| Plan Review Stops For Permit 22081062 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-17 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-17 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-26 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-25 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2022-10-26 13:46:12 | 2ND BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR GLASS UNIT MASONRY. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-15 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-13 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-09-15 13:50:23 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | 1. PROVIDE AN EXISTING FLOOR PLAN. INCLUDE ENTIRE | | | STRUCTURES FOOTPRINT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE A PROPOSED FLOOR PLAN. INCLUDE ENTIRE | | | STRUCTURES FOOTPRINT. INCLUDE DEMENSIONS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-16 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-16 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-14 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-14 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-09-08 |
Time |
14:33 |
Rev Time |
|
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-08 14:37:39 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE CLARITY AS TO THE ELECTRICAL WORK | | | SCOPE. PLEASE SHOW EXISTING ELECTRICAL CONDITIONS ON A | | | FLOOR PLAN. PLEASE PROVIDE PROPOSED ADDITIONAL, | | | MODIFIED OR REMOVED ELECTRICAL WORK ON A SEPARATE PLAN. | | | PLEASE PROVIDE AN ELECTRICAL PROPOSED WORK NARRATIVE. | | | FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-11-22 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-22 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-11-21 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-17 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-02 |
Time |
06:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-26 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-05 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-15 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-24 |
Time |
05:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-11-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-11 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-11 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-06 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-06 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2022-10-06 08:07:13 | PLEASE ADDRESS 1ST REVIEW CYCLE COMMENTS BELOW: | | | | | | PROVIDE A MECHANICAL DRAWING SHOWING THE MECHANCAL WORK | | | BEING COMPLETED FOR THIS PROJECT INCLUDING THE BATH | | | EXHAUST FANS AND ANY DUCTWORK THAT MAY BE MOVED. FBC | | | 107.3.5 | | | | | | ALL DRAWINGS SUBMITTED MUST HAVE THE DESIGNERS NAME AND | | | SIGNATURE. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-25 |
Time |
11:14 |
Rev Time |
|
| Received By |
medwards |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-25 11:13:21 | PROVIDE A MECHANICAL DRAWING SHOWING THE MECHANCAL WORK | | | BEING COMPLETED FOR THIS PROJECT INCLUDING THE BATH | | | EXHAUST FANS AND ANY DUCTWORK THAT MAY BE MOVED. FBC | | | 107.3.5 | | | | | | ALL DRAWINGS SUBMITTED MUST HAVE THE DESIGNERS NAME AND | | | SIGNATURE. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-11-22 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-22 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-03 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-11-03 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2022-11-03 15:53:56 | 3RD PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC 912.1 - YOU HAVE DRAWN ALL 3 TRAPS ON THE | | | HIGH SIDE OF THE VENTED FIXTURE CONNECTION. ONLY ONE | | | TRAP IS ALLOWED ON THE HIGH SIDE OF THE VENTED FIXTURE | | | CONNECTION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-06 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-06 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2022-10-06 07:56:15 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - THE DRAWING YOU'VE | | | SUBMITTED IS NOT A RISER DIAGRAM. PLEASE SUBMIT A RISER | | | DIAGRAM IN ISOMETRIC FORM AND SHOW THE LEGAL | | | CONNECTIONS ACCORDING TO THE CODE. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO | | | DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, | | | AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS | | | REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER | | | 1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-24 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-24 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2022-08-24 07:37:50 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE SUBMIT THE | | | REQUIRED PLUMBING RISER FOR THE NEW BATHROOM. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO | | | DESIGNED THE DRAWING SIGN THEM AS REQUIRED BY THE WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
N |
Date |
2022-11-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-11 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-11 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-06 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-06 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2022-10-06 08:09:11 | PLEASE ADDRESS 1ST EVIEW CYCLE COMMENTS BELOW: | | | | | | 1ST SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-15 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-13 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-09-15 13:47:06 | 1ST SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|
|