Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-12-15 Cont ID  
Sent By rwbrown Date 2022-12-15 Time 07:04 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-12-15 07:05:48CHANGED ADDRESS ON PLAN TO SHOW CORRECT ADDRESS
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-11-21 Cont ID  
Sent By rwbrown Date 2022-11-21 Time 06:16 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-21 06:20:293RD GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - YOU ARE STILL QUOTING THE
 WRONG GAS CHART. THE PIPE IS PE AND THE CHART IS FOR
 METALLIC. ALSO, IF USING THAT CHART, REGARDLESS OF
 MATERIAL, THE BTU LOAD FOR 3/4" PIPE AT 50' (151K) IS
 LOWER THAN THE BTU DEMAND (199K). PLEASE CHOOSE THE
 RIGHT CHART FOR THE MATERIAL AND PRESSURE.
  
 2. 2017 WPB AMENDS 107.2.1 - THE ADDRESS ON THE DRAWING
 IS NOT CORRECT.
  
 3. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME,
 AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS
 REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER
 1.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-10-18 Cont ID  
Sent By rwbrown Date 2022-10-18 Time 10:30 Rev Time 0.00
Received By rwbrown Date 2022-10-18 Time 10:29 Sent To  
Notes
2022-10-18 10:35:032ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE - CHANGES CREATE NEW COMMNETS - SEE #2
  
 2. 2020 FRC G2415.11.1 - IN CHANGING THE GAS LINE TO
 GALVANIZED (OR REMOVING THE NOTATION THAT IT IS PE),
 YOU APPEAR TO BE DRAWING THE GALVANIZED ON THE SAME
 PLANE AS THE METER INLET AND IT APPEARS THE GALVANIZED
 IS UNDERGROUNG. WITHOUT ANY OTHER NOTATIONS, I ASSUME
 IT IS UNDERGROUND. PLEASE CLARIFY. GALVANIZED PIPE IS
 NOT ALLOWED UNDERGROUND. YOUR DRAWING SHOULD ALWAYS
 LABEL THE MATERIALS AND PIPE PRESSURES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 09:08 Rev Time 0.00
Received By rwbrown Date 2022-08-29 Time 09:04 Sent To  
Notes
2022-08-29 09:12:581ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - YOUR PLAN SHOWS
 CONFLICTING INFORMATION. THE DRAWING STATES PE PIPE AND
 THE NOTES AND REFERENCED GAS TABLE ARE FOR METALLIC
 PIPE. PLEASE CORRECT THE DRAWING FOR ACCURACY. PLEASE
 LABEL THE PRESSURE ON THE DRAWING AS WELL AS
 REFERENCING THE TABLE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-15 Cont ID  
Sent By rwbrown Date 2022-12-15 Time 07:07 Rev Time 0.00
Received By rwbrown Date 2022-12-14 Time 07:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-21 Cont ID  
Sent By rwbrown Date 2022-11-21 Time 06:20 Rev Time 0.00
Received By rwbrown Date 2022-11-17 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-18 Cont ID  
Sent By rwbrown Date 2022-10-18 Time 10:35 Rev Time 0.00
Received By rwbrown Date 2022-10-17 Time 07:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 09:13 Rev Time 0.00
Received By rwbrown Date 2022-08-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-12-15 Cont ID  
Sent By rwbrown Date 2022-12-15 Time 07:07 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-11-21 Cont ID  
Sent By rwbrown Date 2022-11-21 Time 06:16 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-21 06:16:35PLUMBING SUB REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-10-18 Cont ID  
Sent By rwbrown Date 2022-10-18 Time 10:26 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-18 10:27:572ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THIS COMMENT WAS NOT ADDRESSED. IS THE WATER HEATER
 A REPLACEMENT (LIKE FOR LIKE)? OR IS IT AN UPGRADE? IS
 IT IN THE SAME PLACE AS THE OLD ONE? OR IN A NEW
 LOCATION??
 2017 WPB AMENDS 107.2.1 - UNABLE TO DETERMINE IF THIS
 IS INSTALLING A TANKLESS IN THE SAME LOCATION AS AN
 EXISTING OR RELOCATING THE WATER HEATER LOCATION TO A
 NEW LOCATION. PLEASE PROVIDE A NOTE ON THE PLAN AS TO
 "EXISTING WATER HEATER LOCATION" OR SHOW A FLOOR PLAN
 WITH "OLD HEATER LOCATION" AND "NEW HEATER LOCATION".
  
 NOTE: IF MOVING THE WATER HEATER TO A NEW LOCATION, A
 PLUMBING SUB WILL BE REQUIRED IN ORDER TO GENERATE THE
 PLUMBING INSPECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 09:05 Rev Time 0.00
Received By rwbrown Date 2022-08-29 Time 09:04 Sent To  
Notes
2022-08-29 09:08:021ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - UNABLE TO DETERMINE IF
 THIS IS INSTALLING A TANKLESS IN THE SAME LOCATION AS
 AN EXISTING OR RELOCATING THE WATER HEATER LOCATION TO
 A NEW LOCATION. PLEASE PROVIDE A NOTE ON THE PLAN AS TO
 "EXISTING WATER HEATER LOCATION" OR SHOW A FLOOR PLAN
 WITH "OLD HEATER LOCATION" AND "NEW HEATER LOCATION".
  
 NOTE: IF MOVING THE WATER HEATER TO A NEW LOCATION, A
 PLUMBING SUB WILL BE REQUIRED IN ORDER TO GENERATE THE
 PLUMBING INSPECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 09:13 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved