Plan Review Details - Permit 22081212
Plan Review Stops For Permit 22081212
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-09-30 Cont ID  
Sent By rmcphers Date 2022-09-30 Time 14:10 Rev Time 0.00
Received By rmcphers Date 2022-09-30 Time 13:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-11-15 Cont ID  
Sent By rmcphers Date 2022-11-15 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2022-11-15 Time 08:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2022-11-07 Time 11:08 Sent To  
Notes
2022-11-07 11:06:07ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING "006 A-601 INT. ELEVATIONS, MILLWORK DTLS. &
 DOOR SCH..PDF V4" AS LABELED IN PROJECTDOX DOES NOT
 SHOW AS DIGITALLY SIGNED -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-10-28 Cont ID  
Sent By rmcphers Date 2022-10-28 Time 11:19 Rev Time 0.00
Received By rmcphers Date 2022-10-28 Time 11:06 Sent To  
Notes
2022-10-28 11:18:55ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW TOILET GRAB BAR MAXIMUM HEIGHT TO THE
 TOP OF THE GRIPPING SURFACE ( NOT TO THE CENTER OF THE
 GRAB BAR) - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 2) THE TOILET REAR GRAB BAR IS SHOWN WITH 6 INCHES FROM
 THE SIDE WALL - SINCE THE TOILET HAS A DIMENSION RANGE
 (16 TO 18 INCHES FROM THE SIDE WALL) THE 6 INCHES SHOWN
 MAY BE INCORRECT - PLEASE REMOVE THE 6 INCHES AND SHOW
 THE TOILET REAR GRAB BAR DIMENSIONS FROM THE CENTER OF
 THE TOILET PER FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 07:53 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 07:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-30 Cont ID  
Sent By rmcphers Date 2022-09-30 Time 14:10 Rev Time 0.00
Received By rmcphers Date 2022-09-30 Time 14:10 Sent To  
Notes
2022-09-30 14:16:27SPLIT SPACE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW WALLS SURROUNDING THE MOP SINKS TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 08:49 Rev Time 0.00
Received By jleahy Date 2022-09-19 Time 08:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-29 Cont ID  
Sent By   Date 2022-08-29 Time   Rev Time 0.00
Received By bdolan Date 2022-08-29 Time 13:45 Sent To  
Notes
2022-08-29 13:46:08THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-11-15 Cont ID  
Sent By rmcphers Date 2022-11-15 Time 08:28 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 11:10 Rev Time 0.00
Received By rmcphers Date 2022-10-29 Time 07:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-28 Cont ID  
Sent By rmcphers Date 2022-10-28 Time 11:20 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2022-10-06 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-30 Cont ID  
Sent By rmcphers Date 2022-09-30 Time 14:19 Rev Time 0.00
Received By rmcphers Date 2022-08-26 Time 05:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-09-30 Cont ID  
Sent By rmcphers Date 2022-09-30 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2022-09-30 Time 14:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 06:20 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 06:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-10-21 Cont ID  
Sent By rwbrown Date 2022-10-21 Time 09:21 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-10-13 Cont ID  
Sent By rwbrown Date 2022-10-13 Time 09:02 Rev Time 0.00
Received By rwbrown Date 2022-10-13 Time 09:02 Sent To  
Notes
2022-10-13 10:30:491ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. ADDRESSED
  
 ----UNLESS YOU CAN SHOW TECHNICAL INFEASIBILITY
 (REFERENCE 202.3 OF THE FLORIDA ACCESSIBILITY CODE),
 PER 806.1 OF THE EXISTING BUILDING CODE SAYS YOU MUST
 PROVIDE ACCESSIBILITY COMPONENTS---COMMENTS 2 AND 3
 MUST BE ADDRESSED
  
 2. PER WPB FBC 107.2.1 AND FBC EX 806.1, INDICATE ON
 THE PLANS THE EXISTING ACCESSIBLE TOILET ROOMS AND
 SINKS (WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT,
 BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC
 ACC 213.2). PER FBC EX 806.1, THE FACILITY SHALL COMPLY
 WITH FBC ACC.
  
 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR EXISTING ACCESSIBLE TOILET ROOMS AND EXISTING
 ACCESSIBLE SINKS.
  
 4. ADDRESSED
  
 5. ADDRESSED
  
 6. ADDRESSED
  
 7. ADDRESSED
  
 8. ADDRESSED
  
 9. ADDRESSED
  
 10. ADDRESSED
  
 11. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, THE DEVICE SHALL BE INSTALLED AT
 THE HOT WATER SOURCE PER 613.1.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-06 Cont ID  
Sent By jesmith Date 2022-09-06 Time 11:15 Rev Time 0.00
Received By jesmith Date 2022-08-31 Time 11:48 Sent To  
Notes
2022-09-06 11:11:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22081212 2007 PALM BEACH LAKES BLVD
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, PROVIDE A FRONT AND SIDE
 ELEVATION VIEW OF THE DRINKING FOUNTAIN. COMPLY WITH
 FBC ACC 602.1, 602.2, 602.3, 602.4, 602.5, 602.7, 306.2
 AND 306.3.
  
 2. PER WPB FBC 107.2.1 AND FBC EX 806.1, INDICATE ON
 THE PLANS THE EXISTING ACCESSIBLE TOILET ROOMS AND
 SINKS (WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT,
 BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC
 ACC 212.3). PER FBC EX 806.1, THE FACILITY SHALL COMPLY
 WITH FBC ACC.
  
 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR EXISTING ACCESSIBLE TOILET ROOMS AND EXISTING
 ACCESSIBLE SINKS.
  
 4. P-0.1/STAFF LOUNGE ROOM SINK DETAIL/NOTE 5:
 ***A) WILKENS 740 BACKFLOW PREVENTER COMPLIES WITH ASSE
 1022 FOR CARBONATED BEVERAGES. PER FBC PL 608.17.1.2,
 PROVIDE A LEAD FREE BACKFLOW PREVENTER WHICH COMPLIES
 WITH ASSE 1024
 ***B) PER FBC PL 608.17.1, THE BACKFLOW PREVENTER SHALL
 BE INSTALLED IN THE DEDICATED LINE TO THE COFFEE MAKER
  
 5. P-0.1/STAFF LOUNGE ROOM SINK DETAIL: PER FBC PL
 606.2, PROVIDE SEPARATE SHUT-OFF VALVES FOR THE
 REFRIGERATOR AND THE COFFEEMAKER.
  
 6. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 7. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 8. PER WPB FBC 107.2.1, PROVIDE DETAIL OF RELOCATED
 WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , EXPANSION TANK OR THERMAL
 EXPANSION RELIEF VALVE (INCLUDING SIZE), T&P DISCHARGE
 (INCLUDING TERMINATION) AND WATER HEATER PAN AND DRAIN
 (INCLUDING TERMINATION) PER WPB FPC 107.2.1; COMPLY
 WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5,
 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 9. PER WPB FBC 107.2.1, PROVIDE DETAIL OF RELOCATED HOT
 WATER RECIRCULATING PUMP; SHOW INTEGRATION WITH WATER
 HEATER. INCLUDE ALL VALVES AND CONTROLS
  
 10. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL
 ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-11-15 Cont ID  
Sent By rmcphers Date 2022-11-15 Time 08:28 Rev Time 0.00
Received By rmcphers Date 2022-11-15 Time 08:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-11-07 Cont ID  
Sent By rmcphers Date 2022-11-07 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2022-11-07 Time 11:08 Sent To  
Notes
2022-11-07 11:10:24SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A601 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-21 Cont ID  
Sent By rwbrown Date 2022-10-21 Time 09:22 Rev Time 0.00
Received By rwbrown Date 2022-10-21 Time 09:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-19 Cont ID  
Sent By rmcphers Date 2022-10-19 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-30 Cont ID  
Sent By rmcphers Date 2022-09-30 Time 14:18 Rev Time 0.00
Received By rmcphers Date 2022-09-30 Time 14:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2022-08-31 11:50:07SIGNATURES FOR PLUMBING PLANS ARE VALID. JS