Plan Review Details - Permit 22081219
| Plan Review Stops For Permit 22081219 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-09-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-09-02 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-02 12:42:48 | FIRE REVIEW COMMENTS: | | | | | | THE SUBMITTED PLAN WAS REVIEWED AND FAILED WITH THE | | | FOLLOWING: | | | | | | (1) PROVIDE THE DISTANCE BETWEEN THE HOOD AND THE | | | MANUAL ACTIVATION, PATH OF EGRESS, AND THE MOUNTING | | | HEIGHT OF THE MANUAL ACTIVATION. NFPA 96 10.5 | | | | | | (2) PROVIDE THE DISTANCE OF THE COOKING APPLIANCES IN | | | REGARDS TO PLACEMENT UNDER THE HOOD PERIMETER. NFPA 17A | | | 5.1.2 | | | | | | (3) PROVIDE THE DISTANCE OF THE NOZZLES TO THE COOKING | | | SURFACE. NFPA 17A 5.5 | | | | | | (4) PROVIDE A CLASS K PORTABLE FIRE EXTINGUISHER. NFPA | | | 96 10.2.1 | | | | | | (5) PROVIDE THE DISTANCE FROM THE COOKING SURFACE TO | | | THE PORTABLE CLASS K FIRE EXTINGUISHER LOCATION. NFPA | | | 96.10.5.1.1 | | | | | | WHEN RESUBMITTING, CORRECTIONS AND/OR ADDITIONS TO THE | | | ORIGINAL PLAN SET SHALL BE CLOUDED. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-16 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-14 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-06 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-01 |
Time |
10:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-16 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-16 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-06 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-06 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2022-09-06 14:38:28 | PROVIDE A COMPLETE DESIGN, FBC 107.3.5 | | | | | | SEE FIRE REVIEW COMMENTS BELOW. | | | | | | FIRE REVIEW COMMENTS: | | | | | | THE SUBMITTED PLAN WAS REVIEWED AND FAILED WITH THE | | | FOLLOWING: | | | | | | (1) PROVIDE THE DISTANCE BETWEEN THE HOOD AND THE | | | MANUAL ACTIVATION, PATH OF EGRESS, AND THE MOUNTING | | | HEIGHT OF THE MANUAL ACTIVATION. NFPA 96 10.5 | | | | | | (2) PROVIDE THE DISTANCE OF THE COOKING APPLIANCES IN | | | REGARDS TO PLACEMENT UNDER THE HOOD PERIMETER. NFPA 17A | | | 5.1.2 | | | | | | (3) PROVIDE THE DISTANCE OF THE NOZZLES TO THE COOKING | | | SURFACE. NFPA 17A 5.5 | | | | | | (4) PROVIDE A CLASS K PORTABLE FIRE EXTINGUISHER. NFPA | | | 96 10.2.1 | | | | | | (5) PROVIDE THE DISTANCE FROM THE COOKING SURFACE TO | | | THE PORTABLE CLASS K FIRE EXTINGUISHER LOCATION. NFPA | | | 96.10.5.1.1 | | | | | | WHEN RESUBMITTING, CORRECTIONS AND/OR ADDITIONS TO THE | | | ORIGINAL PLAN SET SHALL BE CLOUDED. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-07 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-09-07 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-16 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-16 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-06 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-06 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2022-09-06 14:41:08 | THE DESIGNER OF THE DRAWING MUST PRINT AND SIGN THEIR | | | NAME ON THE DRAWING. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
|