Plan Review Details - Permit 22081153
Plan Review Stops For Permit 22081153
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-06 Cont ID  
Sent By rmcdouga Date 2023-07-06 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2023-07-06 Time 13:57 Sent To  
Notes
2023-07-06 13:57:22FINAL ELEVATION CERTIFICATE
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT RESOLVED. REMOVE THE 1792 AND ENTER 2800 IN THE
 SPACE. REMOVE THE NOTE ABOUT THE 2800 SQFT. THIS IS
 EXPLAINED IN THE COMMENT SECTION OF SECTION D.] FOR
 ITEM A8 C) ENTER THE TOTAL COVERAGE AREA OR RATED AREA
 OF THE ENGINEERED OPENINGS WHICH IS EQUIVALENT TO THE
 PERFORMACE THAT WOULD BE PROVIDED BY THAT NUMBER OF
 SQUARE INCHES OF NON-ENGINEERED OPENINGS. THE FLOOD
 VENT DETAIL ON THE ARCHITECTURAL PLANS SPECIFY (14)
 SMART VENTS MODEL NUMBER 1540-520, WHICH HAVE A
 CAPACITY OF 200 SQFT PER VENT. THE TOTAL WILL BE 14 X
 200 = 2800. THE CRAWL SPACE AREA IS 2771 SQFT. FEMA
 TECHNICAL BULLETIN #1 SECTION 9.3.5
  
 2) RESOLVED.
  
 6) RESOLVED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-08 Cont ID  
Sent By rmcdouga Date 2023-06-08 Time 14:42 Rev Time 0.00
Received By rmcdouga Date 2023-06-07 Time 14:26 Sent To  
Notes
2023-06-07 14:26:12FINAL ELEVATION CERTIFICATE
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FOR ITEM A8 C) ENTER THE TOTAL COVERAGE AREA OR
 RATED AREA OF THE ENGINEERED OPENINGS WHICH IS
 EQUIVALENT TO THE PERFORMACE THAT WOULD BE PROVIDED BY
 THAT NUMBER OF SQUARE INCHES OF NON-ENGINEERED
 OPENINGS. THE FLOOD VENT DETAIL ON THE ARCHITECTURAL
 PLANS SPECIFY (14) SMART VENTS MODEL NUMBER 1540-520,
 WHICH HAVE A CAPACITY OF 200 SQFT PER VENT. THE TOTAL
 WILL BE 14 X 200 = 2800. THE CRAWL SPACE AREA IS 2771
 SQFT. FEMA TECHNICAL BULLETIN #1 SECTION 9.3.5
  
 2) THE PHOTOS THAT WERE SUBMITTED ONLY SHOW FLOOD VENTS
 ON ONE WALL. PROVIDE PHOTOS THAT SHOW THE FLOOD VENTS
 ON AT LEAST TWO OF THE ELEVATIONS.
  
 6) THE PHOTOS NEED TO STATE "RIGHT SIDE VIEW" AND "LEFT
 SIDE VIEW" PER INSTRUCTIONS. NOT SOUTH SIDE OR WEST
 SIDE. FEMA ELEVATION CERTIFICATE INSTRUCTIONS
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-25 Cont ID  
Sent By dbattles Date 2022-08-25 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2022-08-25 Time 09:31 Sent To  
Notes
2022-08-25 11:16:14 
 FINAL ELEVATION CERTIFICATE
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NUMBER OF PERMANENT FLOOD OPENINGS LISTED FOR
 ITEM A8(A) IS (9). ITEM A8(D) SPECIFIES THE VENTS AS
 BEING ENGINEERED. THE FLOOD VENT DETAIL ON THE
 ARCHITECTURAL PLANS SPECIFY (14) SMART VENTS MODEL
 NUMBER 1540-520, WHICH HAVE A CAPACITY OF 200 SQFT PER
 VENT. THE CRAWL SPACE AREA IS 2771 SQFT. NINE (9) OF
 THESE VENTS ARE ONLY GOOD FOR 9 X 200 = 1800 SQFT.
 ADDITIONAL VENTS ARE REQUIRED. FBC-R322.2.2
  
 2) SINCE THIS BUILDING HAS NO ATTACHED GARAGE THE BOXES
 FOR A9 (D) SHOULD NOT BE MARKED.
  
 3) SPECIFY THE ENGINEERED FLOOD VENTS THAT WERE USED IN
 THE COMMENTS.
  
 4) PROVIDE PHOTOS THAT SHOW THE FLOOD VENTS ON AT LEAST
 TWO OF THE ELEVATIONS.
  
 5) THE PHOTOS NEED TO BE DATED.
  
 6) THE PHOTOS NEED TO STATE ?FRONT VIEW? ?REAR VIEW?
 ??RIGHT SIDE VIEW? ?LEFT SIDE VIEW? PER INSTRUCTIONS.
  
 7) SECTION ?D? THE BOX ?CHECK HERE IF ATTACHMENTS?
 SHOULD BE CHECKED (FOR THE FLOOD VENT ENGINEERING) ?
 SEE FEMA ELEVATION INSTRUCTIONS ?ITEMS A8B-D?
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-14 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-06 Cont ID  
Sent By rmcdouga Date 2023-07-06 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2023-06-23 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-08 Cont ID  
Sent By rmcdouga Date 2023-06-08 Time 14:42 Rev Time 0.00
Received By rmcdouga Date 2023-06-01 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-25 Cont ID  
Sent By rmcdouga Date 2022-08-25 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2022-08-24 Time 10:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By rmcdouga Date 2023-07-06 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2023-07-06 Time 13:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-07 Cont ID  
Sent By rmcdouga Date 2023-06-07 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2023-06-07 Time 14:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-25 Cont ID  
Sent By rmcdouga Date 2022-08-25 Time 09:31 Rev Time 0.00
Received By rmcdouga Date 2022-08-25 Time 09:31 Sent To  
Notes
2022-08-25 09:33:30SIGNATURES AND SEALS ON THE PAPER FINAL E.C. AND SURVEY
 ARE GOOD.