Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-16 Cont ID  
Sent By pleduc Date 2022-08-16 Time   Rev Time 0.00
Received By pleduc Date 2022-08-16 Time 12:12 Sent To  
Notes
2022-08-16 12:12:32THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE INDICATIONS THAT A DUCT DETECTOR WILL
 CAUSE A FULL FIRE ALARM ACTIVATION. NFPA PROVIDES CODE
 REFERENCES FOR SUPERVISORY SIGNAL ACTIVATION.
  
 PER NFPA 90A
  
 6.4 SMOKE DETECTION FOR AUTOMATIC CONTROL
  
 6.4.2 LOCATION
  
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
  
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY OF GREATER THAT 944 L/SEC(2000FT3/MIN.)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OF FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVE A CAPACITY
 GREATER THAN 7080L/SEC(15.000FT3/MIN) AND SERVING MORE
 THAN ONE STORY.
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4 INSTALLATION
  
 6.4.4.1 SMOKE DETECTORS SHALL BE INSTALLED, TESTED, AND
 MAINTAINED IN ACCORDANCE WITH NFPA 72.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4
 ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN
 APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE
 FOLLOWING SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED
  
 AND
  
 PER NFPA 72, 2016 ED
 CHAPTER 21 EMERGENCY CONTROL FUNCTION INTERFACES
 21.7 HEATING, VENTILATING AND AIR-CONDITIONING (HVAC)
 SYSTEMS.
 21.7.1 THE PROVISIONS OF SECTION SHALL APPLY TO THE
 BASIC METHOD BY WHICH A FIRE ALARM SYSTEM INTERFACES
 WITH THE HEATING, VENTILATING, AND AIR-CONDITIONING
 (HVAC) SYSTEM
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL
  
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET
 THE REQUIREMENTS OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
  
 PLEASE ENSURE THAT THESE DUCT DETECTORS ARE APPLICABLE
 TO CODE TO SEND A SUPERVISORY SIGNAL AND PROGRAM
 ACCORDINGLY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-02 Cont ID  
Sent By jleahy Date 2022-09-02 Time 08:57 Rev Time 0.00
Received By jleahy Date 2022-08-16 Time 05:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-08-24 Cont ID  
Sent By medwards Date 2022-08-24 Time 05:56 Rev Time 0.00
Received By medwards Date 2022-08-24 Time 05:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-24 Cont ID  
Sent By medwards Date 2022-08-24 Time 05:56 Rev Time 0.00
Received By medwards Date 2022-08-24 Time 05:56 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved