| Plan Review Stops For Permit 22081317 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-09-02 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-09-02 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2022-09-02 16:39:55 | WORK TO BE DONE ON 304 30TH ST AND 306 30TH ST |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-09-01 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-09-01 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2022-09-01 12:13:59 | WORK IS TO BE DONE ON BOTH THE SOUTH AND NORTH | | | BUILDING, SOUTH BUILDING NEEDS TO BE GIVEN IT'S OWN | | | UNIQUE ADDRESS TO REPLACES IT'S CURRENT ADDRESS. PLEASE | | | HAVE THE OWNER CONTACT [email protected] OR CALL | | | 561-805-6659 TO DISCUS THE ADDRESSING OPTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-12-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-29 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-29 |
Time |
06:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-12-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-07 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-07 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2022-12-07 16:36:48 | 3RD BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE CABANA. | | | | | | E-MAIL A PERMIT APPLICATION FOR 306 30TH ST TO: | | | [email protected] | | | ALL PLANS SHALL REMAIN UNDER 22081317 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-08 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-08 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2022-11-08 16:47:22 | 2ND BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE CABANA. | | | | | | 1. PROVIDE THE ICC-ES REPORT FOR THE PROPOSED SPRAY | | | FOAM INSULATION. (PLAN PAGE A-4 SHOWS SPRAY FOAM | | | INSULATION) | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-10-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-08 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-07 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2022-10-08 07:48:38 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | 1. PROVIDE THE ICC-ES REPORT FOR THE PROPOSED SPRAY | | | FOAM INSULATION. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 2. PLACE THE CEILING INSULATION TYPE AND R-VALUE ON | | | PLANS: | | | MAIN DWELLING UNIT ENERGY SUBMITTAL: R-20 UNVENTED. | | | COTTAGE ENERGY SUBMITTAL: R-30 VENTED. | | | PLEASE VERIFY? | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | 2022-10-08 07:34:57 | WINDOW AND DOOR DEFERRAL: SUBMIT PRODUCT APPROVALS FOR | | | REVIEW AND APPROVAL PRIOR TO INSTALLATION. CT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-11-30 |
Time |
19:46 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-11-22 |
Time |
21:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-09-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-09-05 |
Time |
19:33 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-09-05 |
Time |
18:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-17 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-17 |
Time |
17:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-12 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2022-10-12 15:09:11 | 2ND GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | THE CURRENT DOCUMENTS WERE SUBMITTED BEFORE THE | | | PLUMBING REVIEW, AND NO NEW PAGES HAVE BEEN SUBMITTED | | | SINCE THE FAILED REVIEW. | | | | | | 1)----NO CHANGES SINCE 1ST REVIEW---- SHEETS P-1, P-2, | | | P-3: THE PLANS INDICATE THE EXISTING GARAGE AND | | | ATTACHED SEMI-FINISHED BASE AREA WILL BE REMODELED AND | | | CONVERTED INTO A DWELLING UNIT. A SEPARATE PERMIT WILL | | | REQUIRED FOR THE PROPOSED WORK- SECS. 105.1& 107.2.1 | | | WPB. | | | | | | 2) ----NO CHANGES SINCE 1ST REVIEW----P-1: THE DRAWINGS | | | ARE LABELED AS WATER/GAS HOWEVER NO GAS PIPING OR GAS | | | APPLIANCES ARE SHOWN ON THE PLANS. PLEASE PROVIDE A GAS | | | RISER DRAWING AND GAS APPLIANCE LOCATION PLAN- SEC. | | | 107.3.5.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-31 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-31 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2022-08-31 13:41:52 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 22081317 | | | 8/31/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-1, P-2, P-3: THE PLANS INDICATE THE | | | EXISTING GARAGE AND ATTACHED SEMI-FINISHED BASE AREA | | | WILL BE REMODELED AND CONVERTED INTO A DWELLING UNIT. A | | | SEPARATE PERMIT WILL REQUIRED FOR THE PROPOSED WORK- | | | SECS. 105.1& 107.2.1 WPB. | | | | | | 2) P-1: THE DRAWINGS ARE LABELED AS WATER/GAS HOWEVER | | | NO GAS PIPING OR GAS APPLIANCES ARE SHOWN ON THE PLANS. | | | PLEASE PROVIDE A GAS RISER DRAWING AND GAS APPLIANCE | | | LOCATION PLAN- SEC. 107.3.5.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-01-06 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-12-20 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-12-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-07 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-15 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-08 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-11 |
Time |
07:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-10-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-08 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-30 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-21 |
Time |
06:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-21 |
Time |
06:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-17 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-17 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2022-11-17 17:06:11 | REMOVE THE DUCTWORK IN THE GARAGE. THIS WOULD BE A | | | DIRECT PATHWAY FOR FIRE OR CARBON MONOXIDE TO TRAVEL | | | FROM THE GARAGE BACK TO THE AHU AND INTO THE LIVING | | | SPACE. THIS IS NOT ALLOWED AS IT IS A PENETRATION INOT | | | THE RATED WALL. FRC R302.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-17 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-17 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2022-10-17 17:09:23 | PLEASE ADDRESS THE 2ND REVIEW CYCLE COMMETS BELOW: | | | | | | 1) THE MECHANICAL SYSTEM DESIGN FOR THE COTTAGE MUST | | | MEET THE SEPARATION REQUIREMENTS FROM THE GARAGE. FRC | | | R302.5 | | | | | | 2) SHOW THE DUCTED RETURN BACK TO THE AHU IN THE | | | GARAGE. RETURN AIR CANNOT BE TAKEN FROM A GARAGE. FRC | | | M1602 NUMBER 4 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-01 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-01 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2022-09-01 09:52:55 | 1) THE MECHANICAL SYSTEM DESIGN FOR THE COTTAGE MUST | | | MEET THE SEPARATION REQUIREMENTS FROM THE GARAGE. FRC | | | R302.5 | | | | | | 2) SHOW THE DUCTED RETURN BACK TO THE AHU IN THE | | | GARAGE. RETURN AIR CANNOT BE TAKEN FROM A GARAGE. FRC | | | M1602 NUMBER 4 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-17 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-17 |
Time |
17:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-12 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2022-10-12 15:08:09 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | THE CURRENT DOCUMENTS WERE SUBMITTED BEFORE THE | | | PLUMBING REVIEW, AND NO NEW PAGES HAVE BEEN SUBMITTED | | | SINCE THE FAILED REVIEW. | | | | | | 1) ----NO CHANGES SINCE 1ST REVIEW---- SHEETS P-1, P-2, | | | P-3: THE PLANS INDICATE THE EXISTING GARAGE AND | | | ATTACHED SEMI-FINISHED BASE AREA WILL BE REMODELED AND | | | CONVERTED INTO A DWELLING UNIT. A SEPARATE PERMIT WILL | | | REQUIRED FOR THE PROPOSED WORK- SECS. 105.1& 107.2.1 | | | WPB. | | | | | | 2) ----NO CHANGES SINCE 1ST REVIEW---- P1, P2, & P3: | | | TWO DWELLINGS ON THE SAME LOT WILL REQUIRE WATER USERS | | | TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT | | | OF DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE | | | WILL BE REQUIRED FOR THE WATER METER PER THE CITY OF | | | WEST PALM CROSS UTILITIES DEPARTMENT AND THEIR | | | CONNECTION CONTROL PROGRAM. | | | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR | | | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE | | | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB | | | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL | | | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. | | | | | | 3) ----NO CHANGES SINCE 1ST REVIEW---- P-1: THE WATER | | | PIPE LEGEND NOTE #3 SPECIFYING A 1/2-INCH MAIN HW LINE | | | APPEARS TO BE INCORRECT AND SHOULD INDICATE 3/4-INCH | | | FOR THE WSFU DEMAND- P2903.6 & P2903.7 FBC RES. | | | | | | 5) ----NO CHANGES SINCE 1ST REVIEW---- P-1, P-2: THE | | | DRAWINGS SHOW A WATER LINE TO A BBQ SINK BUT NO DRAIN | | | AND VENT PIPING- SEC. P2601.2 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-31 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-31 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2022-08-31 12:53:32 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22081317 | | | 8/31/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-1, P-2, P-3: THE PLANS INDICATE THE | | | EXISTING GARAGE AND ATTACHED SEMI-FINISHED BASE AREA | | | WILL BE REMODELED AND CONVERTED INTO A DWELLING UNIT. A | | | SEPARATE PERMIT WILL REQUIRED FOR THE PROPOSED WORK- | | | SECS. 105.1& 107.2.1 WPB. | | | | | | 2) P1, P2, & P3: TWO DWELLINGS ON THE SAME LOT WILL | | | REQUIRE WATER USERS TO INSTALL A BACKFLOW PREVENTION | | | ASSEMBLY AT THE POINT OF DELIVERY. A REDUCED PRESSURE | | | ZONE BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER | | | METER PER THE CITY OF WEST PALM CROSS UTILITIES | | | DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM. | | | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR | | | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE | | | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB | | | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL | | | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. | | | | | | 3) P1: THE LOCATION OF THE TANKLESS WATER HEATER IN THE | | | LAUNDRY CLOSET IS NOT IN COMPLIANCE WITH SECS. P2801.4 | | | & M1305.1 FBC RES- A 30X30 INCH WORKING SPACE IS | | | REQUIRED ON THE CONTROL SIDE OF THE UNIT WITHOUT | | | REMOVAL OF THE STACKABLE WASHER/DRYER APPLIANCE. | | | | | | 4) P-1: THE WATER PIPE LEGEND NOTE #3 SPECIFYING A | | | 1/2-INCH MAIN HW LINE APPEARS TO BE INCORRECT AND | | | SHOULD INDICATE 3/4-INCH FOR THE WSFU DEMAND- P2903.6 & | | | P2903.7 FBC RES. | | | | | | 5) P-1, P-2: THE DRAWINGS SHOW A WATER LINE TO A BBQ | | | SINK BUT NO DRAIN AND VENT PIPING- SEC. P2601.2 FBC | | | RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-12-20 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-12-20 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2022-12-15 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-12-15 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-12-15 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2022-12-15 13:56:56 | PENDING REVISED COI TO BE SENT TO [email protected] | | | CC: | | | [email protected] | | | [email protected] | | | [email protected] | | | | | | F.S. 553.791 (16) | | | IN THE DESCRIPTION OF OPERATIONS PLEASE ADD LANGUAGE TO | | | STATE -THE PROFESSIONAL LIABILITY POLICY INCLUDES AN | | | EXTENDED REPORTING PERIOD ENDORSEMENT (TAIL COVERAGE) | | | FOR FIVE YEARS. ___________IS PROVIDING PROFESSIONAL | | | LIABILITY INSURANCE COVERING ALL SERVICES TO BE | | | PERFORMED AS A PRIVATE PROVIDER. - | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-10-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-08 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-08 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2022-10-08 07:31:14 | PROVISO ON PLAN PAGES A-2 AND A-3: A SEPERATE ROOFING | | | PERMIT IS REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-12-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-29 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-29 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2022-12-21 06:41:23 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-17 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-17 |
Time |
17:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-08 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-01 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-01 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2023-01-05 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2023-01-05 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-12-06 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-12-06 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-12-06 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2022-12-06 16:26:36 | 12/6/22- FAILED. SUBMIT A SEPERATE LANDSCAPE PERMIT. | | | | | | ANGELLA VANN | | | [email protected] | | | 561-822-1441 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-10-14 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-10-14 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-10-14 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2022-10-14 13:58:18 | 10/14/22 FAILED | | | | | | PREVIOUS COMMENT NOT ADDRESSED, NO LANDSCAPE PERMIT HAS | | | BEEN APPLIED FOR AT THIS MOMENT. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-09-02 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-09-02 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2022-09-02 14:24:48 | 09/02/22 FAILED -A SEPERATE DRIVEWAY PERMIT MUST BE | | | SUBMITTED. | | | | | | THE VALUE OF THE CONSTRUCTION ($245800) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($243,364) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 | | | | | | | | | | | | | | | |
|
|