMOKING. |
| | 25.2.4.2.1 SMOKING SHALL NOT BE PERMITTED IN ANY TENT, |
| | UNLESS |
| | APPROVED BY THE AHJ. [101: 11.11.4.2.1] |
| | 25.2.4.2.2 IN ROOMS OR AREAS WHERE SMOKING IS |
| | PROHIBITED, |
| | PLAINLY VISIBLE SIGNS SHALL BE POSTED THAT READ AS |
| | FOLLOWS: |
| | NO SMOKING |
| | |
| | PLEASE PROVIDE |
| | |
| | 6) THERE ARE NO DIMENSION DISTANCES BETWEEN THE TENTS. |
| | |
| | 25.2.3 LOCATION AND SPACING. |
| | 25.2.3.1 THERE SHALL BE A MINIMUM OF 10 FT (3050 MM) |
| | BETWEEN STAKE LINES. [101: 11.11.3.1] |
| | |
| | 25.2.3.5 THE PLACEMENT OF TENTS RELATIVE TO OTHER |
| | STRUCTURES |
| | SHALL BE AT THE DISCRETION OF THE AHJ, WITH |
| | CONSIDERATION GIVEN |
| | TO OCCUPANCY, USE, OPENING, EXPOSURE, AND OTHER SIMILAR |
| | FAC TORS. [101: 11.11.3.5] |
| | |
| | PLEASE PROVIDE |
| | |
| | 7) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS |
| | |
| | 25.2.5 FIRE-EXTINGUISHING EQUIPMENT. PORTABLE FIRE |
| | EXTINGUISHING EQUIPMENT OF APPROVED TYPES SHALL BE |
| | FURNISHED AND MAINTAINED IN TENTS IN SUCH QUANTITY AND |
| | IN SUCH |
| | LOCATIONS AS DIRECTED BY THE AHJ. [101: 11.11.5] |
| | |
| | PLEASE PROVIDE AND MOUNT 2 - 10LB ABC EXTINGUISHERS FOR |
| | THE 40X80 & 40X60 TENTS AND 1 5LB ABC FOR EACH 20X40 |
| | |
| | 8) THERE IS AN INDICATION OF A GENERATOR |
| | |
| | 25.1.9 ELECTRICAL INSTALLATIONS. |
| | 25.1.9.1 ELECTRICAL SYSTEMS. ELECTRICAL WIRING AND |
| | EQUIPMENT |
| | SHALL BE IN ACCORDANCE WITH SECTION 11.1, UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE PER MITTED TO BE CONTINUED IN SERVICE. |
| | [101: 9.1.2] |
| | 25.1.9.2 THE ELECTRICAL SYSTEM SHALL BE INSTALLED, |
| | MAINTAINED, |
| | AND OPERATED IN A SAFE AND PROFESSIONAL MANNER. WHEN IN |
| | USE, |
| | PORTABLE ELECTRICAL SYSTEMS SHALL BE INSPECTED DAILY BY |
| | A QUALI FIED PERSON REPRESENTING THE OWNER, AND ANY |
| | DEFECTS FOUND |
| | SHALL BE CORRECTED BEFORE THE PUBLIC IS ADMITTED. |
| | 25.1.9.3 THE ELECTRICAL SYSTEM AND EQUIPMENT SHALL BE |
| | ISO LATED FROM THE PUBLIC BY PROPER ELEVATION OR |
| | GUARDING, AND ALL |
| | ELECTRICAL FUSES AND SWITCHES SHALL BE ENCLOSED IN |
| | APPROVED EN CLOSURES. CABLES ON THE GROUND IN AREAS |
| | TRAVERSED BY THE PUBLIC |
| | SHALL BE PLACED IN TRENCHES OR PROTECTED BY APPROVED |
| | COVERS. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGMENT |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |