Plan Review Details - Permit 22080874
Plan Review Stops For Permit 22080874
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-08-29 Cont ID  
Sent By cpuell Date 2022-08-29 Time 16:30 Rev Time 0.00
Received By cpuell Date 2022-08-29 Time 16:30 Sent To  
Notes
2022-08-29 16:31:07ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 5 Status P Date   Cont ID  
Sent By   Date 2023-01-12 Time   Rev Time 0.00
Received By swelter Date 2023-01-12 Time 11:53 Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 4 Status F Date 2022-10-13 Cont ID  
Sent By swelter Date 2022-10-13 Time 10:50 Rev Time 0.00
Received By swelter Date 2022-10-13 Time 10:54 Sent To  
Notes
2022-10-13 10:54:22DEVELOPER RECEIVED ART APPLICATION - REQUESTED OPTION 2
 CONTRIBUTION. 9.14.2022 SENT
 EMAIL REMINDER TO JORDAN SPERLING SENT 10.06.2022
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status F Date 2022-10-07 Cont ID  
Sent By swelter Date 2022-10-07 Time 11:45 Rev Time 0.00
Received By swelter Date 2022-10-07 Time 11:47 Sent To  
Notes
2022-10-07 11:47:23INVOICE - PUBLIC ART ASSESSMENT DUE NOW. SENT 09/15 AND
 RESENT 10/06 TO JORDAN SPELLING.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By swelter Date 2022-10-06 Time 09:43 Rev Time 0.00
Received By swelter Date 2022-10-21 Time 12:45 Sent To  
Notes
2022-10-21 12:44:59PUBLIC ART REQUIREMENT MET - OPTION 2

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2022-12-12 Cont ID  
Sent By swelter Date 2022-12-12 Time 11:41 Rev Time 0.00
Received By swelter Date 2022-12-12 Time 11:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By rmcphers Date 2022-10-04 Time 16:07 Rev Time 0.00
Received By rmcphers Date 2022-10-04 Time 13:48 Sent To  
Notes
2022-10-04 16:07:49NEW CAR WASH BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE
 PRODUCT APPROVALS - FL14218 AND FL16554
  
 2) PLEASE PROVIDE A COPY OF THE SOILS REPORT REFERENCED
 ON DRAWING S1.0
  
 3) THE BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING 3.0
 - WOOD FRAMING SHOWN ON DRAWING S3.0 SHOULD BE FIRE
 RETARDANT - FBC 603.1
  
 4) PLEASE SHOW THE ACCESSIBLE VACUUM PARKING SPACE -
 FBC ACCESSIBILITY 228.1
  
 5) SEPARATE PERMITS REQUIRED FOR - DUMPSTER ENCLOSURE,
 PARKING LOT, SIGNS
  
 6) DRAWINGS SP-1, RP-1 AND ALL OF THE CIVIL DRAWINGS DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-08 Cont ID  
Sent By mpeterso Date 2022-12-08 Time 13:52 Rev Time 0.00
Received By mpeterso Date 2022-12-08 Time 13:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-05 Cont ID  
Sent By mpeterso Date 2022-10-05 Time 09:55 Rev Time 0.00
Received By mpeterso Date 2022-10-04 Time 12:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By rrossano Date 2023-01-17 Time   Rev Time 0.00
Received By rrossano Date 2023-01-17 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-11-14 Cont ID  
Sent By rrossano Date 2022-11-14 Time   Rev Time 0.00
Received By rrossano Date 2022-11-14 Time   Sent To  
Notes
2022-11-14 12:54:11UNDER FORMAL ENGINEERING SUBMITTAL REVIEW E22100035.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By rrossano Date 2022-08-29 Time   Rev Time  
Received By rrossano Date 2022-08-29 Time   Sent To  
Notes
2022-08-29 09:31:14SITE PLAN APPROVAL AND FORMAL ENGINEERING SUBMITTALS
 REVIEWS ARE REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-14 Cont ID  
Sent By   Date 2022-11-14 Time   Rev Time 0.00
Received By jcclark Date 2022-11-14 Time 13:34 Sent To  
Notes
2022-11-14 13:34:56PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By   Date 2022-09-06 Time   Rev Time 0.00
Received By bdolan Date 2022-09-06 Time 13:09 Sent To  
Notes
2022-09-06 13:09:46PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-02-08 Cont ID  
Sent By dbattles Date 2023-02-08 Time 09:23 Rev Time 0.00
Received By dbattles Date 2023-02-08 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-06 Cont ID  
Sent By dbattles Date 2023-02-06 Time 11:15 Rev Time 0.00
Received By dbattles Date 2023-01-25 Time 15:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-17 Cont ID  
Sent By dbattles Date 2023-01-17 Time 13:38 Rev Time 0.00
Received By dbattles Date 2023-01-09 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-12 Cont ID  
Sent By aoliver Date 2022-12-12 Time 10:28 Rev Time 0.00
Received By aoliver Date 2022-11-13 Time 18:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-31 Cont ID  
Sent By aoliver Date 2022-10-31 Time 06:43 Rev Time 0.00
Received By aoliver Date 2022-08-25 Time 10:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-02-02 Cont ID  
Sent By aoliver Date 2023-02-02 Time 11:08 Rev Time 0.00
Received By aoliver Date 2023-01-31 Time 14:33 Sent To  
Notes
2023-02-02 11:08:01NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2023-01-31 14:33:581/31/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By rmcphers Date 2022-10-04 Time 15:38 Rev Time 0.00
Received By rmcphers Date 2022-10-04 Time 15:38 Sent To  
Notes
2022-10-04 15:39:52PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-29 Cont ID  
Sent By medwards Date 2022-11-29 Time 15:02 Rev Time 0.00
Received By medwards Date 2022-11-29 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-16 Cont ID  
Sent By medwards Date 2022-09-16 Time 05:53 Rev Time 0.00
Received By medwards Date 2022-09-16 Time 05:53 Sent To  
Notes
2022-09-16 05:53:461ST REVIEW FMC
 PERMIT: 22080874
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.2: PLEASE SHOW THE ROOF HATCH OPENING AND
 EQUIPMENT ON THE ROOF WILL MEET THE GUARD PROTECTION
 REQUIREMENT IN FMC 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-01-26 Cont ID  
Sent By ccole Date 2023-01-26 Time 09:28 Rev Time 0.00
Received By ccole Date 2023-01-26 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-01-13 Cont ID  
Sent By ccole Date 2023-01-13 Time 16:54 Rev Time 0.00
Received By ccole Date 2023-01-13 Time 12:17 Sent To  
Notes
2023-01-13 17:08:44 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22080874
 1/3/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 3RD REQUEST FOR A PERMIT APPLICATION FOR THE
 OIL/SAND INTERCEPTOR TO BE SUBMITTED. THE APPLICATION
 SHALL NOT BE SUBMITTED UNDER THIS PERMIT BUT SEPARATELY
 AS THE YOU HAVE SUBMITTED THE BACKFLOW. AS PREVIOUSLY
 NOTED, I CANNOT APPROVE THE PLUMBING PLANS WITHOUT
 SUBMITTAL OF THE PERMIT APPLICATION FOR THE OIL
 INTERCEPTOR. BASED ON THE RESUBMITTED PLUMBING
 SPECIFYING A SEPARATE PERMIT APPLICATION FOR THE WATER
 REUSE SYSTEM AND RECLAIM TANKS, I CANNOT APPROVE THE
 PLANS WITHOUT SUBMITTAL OF THAT PERMIT APPLICATION.
 THIS WILL ENSURE THAT PERMIT ISSUANCE AND INSPECTIONS
 WILL BE DONE IN TIMELY AND ORDERLY MANNER. PLEASE SEE
 PREVIOUS COMMENT BELOW-
  
 PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 2) SHEETS P1, P4: PLEASE REVISE THE OIL/SAND ISOMETRIC
 DRAWING TO MATCH THE NEW PIPING LAYOUT SHOWN ON P1-
 SEC. 107.2.1 WPB. IT ALSO APPEARS THE LOCATIONS OF THE
 RECLAIM AND OIL DRAIN PIPES AND DRAIN PIPE SIZES ON
 SHEET 3.4 (TRENCH DRAIN CROSS SECTION) DO NOT MATCH
 WITH REVISED P1.
  
 3) P1: SCH 80 PVC SPECIFIED FOR VACUUM PIPING ON THE
 SITE PLAN, HOWEVER THE SUBMITTED SHOP DRAWINGS SPECIFY
 SCH 40. PLEASE CLARIFY IF THE SYSTEM WILL BE PART OF
 THE MAIN PERMIT OR IF TO BE INSTALLED UNDER A SEPARATE
 PERMIT- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-29 Cont ID  
Sent By ccole Date 2022-11-29 Time 15:34 Rev Time 0.00
Received By ccole Date 2022-11-23 Time 14:23 Sent To  
Notes
2022-11-29 15:36:192ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22080874
 11/29/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS #1, 3, 5, & 10
 FROM THE 1ST REVIEW WERE NOT COMPLETELY ADDRESSED. I
 HAVE LISTED THE NUMBER OF THE COMMENTS AND FOLLOW-UP
 NOTES BELOW. NEW COMMENTS BASED ON RESUBMITTED PLANS
 ARE ALSO LISTED BELOW.
  
 1) CONCERNING COMMENT #1 PLEASE NOTE THAT I CANNOT
 APPROVE THE PLUMBING PLANS WITHOUT SUBMITTAL OF THE
 PERMIT APPLICATIONS FOR THE POTABLE WATER SERVICE
 BACKFLOW PREVENTER AND OIL INTERCEPTOR.
 PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 3) THE CORRECTED PLANS AND SHOP DRAWINGS FOR THE WATER
 REUSE SYSTEM DO NOT APPEAR TO ADDRESS THE FOLLOWING
 ITEMS:
 1301.9.4 MAKEUP WATER.
 WHERE AN UNINTERRUPTED SUPPLY IS REQUIRED FOR THE
 INTENDED APPLICATION, POTABLE OR RECLAIMED WATER SHALL
 BE PROVIDED AS A SOURCE OF MAKEUP WATER FOR THE STORAGE
 TANK. THE MAKEUP WATER SUPPLY SHALL BE PROTECTED
 AGAINST BACKFLOW IN ACCORDANCE WITH SECTION 608. A
 FULL-OPEN VALVE LOCATED ON THE MAKEUP WATER SUPPLY LINE
 TO THE STORAGE TANK SHALL BE PROVIDED. INLETS TO THE
 STORAGE TANK SHALL BE CONTROLLED BY FILL VALVES OR
 OTHER AUTOMATIC SUPPLY VALVES INSTALLED TO PREVENT THE
 TANK FROM OVERFLOWING AND TO PREVENT THE WATER LEVEL
 FROM DROPPING BELOW A PREDETERMINED POINT. WHERE MAKEUP
 WATER IS PROVIDED, THE WATER LEVEL SHALL NOT BE
 PERMITTED TO DROP BELOW THE SOURCE WATER INLET OR THE
 INTAKE OF ANY ATTACHED PUMP.
 1301.9.5 OVERFLOW.
 THE STORAGE TANK SHALL BE EQUIPPED WITH AN OVERFLOW
 PIPE HAVING A DIAMETER NOT LESS THAN THAT SHOWN IN
 TABLE 606.5.4. THE OVERFLOW PIPE SHALL BE PROTECTED
 FROM INSECTS OR VERMIN AND SHALL DISCHARGE IN A MANNER
 CONSISTENT WITH STORM WATER RUNOFF REQUIREMENTS OF THE
 JURISDICTION. THE OVERFLOW PIPE SHALL DISCHARGE AT A
 SUFFICIENT DISTANCE FROM THE TANK TO AVOID DAMAGING THE
 TANK FOUNDATION OR THE ADJACENT PROPERTY. DRAINAGE FROM
 OVERFLOW PIPES SHALL BE DIRECTED TO PREVENT FREEZING ON
 ROOF WALKWAYS. THE OVERFLOW DRAIN SHALL NOT BE EQUIPPED
 WITH A SHUTOFF VALVE. A CLEANOUT SHALL BE PROVIDED ON
 EACH OVERFLOW PIPE IN ACCORDANCE WITH SECTION 708.
 1301.9.6 ACCESS.
 NOT LESS THAN ONE ACCESS OPENING SHALL BE PROVIDED TO
 ALLOW INSPECTION AND CLEANING OF THE TANK INTERIOR.
 ACCESS OPENINGS SHALL HAVE AN APPROVED LOCKING DEVICE
 OR OTHER APPROVED METHOD OF SECURING ACCESS.
 BELOW-GRADE STORAGE TANKS, LOCATED OUTSIDE OF THE
 BUILDING, SHALL BE PROVIDED WITH A MANHOLE EITHER NOT
 LESS THAN 24 INCHES SQUARE OR WITH AN INSIDE DIAMETER
 NOT LESS THAN 24 INCHES. MANHOLES SHALL EXTEND NOT LESS
 THAN 4 INCHES ABOVE GROUND OR SHALL BE DESIGNED TO
 PREVENT WATER INFILTRATION. FINISHED GRADE SHALL BE
 SLOPED AWAY FROM THE MANHOLE TO DIVERT SURFACE WATER.
 MANHOLE COVERS SHALL BE SECURED TO PREVENT UNAUTHORIZED
 ACCESS. SERVICE PORTS IN MANHOLE COVERS SHALL BE NOT
 LESS THAN 8 INCHES IN DIAMETER AND SHALL BE NOT LESS
 THAN 4 INCHES ABOVE THE FINISHED GRADE LEVEL. THE
 SERVICE PORT SHALL BE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: WATER STORAGE TANKS FOR TREATED WATER THAT
 ARE LESS THAN 800 GALLONS IN VOLUME AND INSTALLED BELOW
 GRADE SHALL NOT BE REQUIRED TO BE EQUIPPED WITH A
 MANHOLE, PROVIDED THAT THE TANK HAS A SERVICE PORT OF
 NOT LESS THAN 8 INCHES IN DIAMETER.
 1301.9.7 VENTING.
 STORAGE TANKS SHALL BE PROVIDED WITH A VENT SIZED IN
 ACCORDANCE WITH CHAPTER 9 AND BASED ON THE AGGREGATE
 DIAMETER OF ALL TANK INFLUENT PIPES. THE RESERVOIR VENT
 SHALL NOT BE CONNECTED TO SANITARY DRAINAGE SYSTEM
 VENTS. VENTS SHALL BE PROTECTED FROM CONTAMINATION BY
 MEANS OF AN APPROVED CAP OR U-BEND INSTALLED WITH THE
 OPENING DIRECTED DOWNWARD. VENT OUTLETS SHALL EXTEND
 NOT LESS THAN 4 INCHES ABOVE GRADE OR AS NECESSARY TO
 PREVENT SURFACE WATER FROM ENTERING THE STORAGE TANK.
 VENT OPENINGS SHALL BE PROTECTED AGAINST THE ENTRANCE
 OF VERMIN AND INSECTS IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 1301.7.
 1301.9.8 DRAINING OF TANKS.
 TANKS SHALL BE PROVIDED WITH A MEANS OF EMPTYING THE
 CONTENTS FOR THE PURPOSE OF SERVICE OR CLEANING. TANKS
 SHALL BE DRAINED BY USING A PUMP OR BY A DRAIN LOCATED
 AT THE LOWEST POINT IN THE TANK. THE TANK DRAIN PIPE
 SHALL DISCHARGE AS REQUIRED FOR OVERFLOW PIPES AND
 SHALL NOT BE SMALLER IN SIZE THAN SPECIFIED IN TABLE
 606.5.7. NOT LESS THAN ONE CLEANOUT SHALL BE PROVIDED
 ON EACH DRAIN PIPE IN ACCORDANCE WITH SECTION 708.
 1301.9.9 MARKING AND SIGNAGE.
 EACH NONPOTABLE WATER STORAGE TANK SHALL BE LABELED
 WITH ITS RATED CAPACITY. THE CONTENTS OF STORAGE TANKS
 SHALL BE IDENTIFIED WITH THE WORDS "CAUTION: NONPOTABLE
 WATER" DO NOT DRINK." WHERE AN OPENING IS PROVIDED THAT
 COULD ALLOW THE ENTRY OF PERSONNEL, THE OPENING SHALL
 BE MARKED WITH THE WORDS, ???DANGER ??? CONFINED
 SPACE.??? MARKINGS SHALL BE INDELIBLY PRINTED ON THE
 TANK OR ON A TAG OR SIGN CONSTRUCTED OF
 CORROSION-RESISTANT WATERPROOF MATERIAL THAT IS MOUNTED
 ON THE TANK. THE LETTERS OF THE WORDS SHALL BE NOT LESS
 THAN 0.5 INCH IN HEIGHT AND SHALL BE OF A COLOR IN
 CONTRAST WITH THE BACKGROUND ON WHICH THEY ARE APPLIED.
  
  
 5) SHEET P4: PLEASE INDICATE THE WATTS MIXING VALVE IS
 ASSE 1017 APPROVED FOR USE AT THE HOT WATER SOURCE-
 SEC. 607.1.1 FBC P.
  
 10) THE NEW VACCUM SYSTEM SHOP DRAWINGS REFERENCE
 COMPRESSED AIR PIPING AND THE AIR COMPRESSOR BY OTHERS
 ON PAGE V101. PLEASE PROVIDE MORE INFORMATION
 INCLUDING:
 A) COMPRESSOR LOCATION.
 B) COMPRESSOR EQUIPMENT SCHEDULE.
 C) COMPRESSED AIR PIPING RUNS AND TYPES AND SIZES OF
 PIPING.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
  
 1) SHEETS P2 & P4: THE PIPING FLOOR PLAN DRAWING SHOWS
 CW LINES DROPPING FROM THE MAIN LINE TO THE RECLAIM
 SYSTEM PUMP, AND OTHER CAR WASH EQUIPMENT. PLEASE
 PROVIDE BACKFLOW PREVENTERS AT THESE LOCATIONS TO
 PROTECT THE MAIN LINE WHICH IS ALSO SUPPLYING POTABLE
 WATER FIXTURES- SEC. 608.16 FBC P.
  
 2) P2 & P4: THE WATER RISER DRAWING DOES NOT SHOW THE
 CW DROPS TO THE CAR WASH EQUIPMENT AND REQUIRED BF
 PREVENTER LOCATIONS- SEC. 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-21 Cont ID  
Sent By ccole Date 2022-09-21 Time 13:52 Rev Time 0.00
Received By ccole Date 2022-09-19 Time 14:38 Sent To  
Notes
2022-09-21 13:55:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080874
 9/19/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 1.1 & P.1: SEPARATE PERMITS ARE REQUIRED FOR
 INSTALLATION OF THE POTABLE WATER BACKFLOW PREVENTER,
 THE EQUIPMENT WATER SERVICE BACKFLOW PREVENTER,
 OIL/SAND SEPARATOR, AND THE IRRIGATION SYSTEM- SECS.
 105.1 & 107.2.1 WPB.
  
 PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 2) P.1 OIL/SAND SEPARATOR: A SEPARATE PERMIT, PLANS AND
 SPECIFICATIONS ARE REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. A)
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR
 INDICATING THE MANUFACTURER AND LISTING NUMBER AND
 SUBMIT SPECS FOR THE UNIT- SEC. 1003.4.2 FBC P. B)
 UNLISTED INTERCEPTORS SHALL COMPLY WITH SECS.
 1003.2.4.1 & 1003.4.2.2. AND DETAILS SHALL BE PROVIDED
 INDICATING THE UNIT HAS A DEPTH OF 2 FT. BELOW THE
 INVERT, NOT LESS THAN AN 18-INCH WATER SEAL, AND SHALL
 HAVE A CAPACITY NOT LESS THAN 6 CU. FT. FOR THE FIRST
 100 SQ. FT. OF AREA TO BE DRAINED PLUS 1 CU. FT. FOR
 EACH ADDITIONAL 100 SQ. FT. C) PLEASE PROVIDE AN
 ENLARGED PIPING AND INSTALLATION DIAGRAM SHOWING THE
 LOCATIONS OF CLEANOUTS, VENTS, AND SAMPLING PORT- SEC.
 1003.9. D) PROVIDE INTERCEPTOR INSTALLATION DETAILS
 INCLUDING AN ELEVATION VIEW SHOWING THE BURIAL DEPTH,
 FOUNDATION BASE MATERIAL, AND BACKFILLING FOR SUPPORT
 AND STABILIZATION OF THE TANK. PLEASE CONTACT THE CITY
 OF WEST PALM BEACH UTILITIES DEPT. FOR ADDITIONAL
 REQUIRED INSPECTION AND TEST SAMPLING INFORMATION AND
 GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065
 OR 561-822-2274 OR EMAIL [email protected]. E) ALL SUBMITTALS
 SHALL BE APPROVED AND STAMPED BY THE DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE- SECTION 107.2.1,
 107.3.4. WPB. SUBMITTALS MAY BE DEFERRED IN ACCORDANCE
 WITH SECTION 107.3.4.1 WPB.
  
 3) P.1: CAR WASH ONSITE WATER REUSE SYSTEM- SECS.1301 &
 1302 FBC P. A) PROVIDE AN ISOMETRIC DRAWING SHOWING THE
 PIPING RUNS BETWEEN THE WASH BAY DRAINS TO THE TANKS,
 AND LOCATIONS OF PUMP, DRAINS, VENTS, CLEANOUTS AND
 MAKEUP WATER CONNECTION. B) PROVIDE STORAGE TANK AND
 TRAFFIC LID SPECIFICATIONS FROM THE MANUFACTURERS. C)
 PROVIDE TANK INSTALLATION DETAILS INCLUDING ELEVATION
 VIEWS SHOWING THE BURIAL DEPTH, FOUNDATION BASE
 MATERIALS AND BACKFILLING FOR SUPPORT. D) PROVIDE
 PIPING SPECIFICATIONS. E) ALL SUBMITTALS SHALL BE
 APPROVED AND STAMP BY THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE- SECTIONS 107.2.1 & 107.3.4. WPB.
 SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION
 107.3.4.1 WPB.
  
 4) P1, P.4 & P.5: PLEASE ADD THE WASHER AND WASHER
 EXTRACTOR TO THE EQUIPMENT SCHEDULE- SEC. 107.2.1 WPB.
 A) LINT INTERCEPTORS ARE REQUIRED FOR THE WASHER AND
 WASHER EXTRACTOR- SEC. 1003.6 FBC P. PLEASE ADD THE
 INTERCEPTORS TO THE EQUIPMENT SCHEDULE AND REVISE THE
 PLANS TO SHOW LOCATIONS AND PIPING DETAILS.
  
 5) P.2 & P.4: A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE FROM THE WASHING MACHINES AND MOP
 SINK SHALL BE PROVIDED IN ACCORDANCE WITH SEC. 607.1.1
 FBC P.
  
 6) P.2 & P.4: PLEASE PROVIDE SEPARATE LINE SYMBOLS TO
 DISTINGUISH HW AND HWR PIPING- SEC. 107.2.1 WPB.
  
 7) P.5: REVISE THE WATER HEATER DETAIL TO SHOW THE
 LOCATIONS OF THE RECIRCULATION PUMP, HW RETURN LINE
 CONNECTIONS, AND THE DRAIN PAN LINE AND TERMINATION
 LOCATION- SECS. 607.2.1.2 & 504.7.1, 507.4.7.2 FBC P.
  
 8) P.4 ROOF DRAINAGE: PROVIDE THE RAINFALL RATE USED AS
 THE BASIS OF THE CALCULATIONS- SEC. 1105.2 & 1106.1 FBC
 P. A) IT APPEARS WATER FROM THE UPPER ROOF WILL DRAIN
 ONTO THE MAIN ROOF. PLEASE ADD THE SQUARE FOOTAGE AND
 GPM FOR THE UPPER ROOF TO THE CALCULATIONS- SEC.
 107.2.1 WPB.
  
 9) SHEETS 3.1 & 3.3: REFER TO SECTIONS 306, 307, AND
 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW THE LOCATIONS OF THE FOUNTAINS
 WILL BE IN COMPLIANCE WITH SECTION 307.2 PROTRUSION
 LIMITS.
  
 10) SHEET 2.1 VACUUM AND COMPRESSED AIR SYSTEM A)
 PROVIDE PIPING LAYOUT DRAWINGS THAT SHOW THE TYPES AND
 SIZES OF VACUUM AND COMPRESSED AIR PIPINGS, AND THE
 PIPING RUNS. B) PROVIDE EQUIPMENT SCHEDULES FOR THE
 VACUUM AND COMPRESSOR AND EQUIPMENT ANCHORING DETAILS-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2022-09-21 Cont ID  
Sent By ccole Date 2022-09-21 Time 13:55 Rev Time 0.00
Received By ccole Date 2022-09-21 Time 13:55 Sent To  
Notes
2022-09-21 13:56:32A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR
 THE OIL/SAND INTERCEPTOR.

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2022-09-21 Cont ID  
Sent By ccole Date 2022-09-21 Time 13:57 Rev Time 0.00
Received By ccole Date 2022-09-21 Time 13:57 Sent To  
Notes
2022-09-21 13:59:57A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR
 THE IRRIGATION SYSTEM.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2023-02-08 Cont ID  
Sent By dbattles Date 2023-02-08 Time 09:15 Rev Time 0.00
Received By dbattles Date 2023-02-08 Time 09:15 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By dbattles Date 2023-02-06 Time 11:06 Rev Time 0.00
Received By dbattles Date 2023-02-06 Time 11:01 Sent To  
Notes
2023-02-06 11:15:15 
  
 1. CERTIFICATE OF INSURANCE FOR PROFESSIONAL LIABILITY
 OF FIRM. MINIMUM COVERAGE OF $1,000,000.00 PER
 OCCURRENCE AND $2,000,000.00 AGGREGATE ARE REQUIRED.
 F.S. 553.791 (4) (B) AND (16). CERTIFICATE OF INSURANCE
 FOR PROFESSIONAL LIABILITY OF FIRM. MINIMUM COVERAGE OF
 $1,000,000.00 PER OCCURRENCE AND $2,000,000.00
 AGGREGATE ARE REQUIRED. F.S. 553.791 (4) (B) AND (16).
 IN THE DESCRIPTION OF OPERATIONS PLEASE ADD LANGUAGE TO
 STATE "THE PROFESSIONAL LIABILITY POLICY INCLUDES AN
 EXTENDED REPORTING PERIOD ENDORSEMENT (TAIL COVERAGE)
 FOR FIVE YEARS. ___________IS PROVIDING PROFESSIONAL
 LIABILITY INSURANCE COVERING ALL SERVICES TO BE
 PERFORMED AS A PRIVATE PROVIDER.
 -PLEASE PROVIDE CERTIFICATE OF INSURANCE
  
 2. PLEASE PROVIDE QUALIFICATIONS FOR INSPECTORS WITH
 THEIR LICENSES.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 14:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-10-04 Cont ID  
Sent By rmcphers Date 2022-10-04 Time 15:40 Rev Time 0.00
Received By rmcphers Date 2022-10-04 Time 15:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-26 Cont ID  
Sent By ccole Date 2023-01-26 Time 09:28 Rev Time 0.00
Received By ccole Date 2023-01-26 Time 09:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-10 Cont ID  
Sent By pvalenti Date 2023-01-10 Time 07:14 Rev Time 0.00
Received By pvalenti Date 2023-01-10 Time 07:13 Sent To  
Notes
2023-01-10 07:19:10 
  
 SIGNATURE REVIEW DENIED:
  
 THE CIVIL DRAWINGS (9) SHEETS HAVE BEEN APPROVED BY
 SUBMITTAL OF ORIGINAL HAND SIGNED/SEALED PAPER PLAN
 SHEETS.
  
 PLAN SHEETS SP-1 & RP-1 ARE STILL PENDING SIGNATURES
 PER THE NOTES BELOW:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 14:07 Sent To  
Notes
2022-12-08 14:08:18SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP-1, RP-1 AND ALL OF THE CIVIL DRAWINGS DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 MECHANICAL DIGITAL SIGNATURES APPROVED ME
2022-11-29 15:03:22MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By rmcphers Date 2022-10-04 Time 16:20 Rev Time 0.00
Received By rmcphers Date 2022-10-04 Time 16:20 Sent To  
Notes
2022-10-04 16:22:33SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP-1, RP-1 AND ALL OF THE CIVIL DRAWINGS DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2022-09-16 05:54:26MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 4 Status P Date 2023-01-31 Cont ID  
Sent By kdefranc Date 2023-01-31 Time 13:40 Rev Time 0.00
Received By kdefranc Date 2023-01-31 Time 13:33 Sent To  
Notes
2023-01-31 13:33:361/31/23 ??? PASSED
  
 PREVIOUS REVIEW COMMENT TO BE ADDRESSED:
 1. REQUIRES PRIOR APPROVAL OF INFORMAL SITE PLAN REVIEW
 (ISPR) APPLICATION 22-02 (Z22030025). [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS TO BE ADDRESSED:
 2. PLEASE PROVIDE THE CONDITIONAL APPROVAL LETTER FOR
 ISPR 22-02 (Z22030025). [SATISFIED]
 3. PLEASE PROVIDE THE APPROVED PLANS AS
 LISTED/INDICATED IN THE CONDITIONAL APPROVAL LETTER FOR
 ISPR 22-02 (Z22030025). [SATISFIED]
 4. PLEASE REMOVE THE ARCHITECTURAL SITE PLAN (SHEET
 2.1) AND THE LANDSCAPE RELATED PLANS/SHEETS (TD-1,
 LP-1, LP-2, LP-3, LP-4) FROM THE SUBJECT PERMIT
 SUBMITTAL FILE. [SATISFIED]
 5. PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION FOR THE
 SUBJECT PROJECT. [SATISFIED]
 6. REQUIRES PRIOR APPROVAL OF SITE PLAN AMENDMENT FOR
 DETECTED CHANGES TO THE SITE PLAN.
  
 PROVISO:
 SHALL PROVIDE AS-BUILTS AND OBTAIN AN APPROVAL FOR THE
 AMENDMENTS TO THE APPROVED PLANS PRIOR TO ISSUANCE OF
 CERTIFICATE OF OCCUPANCY.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-12 Cont ID  
Sent By kdefranc Date 2023-01-12 Time 15:14 Rev Time 0.00
Received By kdefranc Date 2023-01-12 Time 15:14 Sent To  
Notes
2023-01-12 15:14:331/12/23 ??? FAILED
  
 PREVIOUS REVIEW COMMENT TO BE ADDRESSED:
 1. REQUIRES PRIOR APPROVAL OF INFORMAL SITE PLAN REVIEW
 (ISPR) APPLICATION 22-02 (Z22030025). [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS TO BE ADDRESSED:
 2. PLEASE PROVIDE THE CONDITIONAL APPROVAL LETTER FOR
 ISPR 22-02 (Z22030025).
 3. PLEASE PROVIDE THE APPROVED PLANS AS
 LISTED/INDICATED IN THE CONDITIONAL APPROVAL LETTER FOR
 ISPR 22-02 (Z22030025).
 4. PLEASE REMOVE THE ARCHITECTURAL SITE PLAN (SHEET
 2.1) AND THE LANDSCAPE RELATED PLANS/SHEETS (TD-1,
 LP-1, LP-2, LP-3, LP-4) FROM THE SUBJECT PERMIT
 SUBMITTAL FILE.
 5. PLEASE SUBMIT A LANDSCAPE PERMIT APPLICATION FOR THE
 SUBJECT PROJECT.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-144
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-22 Cont ID  
Sent By kdefranc Date 2022-11-22 Time 12:50 Rev Time 0.00
Received By kdefranc Date 2022-11-22 Time 12:50 Sent To  
Notes
2022-11-22 12:50:3411/22/22 ??? FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. REQUIRES PRIOR APPROVAL OF INFORMAL SITE PLAN REVIEW
 (ISPR) APPLICATION 22-02 (Z22030025). [NOT SATISFIED]
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-07 Cont ID  
Sent By kdefranc Date 2022-09-07 Time 15:37 Rev Time 0.00
Received By kdefranc Date 2022-09-07 Time 15:34 Sent To  
Notes
2022-09-07 15:36:409/7/22 - FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. REQUIRES PRIOR APPROVAL OF INFORMAL SITE PLAN REVIEW
 (ISPR) APPLICATION 22-02 (Z22030025).
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449