| 2022-08-31 14:12:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP 06 N - THERE IS AN INDICATION OF A ROOF |
| | MANIFOLD AT THE NOUTHERN END OF THE ROOF TOP THAT IS |
| | TOO FAR REMOTELY LOCATED. |
| | |
| | THAT MANIFOLD NEEDS TO BE RELOCATED TO SOME WHERE |
| | TOWARDS THE CENTER OF THE ROOF, AROUND/NEAR THE # 8 |
| | SECTION LINE ACCESSIBLE FROM THE ROOF TRAVEL PATH. |
| | |
| | FF'S WOULD HAVE DIFFICULTY ACCESSING THE MANIFOLD IN |
| | THE EVENT OF AN INCIDENT AROUND THAT AREA. |
| | |
| | PER NFPA 14 |
| | |
| | CH 1 |
| | |
| | 1.3.2 IN THOSE CASES WHERE THE AUTHORITY HAVING |
| | JURISDICTION |
| | DETERMINES THAT THE EXISTING SITUATION PRESENTS AN |
| | UNACCEPT ABLE DEGREE OF RISK, THE AUTHORITY HAVING |
| | JURISDICTION SHALL BE |
| | PERMITTED TO APPLY RETROACTIVELY ANY PORTIONS OF THIS |
| | STANDARD |
| | DEEMED APPROPRIATE. |
| | |
| | CONFER WITH THE OFFICE OF THE FIRE MARSHAL SHOULD YOU |
| | NEED TO LOCATE ACCURATELY. |
| | |
| | |
| | |
| | 2) SHEET FP 08 N - ALL FIRE LINE UNDERGROUND SHALL BE |
| | INSTALLED PER NFPA 24 UNDER SEPARATE PERMIT, SHOP |
| | DRAWINGS AND MANUFACTURE'S SPECIFICATIONS. |
| | |
| | DO NOT COVER ANY FIRE LINE JOINTS PRIOR TO FIRE |
| | INSPECTION APPROVAL. |
| | |
| | THIS PERMIT IS IN ADDITION TO AND SEPARATE FROM AN |
| | ENGINEERING PERMIT. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 2A) PLEASE ENSURE THAT THE FDC'S WILL INSTALLED WITHIN |
| | 100' OF A FDC PER NFPA 14. |
| | |
| | PROVIDE A NOTE OF ACKNOWLEDGMENT AND THE APPROX. THE |
| | DIMENSION. |
| | |
| | |
| | |
| | 3) SHEET FP 07 .N - THERE ARE INDICATIONS OF AN |
| | ELECTRIC FIRE PUMP. |
| | |
| | PLEASE CONFIRM THAT THIS ELECTRIC FIRE PUMP WILL BE |
| | CONNECTED TO AN ALTERNATE POWER SOURCE, I.E. EMERGENCY |
| | GENERATOR. IN THE EVENT OF POWER LOSS INCLUDING THE |
| | FUEL SOURCE OF THIS GENERATOR. |
| | |
| | |
| | |
| | 4) SHEET FP 1.1 N & 1.2 N - THESE SHEETS AAPPEAR TO BE |
| | IDENTICAL. BOTH INDICATE LEVEL 1 (AREA B) |
| | |
| | IS THERE AN( AREA A)? |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATION, |
| | |
| | |
| | |
| | 5) SHEET FP 05 N - THERE APPEARS TO BE INDICATIONS OF |
| | ROOF TYPE STRUCTURE OVER PARKING AREAS (POSSIBLE FLOOR |
| | DRAIN LINES), A TERRACE, A STORAGE ROOM, AND PICKLE |
| | BALL COURTS. |
| | |
| | THESE AREAS DO NOT SHOW FIRE SPRINKLER COVERAGE. |
| | |
| | PER NFPA 13 THESE AREAS REQUIRE PROTECTION UNLESS THEY |
| | MEER THE EXCEPTION REQUIREMENTS. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE A JUSTIFICATION |
| | STATEMENT AND CODE REFERENCE FOR THEIR OMITTANCE. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |