| Plan Review Stops For Permit 22080886 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-09-29 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-09-29 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2022-09-29 08:06:22 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2023-05-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-23 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-23 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-04-24 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-04-24 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-20 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-20 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2023-03-20 15:54:42 | 3RD D BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | 1.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED WINDOWS AND EXT. DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOAS DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-23 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-23 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2023-02-23 15:23:56 | 2ND BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE | | | SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | | | | 3. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) | | | R401.2COMPLIANCE. | | | SECTION R405 AND THE PROVISIONS OF SECTIONS R401 | | | THROUGH R404 LABELED MANDATORY. | | | | | | 4. IDENTIFY CEILING AND WALL INSULATION TYPE AND | | | R-VALUE ON PLANS. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 5. PROVIDE A WINDOW AND DOOR SCHEDULE. CREATE A LEGEND | | | AND IDENTIFY WINDOWS ON FLOOR PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 6.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED WINDOWS AND EXT. DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOAS DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7. PROVIDE A ROOF DRAINAGE [PLAN. | | | R903.4ROOF DRAINAGE. | | | UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF | | | DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE | | | ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL | | | BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR | | | PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY | | | THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. | | | R903.4.1OVERFLOW DRAINS AND SCUPPERS. | | | | | | 8. CORRECTED | | | | | | 9. CORRECTED | | | | | | 10.CORRECTED | | | | | | 11. PROVIDE A ROOF TRUSS TO EXT. WALL CONNECTOR | | | SCHEDULE.PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL | | | AND/OR REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW | | | COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | ***** UNSAT 2ND REVIEW **** | | | | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-07 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-07 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2022-11-07 13:10:23 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: VALUE WAS ADJUSTED TO $468,974 PER THE ICC | | | BUILDING VA;LUATION DATA. | | | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE | | | SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | | | | 3. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) | | | R401.2COMPLIANCE. | | | SECTION R405 AND THE PROVISIONS OF SECTIONS R401 | | | THROUGH R404 LABELED MANDATORY. | | | | | | 4. IDENTIFY CEILING AND WALL INSULATION TYPE AND | | | R-VALUE ON PLANS. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 5. PROVIDE A WINDOW AND DOOR SCHEDULE. CREATE A LEGEND | | | AND IDENTIFY WINDOWS ON FLOOR PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 6.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED WINDOWS AND EXT. DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOAS DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7. PROVIDE A ROOF DRAINAGE [PLAN. | | | R903.4ROOF DRAINAGE. | | | UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF | | | DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE | | | ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL | | | BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR | | | PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY | | | THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. | | | R903.4.1OVERFLOW DRAINS AND SCUPPERS. | | | | | | 8. STOOP LOCATED AT REAR FRENCH DOORS MUST BE THREE | | | FEET IN THE DIRECTION OF TRAVEL. | | | R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. | | | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH | | | EXTERIOR DOOR. | | | THE WIDTH OF EACH LANDING SHALL NOT BE LESS THAN THE | | | DOOR SERVED. EVERY LANDING SHALL HAVE A MINIMUM | | | DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE | | | DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE | | | PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT | | | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). | | | | | | 9. ELEVATION DRAWINGS: | | | REMOVE ALL OTHER ADDRESS FROM THE ELEVATION DRAWINGS. | | | INCLUDE THE EAST, WEST AND SOUTH ELEVATION. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 10. PLAN PAGE S2 SHOWS ROOF PRESSURES FOR A HIP ROOF. | | | THIS PROJECT WILL HAVE A FLAT ROOF. PROVIDE DESIGN | | | PRESSURES FOR A FLAT ROOVE. INCLUDE A FASTENER SCHEDULE | | | BASED ON THESE NEW PRESSURES. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 11. PROVIDE A ROOF TRUSS TO EXT. WALL CONNECTOR | | | SCHEDULE.PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL | | | AND/OR REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW | | | COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | ***** UNSAT 2ND REVIEW **** | | | | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2023-05-24 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-05-24 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-05-24 |
Time |
12:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-04-19 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-04-19 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-27 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-27 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-06 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-06 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-17 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-17 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2022-10-17 15:00:18 | ELECTRICAL REVIEW FAILED | | | | | | 1) ELECTRIC PANELS APPEAR TO BE LOCATED IN A CLOSET | | | WHICH IS NON-COMPLIANT WITH NEC 240.24(D) | | | 2) PLEASE PROVIDE SITE PLAN DETAILING ALL OUTSIDE | | | DISCONNECTS AND METERS. FBC 107.2 | | | 3) RISER DIAGRAM DETAILS ELECTRIC PANEL WITH #3 CU | | | FEEDERS SUPPLING A 200 AMP PANEL NOT IN COMPLIANCE WITH | | | NEC 310.15. PLEASE CORRECT AND SIZE FEEDERS AS PER | | | 310.15 TABLES | | | 4) PLEASE INCLUDE A NOTE WITH DRAWINGS STATING | | | GENERATORS, POOL AND SITE LIGHTING ARE UNDER SEPARATE | | | PERMITS | | | 5) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AT REAR OF | | | HOUSE AND NEXT TO AC EQUIPMENT AS PER NEC 210.50 (E), | | | 210.63 AND 210.64 | | | 6) IT APPEARS RECEPTACLE SPACING IN TO LEFT OF SINK IN | | | KITCHEN IS NOT COMPLIANT WITH NEC 210.52 FOR RECEPTACLE | | | SPACING | | | 7) PLEASE DETAIL DISHWASHER AND CLOTHES WASHER | | | RECEPTACLES ON ELECTRIC FLOOR PLAN. FBC 107.2 | | | 8) ELECTRIC PANEL SIZE ON RISER DIAGRAM CONFLICTS WITH | | | SIZE ON PANEL SCHEDULE. PLEASE CORRECT AS APPLICABLE. | | | FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
5 |
Status |
P |
Date |
2023-05-24 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-24 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-24 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2023-05-10 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-05-10 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-05-10 |
Time |
09:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-04-12 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-04-12 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-04-12 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-02-13 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-02-13 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-10-07 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-10-07 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2022-10-07 14:00:12 | PLEASE PROVIDE EXTERIOR ELEVATIONS FOR SOUTH, WEST AND | | | EAST. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-05-25 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-05-25 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-05-12 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-05-11 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-05-11 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-04-13 |
Time |
12:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-13 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-14 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-23 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-30 |
Time |
13:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-11-08 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-09-29 |
Time |
05:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-06-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-06-13 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-05-25 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2023-06-08 10:46:30 | RECEIPT MU-2023-023949 - $2491.56 PAID | | 2023-05-25 08:23:11 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-07 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-07 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2022-11-07 09:29:30 | IMPACT FEES | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2023-05-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-05-24 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-05-24 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2023-05-24 13:41:02 | PLAN PASS PROVISO | | | 1) REMOVE RETURN AIR FROM KITCHEN M1602 RETURN AIR | | | 2020 FBC RISIDENTIAL CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-24 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-24 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2023-04-24 07:51:17 | | | | PLEASE UNDERSTAND THE DESIGN OF THE MECHANICAL DRAWINGS | | | IS UNKNOW. THE DESIGNER OF THE MECHANICAL DRAWINGS MUST | | | PRINT AND SIGN THEIR NAME ON EACH SHEET. SEE PREVIOUS | | | COMMENT BELOW: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-16 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-16 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2023-03-16 08:20:28 | 3RD REVIEW FMC | | | PERMIT: 22080886 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) FIRST FLOOR BATH EXHAUST FAN SHOULD BE A MINIMUM OF | | | 50 CFM. FRC TABLE M1506.2 | | | | | | 2) PROVIDE THE DUCT SIZES FOR ALL BATH EXHAUST FANS. | | | FRC TABLE M1506.2 | | | | | | 3) THE RETURNS DO NOT SHOW ANY DUCTWORK. IS THE SPACE | | | ABOVE THE CEILING TO BE A RETURN AIR PLENUM? IF SO, ADD | | | A DETAIL DRAWING AND PROVIDE A NOTE ON THE DRAWINGS TO | | | SHOW THIS OR SHOW THE RETURN AIR DUCTWORK SYSTEM. FRC | | | M1601.1.1 NOTE 7.4 | | | | | | 4) PROVIDE THE DRYER DUCT MATERIAL, LENGTH, AND | | | TERMINATION LOCATION. FRC M1502 | | | | | | 5) PROVIDE THE ANCHORAGE DETAIL FOR THE CONDENSING | | | UNIT. FRC M1307.2 | | | | | | 6) PROVIDE THE CONDENSATE DISPOSAL PIPING AND | | | TERMINATION LOCATION. FRC M1411.3 | | | | | | 7) PROVIDE THE TERMINATION LOCATION FOR THE KITCHEN | | | HOOD EXHAUST. FRC M1506.3 | | | | | | 8) THE DESIGNER OF THE MECHANICAL SYSTEM WILL NEED TO | | | DIGITALLY SIGN THE DOCUMENTS. FS 471/481 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-31 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-31 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2023-01-31 07:44:31 | 2ND REVIEW FMC | | | PERMIT: 22080886 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1 IS THE ELECTRICAL DRAWING. PROVIDE A | | | COMPLETE MECHANICAL DRAWING FOR THIS PROJECT ALONG WITH | | | THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT | | | SIZING CALCULATIONS. | | | SEE BELOW: | | | | | | PROVIDE ALL THAT APPLY FROM THE LIST BELOW: | | | | | | FBC 107.3.5- | | | MECHANICAL: | | | 1. ENERGY CALCULATIONS | | | 2. EXHAUST SYSTEMS: | | | CLOTHES DRYER EXHAUST | | | KITCHEN EQUIPMENT EXHAUST | | | SPECIALTY EXHAUST SYSTEMS | | | 3. EQUIPMENT | | | 4. EQUIPMENT LOCATION | | | 5. MAKE-UP AIR | | | 6. ROOF-MOUNTED EQUIPMENT | | | 7. DUCT SYSTEMS | | | 8. VENTILATION | | | 9. COMBUSTION AIR | | | 10. CHIMNEYS, FIREPLACES AND VENTS | | | 11. APPLIANCES | | | 12. BOILERS | | | 13. REFRIGERATION | | | 14. BATHROOM VENTILATION | | | 15. LABORATORY | | | 16. DESIGN FLOOD ELEVATION | | | | | | | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-06 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-06 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2022-10-06 09:49:08 | 1ST REVIEW FMC | | | PERMIT: 22080886 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THERE WAS NOTHING SUBMITTED FOR THE MECHANICAL | | | DESIGN OF THIS NEW 2 STORY RESIDENCE. PROVIDE A | | | COMPLETE MECHANICAL DESIGN FOR THIS 2 STORY NEW | | | RESIDENCE. FBC 107.3.5 | | | | | | 107.3.5 | | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING | | | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA | | | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION | | | PLAN; FLOOR/ROOF | | | FRAMING PLAN OR TRUSS LAYOUT; ALL FENESTRATION | | | PENETRATIONS; FLASHING; AND ROUGH OPENING DIMENSIONS; | | | AND ALL EXTERIOR ELEVATIONS: | | | | | | MECHANICAL: | | | 1. ENERGY CALCULATIONS | | | 2. EXHAUST SYSTEMS: | | | CLOTHES DRYER EXHAUST | | | KITCHEN EQUIPMENT EXHAUST | | | SPECIALTY EXHAUST SYSTEMS | | | 3. EQUIPMENT | | | 4. EQUIPMENT LOCATION | | | 5. MAKE-UP AIR | | | 6. ROOF-MOUNTED EQUIPMENT | | | 7. DUCT SYSTEMS | | | 8. VENTILATION | | | 9. COMBUSTION AIR | | | 10. CHIMNEYS, FIREPLACES AND VENTS | | | 11. APPLIANCES | | | 12. BOILERS | | | 13. REFRIGERATION | | | 14. BATHROOM VENTILATION | | | 15. LABORATORY | | | 16. DESIGN FLOOD ELEVATION | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-05-15 |
Time |
06:05 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-05-15 |
Time |
06:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-17 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-17 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2023-04-17 07:27:22 | 4TH PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. BATH #2 -- 2020 FRC P3108.1 - THE LAUNDRY CANNOT | | | VENT THE SHOWER. THE LAUNDRY MUST DISCHARGE DOWNSTREAM | | | OF THE WET VENT SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-17 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-17 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2023-03-17 10:27:52 | 3RD PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC P3101.2.1 - THE BATHROOM GROUPS AND THE | | | KITCHEN ARE NOT VENTED. THE DOUBLE BOWL LAV IN THE | | | MASTER HAS A TRAP BELOW THE FLOOR THAT SERVES TWO | | | FIXTURES AND CANNOT, AND IT'S NOT VENTED. SHOWING TRAPS | | | BENEATH THE FLOOR FOR EACH LAVATORY IS BOTH NOT TYPICAL | | | AND NOT TO CODE. THE RISER ON EACH TRAP IS LIMITED TO | | | 24" (FRC P3201.6), AND THE CABINET HEIGHT COMBINED | | | WOULD EXCEED THAT. ALSO, WOULD CREATE AN ILLEGAL TRAP | | | TYPE (S-TRAP) PLEASE SUBMIT A CODE COMPLIANT DRAWING. | | | | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-01 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-01 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2023-02-01 07:23:17 | 2ND PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | COMMENTS NOT ADDRESSED | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - THE PLUMBING RISER | | | DOES NOT REPRESENT TYPICAL PLUMBING AND IS PARTIAL IN | | | COMPLETION. THE SHOWER AND TUB ARE NOT SHOWN. THE | | | SHOWERS THAT ARE SHOWN DO NOT SHOW A TRAPS. THE TOILETS | | | DO NOT CONNECT IN A TYPICAL MANNER (HORIZONTALLY) TO | | | THE HORIZONTAL BRANCHES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-03 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-03 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2022-10-03 15:08:00 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - THE PLUMBING RISER | | | DOES NOT REPRESENT TYPICAL PLUMBING AND IS PARTIAL IN | | | COMPLETION. THE SHOWER AND TUB ARE NOT SHOWN. THE | | | SHOWERS THAT ARE SHOWN DO NOT SHOW A TRAPS. THE TOILETS | | | DO NOT CONNECT IN A TYPICAL MANNER (HORIZONTALLY) TO | | | THE HORIZONTAL BRANCHES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-07 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-07 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2022-11-07 10:37:07 | PROVISO ON PLAN PAGE S2: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
N |
Date |
2023-05-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-23 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-23 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
N |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-04-24 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-04-24 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-20 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-20 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2023-03-20 14:10:51 | 3RD SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | 2023-03-16 08:23:10 | THE DESIGNER OF THE MECHANICAL DOCUMENTS WILL NEED TO | | | SIGN EACH SHEET. ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-06 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-06 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2023-02-06 13:25:04 | PREVIOUS COMMENTS NOT ADDRESSED | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-07 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-07 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2022-11-07 12:07:09 | 1ST SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | | | | 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | | SHEETS UNDER THEIR AUTHORITY. | | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2023-05-24 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-24 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-24 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2023-05-10 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-05-10 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-05-10 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-03-28 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-03-28 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-02-13 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-02-13 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2023-02-13 10:05:55 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | REVISED PLANS SHOW PORCH EXTENDING TOO FAR INTO FRONT | | | SETBACK. PORCH MAY ONLY ENCROACH UP TO 3FT INTO | | | SETBACK, PLEASE REVISE | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-10-07 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-10-07 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2022-10-07 13:59:09 | REQUIRES SUBMITTAL OF SEPERATE LANDSCAPE PERMIT |
|
|