Plan Review Details - Permit 22081027
Plan Review Stops For Permit 22081027
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-11-21 Cont ID  
Sent By dbattles Date 2022-11-21 Time 10:35 Rev Time 0.00
Received By dbattles Date 2022-11-21 Time 10:35 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcphers Date 2022-10-27 Time 15:48 Rev Time 0.00
Received By rmcphers Date 2022-10-27 Time 14:55 Sent To  
Notes
2022-10-27 15:48:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-18 Cont ID  
Sent By rmcphers Date 2023-01-18 Time 10:56 Rev Time 0.00
Received By rmcphers Date 2023-01-18 Time 10:56 Sent To  
Notes
2023-01-18 11:31:33 
  
 CORRECTIONS NEEDED -
  
 1) ALL SIGNED AND SEALED DRAWINGS EXCEPT FOR S001 DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 15:07 Sent To  
Notes
2022-12-09 15:10:51TARGET REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING AD110 SHOWS THE REMOVAL OF 2 EXIT DOORS FOR
 EXIT NUMBER 4 - DRAWING A020 SHOWS THE DOORS REPLACED
 WITH A WALL - DRAWING A021 SAYS THAT THE EXIT CONSIST
 OF 1 - 8' EXIT AND 1 - 3' EXIT PLEASE RE EVALUATE THE
 MEANS OF EGRESS - FBC 1005.4 CONTINUITY.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF
 EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT
 BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL
 ARRIVAL AT THE PUBLIC WAY.
  
 2) DRAWING ACC2 - ALL ACCESSIBLE PARKING SPACES NEED TO
 BE 12' WIDE - FBC 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET (3658 MM)
 WIDE,
  
 3) PLEASE PROVIDE A NOTE ON THE DRAWINGS AS TO THE WALL
 FINISH AND CEILING FINISH FIRE CLASSIFICATIONS PER FBC
 803.1
  
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE BUILDING DESIGNER OF RECORD FBC WPB 107.3.4
  
 5) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-27 Cont ID  
Sent By rmcphers Date 2022-10-27 Time 16:22 Rev Time 0.00
Received By rmcphers Date 2022-10-27 Time 14:55 Sent To  
Notes
2022-10-27 16:22:05TARGET REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S001 AND THE STRUCTURAL CALCULATIONS
 PROVIDED SHOW A WIND SPEED OF 168MPH USED FOR THE WIND
 DESIGN - WIND SPEED FOR A RISK CATEGORY II SHOULD BE
 170MPH PER FBC WPB SECTION 120.
  
 2) DRAWING AD110 SHOWS THE REMOVAL OF 2 EXIT DOORS FOR
 EXIT NUMBER 4 - DRAWING A020 SHOWS THE DOORS REPLACED
 WITH A WALL - DRAWING A021 SAYS THAT THE EXIT CONSIST
 OF 1 - 8' EXIT AND 1 - 3' EXIT PLEASE RE EVALUATE THE
 MEANS OF EGRESS - FBC 1005.4 CONTINUITY.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF
 EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT
 BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL
 ARRIVAL AT THE PUBLIC WAY.
  
 3) DRAWING ACC2 SHOWS THE ACCESSIBLE PARKING SPACE
 WIDTH AT 11' - SHOULD BE 12' PER FBC 502.2 VEHICLE
 SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET (3658 MM)
 WIDE,
  
 4) PLEASE PROVIDE A NOTE ON THE DRAWINGS AS TO THE WALL
 FINISH AND CEILING FINISH FIRE CLASSIFICATIONS PER FBC
 803.1
  
 5) PLEASE SHOW THE REQUIREMENT FOR TERMITE TREATMENT
 FOR THE DISTURBED SOILS PER FBC 1816.1.2
  
 6) STRUCTURAL DRAWINGS SAY TO SEE THE ARCHITECTURAL
 DRAWINGS FOR THE EXTERIOR WALL FINISHES/CLADDING ETC. -
 I DO NOT SEE ANY EXTERIOR WALL DETAILS ON THE
 ARCHITECTURAL DRAWINGS - FBC 1403
  
 7) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE BUILDING DESIGNER OF RECORD FBC WPB 107.3.4
  
 8) ACCESSIBLE RESTROOM - WHEN REFERRING TO THE MIRROR
 OVER THE SINK DIMENSIONS FROM THE FLOOR PLEASE USE THE
 WORD "REFLECTIVE SURFACE" FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 9) PLEASE PROVIDE A STATEMENT ON THE DRAWING THAT THE
 STORAGE RACKS COMPLY WITH RMI/ANSI MH 16.1 - FBC 2209.1
 STORAGE RACKS.
 THE DESIGN, TESTING AND UTILIZATION OF STORAGE RACKS
 MADE OF COLD-FORMED OR HOT-ROLLED STEEL STRUCTURAL
 MEMBERS SHALL BE IN ACCORDANCE WITH RMI/ANSI MH 16.1.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By fgiaquin Date 2022-10-17 Time 21:38 Rev Time 0.00
Received By fgiaquin Date 2022-10-13 Time 19:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-08 Cont ID  
Sent By parking Date 2022-12-08 Time   Rev Time 0.00
Received By bdolan Date 2022-12-08 Time 11:15 Sent To  
Notes
2022-12-08 11:16:02THE FOLLOWING COMMENTS WERE SUBMITTED BY CAPT.BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 CAPT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By   Date 2022-10-06 Time   Rev Time  
Received By bdolan Date 2022-09-19 Time 12:18 Sent To  
Notes
2022-10-06 10:11:49THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-20 Cont ID  
Sent By medwards Date 2023-01-20 Time 13:32 Rev Time 0.00
Received By medwards Date 2023-01-11 Time 06:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-16 Cont ID  
Sent By medwards Date 2022-12-16 Time 14:00 Rev Time 0.00
Received By medwards Date 2022-11-29 Time 17:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-17 Cont ID  
Sent By aoliver Date 2022-11-17 Time 15:03 Rev Time 0.00
Received By aoliver Date 2022-09-13 Time 09:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-09-22 Cont ID  
Sent By dbattles Date 2022-09-22 Time 09:03 Rev Time 0.00
Received By dbattles Date 2022-09-22 Time 09:03 Sent To  
Notes
2022-09-22 09:03:51INTERIOR REMODEL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-20 Cont ID  
Sent By medwards Date 2023-01-20 Time 13:30 Rev Time 0.00
Received By medwards Date 2023-01-20 Time 13:30 Sent To  
Notes
2023-01-20 13:31:26THE OUTDOOR AIR CALCULATIONS FOR THE RTU-5 ARE
 APPROVED, BUT THE DRAWING MUST BEAR THE ENGINEERS
 ELECTRONIC THIRD PARTY VERIFIED DIGITAL SIGNATURE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-16 Cont ID  
Sent By medwards Date 2022-12-16 Time 14:00 Rev Time 0.00
Received By medwards Date 2022-12-16 Time 14:00 Sent To  
Notes
2022-12-16 14:00:302ND REVIEW FMC
 PERMIT: 22081027
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE RESPOND TO 1ST CYCLE COMMENT 5 BELOW:
 5)SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS
 EXHAUST SYSTEM. FMC TABLE 403.3.1.1
  
 2) SHEET M601: VENTILATION SCHEDULE- RTU-5 ??? PLEASE
 PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE RTU-5
 BASED ON THE OCCUPANCY CLASSIFICATION AND OCCUPANCY
 DENSITY FROM TABLE 403.3.1.1. SOME OF THE OCCUPANT
 COUNTS APPEAR TO BE LOW IN THE VENTILATION SCHEDULE
 BASED ON TABLE 403.3.1.1, WHICH MAKES THE REQUIRED
 OUTDOOR AIR FOR THAT AREA TO BE LOW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-13 Cont ID  
Sent By medwards Date 2022-10-13 Time 11:04 Rev Time 0.00
Received By medwards Date 2022-10-13 Time 11:04 Sent To  
Notes
2022-10-13 11:04:181ST REVIEW FMC
 PERMIT: 22081027
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS AND THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON THE
 2020 FLORIDA ENERGY CODE.
  
 2) PLEASE ADD A NOTE ON THE REFRIGERATION DRAWINGS
 STATING THAT ALL REFRIGERATION WILL REQUIRE A SEPARATE
 PERMIT APPLICATION, SUBMITTAL AND REVIEW AS IT WILL NOT
 BE REVIEWED UNDER THIS PERMIT APPLICATION. THEY WILL
 ALSO BE REQUIRED TO MEET- FEC C403.2.14 REFRIGERATION
 EQUIPMENT PERFORMANCE.
 REFRIGERATION EQUIPMENT PERFORMANCE SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTIONS C403.2.14.1 AND C403.2.14.2
 FOR COMMERCIAL REFRIGERATORS, FREEZERS,
 REFRIGERATOR-FREEZERS, WALK-IN COOLERS, WALK-IN
 FREEZERS AND REFRIGERATION EQUIPMENT. THE ENERGY USE
 SHALL BE VERIFIED THROUGH CERTIFICATION UNDER AN
 APPROVED CERTIFICATION PROGRAM OR, WHERE
 A CERTIFICATION PROGRAM DOES NOT EXIST, THE ENERGY USE
 SHALL BE SUPPORTED BY DATA FURNISHED BY THE EQUIPMENT
 MANUFACTURER.
 EXCEPTION:
 WALK-IN COOLERS AND WALK-IN FREEZERS REGULATED UNDER
 FEDERAL LAW IN ACCORDANCE WITH SUBPART R OF 10 CFR 431.
  
 3) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR
 ALL NEW MECHANICAL UNITS. FEC C403.2.1
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE FOR THIS PROJECT. PLEASE USE THE OCCUPANCY
 CLASSIFICATIONS LISTED IN TABLE 403.3.1.1 WHEN NAMING
 EACH SPACE. FMC 403.3.1.1
  
 5) SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS
 EXHAUST SYSTEM. FMC TABLE 403.3.1.1
  
  
 6) SHEET M311: THERE ARE 3 CU???S SHOWN ON THE DRAWING
 FOR AC-3, AC-4 AND AC-5. ARE THESE NEW CU???S GOING TO
 BE MOUNTED ON THE ROOF? IF SO PLEASE SHOW THE ANCHORAGE
 DETAILS. FBC 107.3.5
  
 7) PLEASE SHOW A MECHANICAL ROOF DRAWING SHOWING THE
 EXISTING AND NEW SYSTEMS AND THE DISTANCE FROM THE
 ROOFS EDGE. FMC 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-01-12 Cont ID  
Sent By rwbrown Date 2023-01-12 Time 12:50 Rev Time 0.00
Received By rwbrown Date 2023-01-12 Time 12:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-12-09 Cont ID  
Sent By rwbrown Date 2022-12-09 Time 06:59 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-12-09 06:59:332ND PLUMBING REVIEW
 RESPONSE LETTER FROM 1ST REVIEW NOT RECEIVED AND
 CORRECTIONS ARE NOT CLEAR. THE RE-REVIEW WAS NOT
 COMPLETED AT THIS TIME BECAUSE A RESPONSE LETTER AND/OR
 THE CORRECTIONS ARE NOT CLEAR. MAYBE A PHONE CALL OR
 EMAIL WOULD BE HELPFUL.
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. CORRECTIONS NOT CLEAR - TYPICALLY THERE IS A FLOOR
 PLAN OF THE FIXTURES WITH THE DRAINS IN THE SAME FLOOR
 PLAN. IT IS VIRTUALLY IMPOSSIBLE TO DECIPHER WHICH
 FIXTURES ARE DRAINING INTO WHICH RECEPTACLE.
 2017 WPB AMENDS 107.2.1 - THE DRAIN ISOMETRICS DO NOT
 CLEARLY INDICATE WHICH FIXTURES DISCHARGE TO WHICH
 DRAINS. PLEASE SHOW A FLOOR PLAN FOR THE DRAINS THAT
 CLEARLY SHOW THE LOCATION OF EACH FIXTURE'S DISCHARGE
 TO CLARIFY WHICH ONES ARE INTO THE SANITARY AND WHICH
 ARE INTO THE GREASE WASTE. SEE COMMENT #2
  
 2. IT APPEARS THIS COMMENT WAS NOT FULLY ADDRESSED, BUT
 CANNOT BE VERIFIED UNTIL COMMENT #1 IS ADDRESSED. IS
 THE EYE WASH STILL GOING INTO THE GREASE WASTE?
 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK,
 DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES
 THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE
 GOING TO THE SANITARY AND NOT TO THE GREASE WASTE.
 PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF
 GREASE WASTE AND SANITARY WASTE. CURRENLY, AT THE VERY
 LEAST, THE HAND SINK IS GOING TO THE GREASE WASTE AND
 SHOULD NOT.
  
 3. 2017 WPB AMENDS 107.2.1 - IT APPEARS THAT ALL THE
 DRAINS ARE LABELED AS FLOOR DRAINS. INDIRECT WASTES
 SHOULD DISCHARGE TO FLOOR SINKS OR HUB DRAINS AND FLOOR
 DRAINS RECEIVE FLOOR DRAINAGE. PLEASE CORRECTLY LABEL
 AND DETAIL THE FLOOR SINKS AND FLOOR DRAINS.
  
 4. NOT ADDRESSED. THE ISOMETRIC AND THE PIPING DIAGRAM
 7-P501 DOES NOT SHOW A THERMOSTATIC MIXING DEVICE AT
 THE WATER HEATER
 HOT WATER 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS
 - THE THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE
 THE LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE
 PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE
 OF HOT WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, SHALL BE INSTALLED AT THE HOT WATER
 SOURCE PER 613.1.
  
 5. NOT ADDRESSED. A DETAIL SHOWING MIXING VALVES AT THE
 PUBLIC HANDWASHING SINKS NOT SHOWN.
 TEMPERED WATER/PUBLIC HAND WASHING 2020 FPC
 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR THE LIMITING
 DEVICE REQUIRED FOR PUBLIC HANDWASHING FACILITIES AND
 TEMPERED WATER. THE DEVICE SHOULD CONFORM TO ASSE 1070.
  
 6. 16-P501 STILL DOES NOT DETAIL THE REQUIRED OIL ALARM
 FOR THE ELEVATOR SUMP.
 2020 FPC 1003.4 - PLEASE DETAIL THE OIL ALARM FOR THE
 ELEVATOR SUMPS OR SHOW THE OIL SEPARATOR THAT WOULD BE
 REQUIRED IN IT'S ABSENCE.
  
 7. -------THE ELEVATOR SUMP PUMP DISCHARGE CANNOT GO TO
 THE STORM.
 WPB ORD. SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
  (C) ILLICIT CONNECTIONS. NO PERSON MAY MAINTAIN, USE
 OR ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE
 STORM WATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN
 VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS
 RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE
 PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR
 OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS
 OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE
 CONNECTION WAS MADE.
  
  
 8. -------THE DISCHARGE FROM AIR HANDLERS/AIR
 CONDITIONING CONDENSATE CANNOT DISCHARGE INTO THE
 SANITARY. IT MUST GO TO THE STORM OR OTHER APPROVED
 PLACE OF DISPOSAL.
 WPB ORD. SEC. 90 - 126 - PROHIBITIONS AND LIMITATIONS
 OF DISCHARGE.
  A) GENERALLY. USERS SHALL NOT DISCHARGE POLLUTANTS
 INTO THE WWF UNLESS IN ACCORDANCE WITH THIS ARTICLE.
  (B) DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE
 INTO THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE
 PASS THROUGH OR INTERFERE WITH THE OPERATION OR
 PERFORMANCE OF THE WWF. NO USER SHALL DISCHARGE INTO
 THE WWF OR ANY CONNECTED SYSTEM ANY WASTE OR WASTEWATER
 CONTAINING ANY OF THE FOLLOWING:
  (5) STORM WATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By rwbrown Date 2022-10-06 Time 13:15 Rev Time 0.00
Received By rwbrown Date 2022-10-06 Time 12:27 Sent To  
Notes
2022-10-06 13:22:171ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - THE DRAIN ISOMETRICS DO
 NOT CLEARLY INDICATE WHICH FIXTURES DISCHARGE TO WHICH
 DRAINS. PLEASE SHOW A FLOOR PLAN FOR THE DRAINS THAT
 CLEARLY SHOW THE LOCATION OF EACH FIXTURE'S DISCHARGE
 TO CLARIFY WHICH ONES ARE INTO THE SANITARY AND WHICH
 ARE INTO THE GREASE WASTE. SEE COMMENT #2
  
 2. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK,
 DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES
 THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE
 GOING TO THE SANITARY AND NOT TO THE GREASE WASTE.
 PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF
 GREASE WASTE AND SANITARY WASTE. CURRENLY, AT THE VERY
 LEAST, THE HAND SINK IS GOING TO THE GREASE WASTE AND
 SHOULD NOT.
  
 3. 2017 WPB AMENDS 107.2.1 - IT APPEARS THAT ALL THE
 DRAINS ARE LABELED AS FLOOR DRAINS. INDIRECT WASTES
 SHOULD DISCHARGE TO FLOOR SINKS OR HUB DRAINS AND FLOOR
 DRAINS RECEIVE FLOOR DRAINAGE. PLEASE CORRECTLY LABEL
 AND DETAIL THE FLOOR SINKS AND FLOOR DRAINS.
  
 4. HOT WATER 2020 FPC - 607.1.1 TEMPERATURE LIMITING
 MEANS - THE THERMOSTAT CONTROL ON THE WATER HEATER
 CANNOT BE THE LIMITING DEVICE FOR HOT WATER DELIVERY.
 PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE
 PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN
 ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR
 PUBLIC HANDWASHING 607.1.2/419.5. AND, SHALL BE
 INSTALLED AT THE HOT WATER SOURCE PER 613.1.
  
 5. TEMPERED WATER/PUBLIC HAND WASHING 2020 FPC
 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR THE LIMITING
 DEVICE REQUIRED FOR PUBLIC HANDWASHING FACILITIES AND
 TEMPERED WATER. THE DEVICE SHOULD CONFORM TO ASSE 1070.
  
 6. 2020 FPC 1003.4 - PLEASE DETAIL THE OIL ALARM FOR
 THE ELEVATOR SUMPS OR SHOW THE OIL SEPARATOR THAT WOULD
 BE REQUIRED IN IT'S ABSENCE.
  
 7. -------THE ELEVATOR SUMP PUMP DISCHARGE CANNOT GO TO
 THE STORM.
 WPB ORD. SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
  (C) ILLICIT CONNECTIONS. NO PERSON MAY MAINTAIN, USE
 OR ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE
 STORM WATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN
 VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS
 RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE
 PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR
 OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS
 OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE
 CONNECTION WAS MADE.
  
  
 8. -------THE DISCHARGE FROM AIR HANDLERS/AIR
 CONDITIONING CONDENSATE CANNOT DISCHARGE INTO THE
 SANITARY. IT MUST GO TO THE STORM OR OTHER APPROVED
 PLACE OF DISPOSAL.
 WPB ORD. SEC. 90 - 126 - PROHIBITIONS AND LIMITATIONS
 OF DISCHARGE.
  A) GENERALLY. USERS SHALL NOT DISCHARGE POLLUTANTS
 INTO THE WWF UNLESS IN ACCORDANCE WITH THIS ARTICLE.
  (B) DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE
 INTO THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE
 PASS THROUGH OR INTERFERE WITH THE OPERATION OR
 PERFORMANCE OF THE WWF. NO USER SHALL DISCHARGE INTO
 THE WWF OR ANY CONNECTED SYSTEM ANY WASTE OR WASTEWATER
 CONTAINING ANY OF THE FOLLOWING:
  (5) STORM WATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-18 Cont ID  
Sent By rmcphers Date 2023-01-18 Time 11:30 Rev Time 0.00
Received By rmcphers Date 2023-01-18 Time 11:29 Sent To  
Notes
2023-01-18 11:29:56SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL SIGNED AND SEALED DRAWINGS EXCEPT FOR S001 DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 15:20 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 15:20 Sent To  
Notes
2022-12-09 15:22:15SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL SIGNED AND SEALED DRAWINGS EXCEPT FOR S001 DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-09-22 Cont ID  
Sent By dbattles Date 2022-09-22 Time 09:03 Rev Time 0.00
Received By dbattles Date 2022-09-22 Time 09:03 Sent To  
Notes
2022-09-22 09:13:37SIGNATURE REVIEW COMMENTS:
  
 W.P.B. PERMIT: 2206
 REVIEWED: SEPTEMBER 22, 2022
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 -61G15-23 PE RULES FAC, FS 471 ENGINEERING FS
 -ARCHITECTS RULES FAC, FS 481 ARCHITECTS AND LANDSCAPE
 ARCHITECTS FS AND 61G10 LANDSCAPE ARCHITECTS RULES FAC
  
 107.2.1 FBC[AMENDED] SHEETS UPLOADED INTO DRAWINGS
 FOLDER ARE NOT DIGITALLY SIGNED.
 - PLEASE PROVIDE REPLACEMENT SHEETS THAT ARE DIGITALLY
 SIGNED FOR THE SECOND REVIEW CYCLE OR CONTACT ME FOR
 ALTERNATE SIGNATURE METHODS IF FULL REPLACEMENT IS NOT
 FEASABLE.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By jroach Date 2022-11-17 Time 12:02 Rev Time 0.00
Received By jroach Date 2022-11-17 Time 12:02 Sent To  
Notes
2022-11-17 12:04:38PRIOR TO CERTIFICATE OF OCCUPANCY (CO) OR CERTIFICATE
 OF COMPLETION (CC) A MINOR AMENDMENT TO THE TARGET
 COMMERCIAL PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED
 TO AND APPROVED BY THE CITY'S PLANNING DIVISION TO
 REFLECT THE REVISED PARKING CONFIGURATION/COUNT.
  
 THIS PERMIT REVIEW DOES NOT COVER THE INSTALLATION OF
 ANY SIGNAGE ON THE EXTERIOR OF THE BUILDING; SUCH
 SIGNAGE SHALL BE SUBJECT TO A SEPARATE PERMIT/REVIEW.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  