Plan Review Details - Permit 22081270
Plan Review Stops For Permit 22081270
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-09-19 Cont ID  
Sent By cpuell Date 2022-09-19 Time 12:41 Rev Time 0.00
Received By cpuell Date 2022-09-19 Time 12:41 Sent To  
Notes
2022-09-19 12:41:27ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 11:15 Sent To  
Notes
2023-04-05 11:22:10DERMOLITION ONLY PERMIT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 15:20 Sent To  
Notes
2022-10-21 15:23:35PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ???ASBESTOS???
 IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 11:17 Sent To  
Notes
2023-04-05 11:25:47DEMOLITION ONLY PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-27 Cont ID  
Sent By mpeterso Date 2023-03-27 Time 10:47 Rev Time 0.00
Received By mpeterso Date 2023-03-27 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-07 Cont ID  
Sent By fgiaquin Date 2022-09-24 Time 17:56 Rev Time 0.00
Received By mpeterso Date 2022-10-07 Time 09:21 Sent To  
Notes
2022-10-07 09:22:3210.7.22 CUSTOMER EMAILED ME AN APPLICATION AND I
 UPLOADED IT TO SUPPOTING DOCS. MP
2022-09-24 17:55:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION REQUIRED FOR ELEC DEMO BY
 LICENSED ELECTRICAL CONTRACTOR. FBC 105.1
  
 PLEASE EMAIL [email protected] [email protected] OR
 [email protected] ONCE IT HAS BEEN UPLOADED TO CHANGE
 ELEC REVIEW ON THIS PERMIT FROM FAIL TO PASS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK J. GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-27 Cont ID  
Sent By pleduc Date 2023-03-27 Time   Rev Time 0.00
Received By pleduc Date 2023-03-27 Time 10:46 Sent To  
Notes
2023-03-27 10:47:12FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-16 Cont ID  
Sent By pleduc Date 2022-09-16 Time   Rev Time 0.00
Received By pleduc Date 2022-09-16 Time 11:11 Sent To  
Notes
2022-09-16 11:13:53FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2023-03-26 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2022-09-15 Time 15:45 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 15:20 Sent To  
Notes
2022-10-21 15:20:46NOT A SUBSTANTIAL IMPROVEMENT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 11:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 15:38 Sent To  
Notes
2022-10-21 16:22:58THE SIGNATURE READER STATES THAT THE DOCUMENT HAS BEEN
 ALTERED AFTER IT WAS SIGNED BY THE ARCHITECT.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15
  
  
  