Plan Review Details - Permit 22080873
Plan Review Stops For Permit 22080873
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By cpuell Date 2022-10-21 Time 13:18 Rev Time 0.00
Received By cpuell Date 2022-10-21 Time 13:18 Sent To  
Notes
2022-10-21 13:18:57SUITE 304 ADDED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By cpuell Date 2022-10-06 Time 12:17 Rev Time 0.00
Received By cpuell Date 2022-10-06 Time 12:17 Sent To  
Notes
2022-10-06 12:18:02SUITE 304 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER
 QUESTIONS YOU CAN ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By jwitmer Date 2022-12-20 Time 14:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-15 Cont ID  
Sent By jwitmer Date 2022-11-15 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2022-11-15 Time 07:43 Sent To  
Notes
2022-11-15 09:13:06COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By jwitmer Date 2022-12-20 Time 14:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-15 Cont ID  
Sent By jwitmer Date 2022-11-15 Time 09:12 Rev Time 0.00
Received By jwitmer Date 2022-11-15 Time 07:43 Sent To  
Notes
2022-11-15 09:12:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080873
 ADD: 1818 S AUSTRALIAN AVE. # 304
 CONT: FOUR SEAS ENTERPRISES
 TEL: 561-315-2914
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 15TH/ 2022
 ACTION: DENIED
  
 1) LS-01:
 1A) THE OCCUPANCY CLASSIFICATION IS BUSINESS AND THE
 OCCUPANT LOAD FACTOR IS TAKEN @ 100 SQ. FT./ PERSON.
 PLEASE REVIEW THE 2020 FBC-BUILDING TABLE 1004.5, FOR
 BUSINESS THE OCCUPANT LOAD FACTOR IS TAKEN AT 150 SQ.
 FT./ PERSON, GROSS.
  
 1B) THE LARGE AND SMALL MEETING ROOMS DOES NOT SHOW
 TABLES AND CHAIRS OR THE PROPOSED OCCUPANT LOADS FOR
 THESE ROOMS. BETWEEN THE 35 CUBICLES, 16 CHAIRS IN THE
 BREAK ROOM AND UNKNOWN OCCUPANT LOAD OF THE MEETING
 ROOMS PLEASE DECLARE THE PROPOSED, NORMAL OCCUPANT LOAD
 FOR THIS SPACE IN ACCORDANCE WITH
 SECTION 1004.2 OF THE 2020 FBC-BUILDING.
  
 1C) NOTE IF THE INCREASED OCCUPANT LOAD IS OVER 49
 PERSONS, THEN 2 MEANS OF EGRESS WILL BE REQUIRED, AND
 THE 2 EXIT DOORS DOES NOT MEET THE 1/3RD DISTANCE
 APART, 2020 FBC-BUILDING CODE 1007.1.1 EXCEPTION (2).
  
 2) SHEET A211 DETAILS 1, 2 & 3 ALL SHOW THE CABINET
 ELEVATIONS WITH THE BASE CABINETRY AT 36 INCHES HIGH,
 FROM THE FINISHED FLOOR LEVEL TO THE TOP OF COUNTERTOP.
 2022 FBC-ACCESSIBILITY CODE SECTIONS:
  
 2A) 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2B) SINKS> 2020 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2C) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 2D) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By mpeterso Date 2022-12-20 Time 15:25 Rev Time 0.00
Received By mpeterso Date 2022-12-20 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By mpeterso Date 2022-10-25 Time 09:34 Rev Time 0.00
Received By mpeterso Date 2022-10-25 Time 09:33 Sent To  
Notes
2022-10-25 09:40:41ELECTRIC REVIEW FAILED
 1) THE ELECTRIC LOAD CALCULATION PROVIDED EXCEEDS THE
 RATING OF THE MAIN DISCONNECT OCP. NEC 220, NEC 215.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By cwalker Date 2022-12-16 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-12-16 08:15:02FIRE PROVISO COMMENT:
  
 (1) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE CONDUCTED BY PROPERLY
 LICENSED CONTRACTORS UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
  
 (3) ANY REMOVAL AND/OR REPLACEMENT OF CEILINGS AND/OR
 WALLS WILL REQUIRE AN EVALUATION OF ALL LIFE SAFETY
 SYSTEMS (FIRE SPRINKLER AND/OR FIRE ALARM) TO ENSURE
 CODE COMPLIANT COVERAGE IS MAINTAINED.
  
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-11 Cont ID  
Sent By cwalker Date 2022-10-11 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-10-11 10:47:47FIRE PROVISO COMMENTS:
  
 (1) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE CONDUCTED BY PROPERLY
 LICENSED CONTRACTORS UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS FOUR
 CONTINUOUS HOURS IN DURATION SHALL REQUIRE THE
 IMPLEMENTATION OF A FIRE WATCH.
  
 (3) ANY REMOVAL AND/OR REPLACEMENT OF CEILINGS AND/OR
 WALLS WILL REQUIRE AN EVALUATION OF ALL LIFE SAFETY
 SYSTEMS (FIRE SPRINKLER AND/OR FIRE ALARM) TO ENSURE
 CODE COMPLIANT COVERAGE IS MAINTAINED.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 09:16 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 07:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-11-15 Time   Rev Time 0.00
Received By cdecoeur Date 2022-10-06 Time 07:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-11-15 Cont ID  
Sent By jwitmer Date 2022-11-15 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2022-11-15 Time 07:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 09:15 Rev Time 0.00
Received By medwards Date 2022-12-21 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 17:04 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 17:04 Sent To  
Notes
2022-10-18 17:04:571ST REVIEW FMC
 PERMIT: 22080873
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M001: REVISE THE DRAWING TO SHOW THAT EACH HP
 CAN CONTROL THE REQUIRED OUTDOOR AIR WHILE THE BUILDING
 IS OCCUPIED. FMC 405.1
  
 2) SHEET M001: REVISE THE DRAWING TO SHOW THE SD ON THE
 SUPPLY SIDE OF HP-1 AND HP-2. FMC 606.2.2
  
 3) THE IGC CA 1 THIRD PARTY CERTIFICATE HAS EXPIRED FOR
 THE MECHANICAL DESIGNER SEAN M GEARY. PLEASE PROVIDE
 UPDATED DIGITAL SIGNATURE OF THE EOR. FS 471/481
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-12-16 Cont ID  
Sent By rwbrown Date 2022-12-16 Time 09:04 Rev Time 0.00
Received By rwbrown Date 2022-12-16 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-14 Cont ID  
Sent By rwbrown Date 2022-10-14 Time 12:41 Rev Time 0.00
Received By rwbrown Date 2022-10-14 Time 12:41 Sent To  
Notes
2022-10-14 12:43:461ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, THE DEVICE SHALL MEET THE ASSE 1017
 STANDARD AND BE INSTALLED AT THE HOT WATER SOURCE PER
 613.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By mpeterso Date 2022-12-20 Time 15:27 Rev Time 0.00
Received By mpeterso Date 2022-12-20 Time 15:27 Sent To  
Notes
2022-12-20 14:23:12ARCHITECTURAL SHEETS GOOD 12/20/22 JWITMER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-11-15 Time 09:25 Rev Time  
Received By   Date   Time   Sent To  
Notes
2022-11-15 09:25:56SEE MECHANICAL PAGES
2022-10-18 17:05:35 THE IGC CA 1 THIRD PARTY CERTIFICATE HAS EXPIRED FOR
 THE MECHANICAL DESIGNER SEAN M GEARY. PLEASE PROVIDE
 UPDATED DIGITAL SIGNATURE OF THE EOR. FS 471/481